09
Specifications
Global Fire Equipment S.A.
MARF - Armazens F3 e F4, Sítio do Guelhim, Estoi, 8009-021 FARO, PORTUGAL
Tel: + 351 289 896 560 Fax: + 351 289 865 587
Sales
Technical Support
Technical Specifications
Supply Input
Supply Output
Current Output
Battery Charger - Current O/P
Battery
Battery Charger Monitored
Battery Fuse
I/O Unit - Loop Current
Address Range
Fault Relay
Supply Relay
Dimensions
Weight
Operating Temperature
Storage Temperature
Humidity/ Protection
28.5 V DC - Monitored
28V DC
10A max. @ 28V DC nominal
4A max.
N/A
YES
10A
1.7mA Quiescent - 2.4mA Fault
1-125
Changeover-30V DC 1A Resistive
Changeover-240V AC 10A Resistive
131(W) x 81(W) x 41(H) mm
225 g
0ºC to +40ºC
N/A
85-265 V AC - Monitored
28 V DC
1.7A OR 2.4A @ 28 V DC nominal
1A max.
Max. 2 x 12V 7 AH - Lead Acid VRLA
YES
3A
1.7mA Quiescent - 2.4mA Fault
1-125
Changeover-30V DC 1A Resistive
Changeover-240V AC 10A Resistive
0ºC to +40ºC
-10 to +50ºC
max 85% no condensation - IP21
242(W) x 404(H) x 107(D) mm
1.7 Kg - 7 Kg inc. 2 x 7AH Bat.
GFE-BCM-3
GFE-BCM-10
-10 to +50ºC
Order Code
BATTERY CHARGER MODULE - INCLUDING CHASSIS
BATTERY CHARGER MODULE - I/O INC. - 28V DC 1.7A PSU - BOXED
BATTERY CHARGER MODULE - I/O INC. - 28V DC 2.4A PSU - BOXED
BATTERY CHARGER MODULE - 28V DC 1.7A PSU - BOXED
BATTERY CHARGER MODULE - 28V DC 2.4A PSU - BOXED
GFE-BCM-10
GFE-BCM-3-I/O (1.7A)
GFE-BCM-3-I/O (2.4A)
GFE-BCM-3 (1.7A)
GFE-BCM-3 (2.4A)
Manufacturers of Fire Detection Equipment
Manufacturers of Fire Detection Equipment
GFE-BCM
131.0 mm
81.0 mm
107
242.0 mm
404.0 mm
K1
F1
Battery Fuse
L2
L1
SPLY IN
CN2
ADDRESS
1
2
3
4
5
6
7
8
- +
BA
T
K2
BAT FLT
CHAR FLT
- +
OUT
- +
24V IN
NC C NO
FA
UL
T RELA
Y
OUTPUT RELA
Y
NC C NO
1
2
3
INSTALLATION MANUAL
Version 2.0 - 12/2010