Global Fire Equipment GFE-BCM Series Installation Manual Download Page 5

05

Settings

Manufacturers of Fire Detection Equipment

GFE-BCM

1

2

3

1

2

3

Conventional

SW 1 - ON
SW 2 - ON

Addressable

SW 1 - OFF
SW 2 - OFF

SW 3 - OFF 

When OFF the module will monitor the battery voltage and it will disconnect battery when 
below 21V DC avoiding deep discharge.

SW 3 - ON

In this case the battery voltage monitoring is disabled.

1

2

3

1

2

3

SW 3 - OFF 

SW 3 - ON 

SPLY IN

BAT FLT

CHAR FLT

ON when supply input is present.

ON when battery charger is faulty or batteries are not connected 
or faulty.

ON when battery voltage is below 21 V DC.

INSTALLATION  MANUAL

Version 2.0 - 12/2010

Addressable IO Unit

Units fitted with a built-in addressable IO unit can be directly connected to a device loop on any 
of GFE’s  addressable panels, via the loop connections. These devices will be monitored directly 
by the panel.

When fitted, these units will be displayed as IO units and its analogue value monitored by the 
panel. When there are no faults on the BCM unit the analogue value reported by the device to 
the panel is 16 and when in fault condition is 2.

When the device is showing a fault condition, which is always associated with either a fault in 
the battery charger or battery voltage as monitored by the module, the panel will also indicate 
this condition locally by turning ON the GENERAL FAULT and SUPPLY FAULT LEDs. The LCD of 
the panel will also display the location of module with a clear indication of both Loop and Device 
Address and its associated text label.

Activation of the relay output is accomplished by including the unit in an  IO Group. This group 
can then be assigned to either a zone or device. Please refer to the Installation Manual of the 
panel  being  used  for  further  information  regarding  cause  and  effect  programming  and 
functions associated with IO units and groups.

Summary of Contents for GFE-BCM Series

Page 1: ...INSTALLATION MANUAL Version 2 0 11 2010 Manufacturers of Fire Detection Equipment GFE BCM Battery Charger Monitor Manufacturers of Fire Detection Equipment ...

Page 2: ...n Battery charge is fully monitored and current output controlled and limited to a maximum of 4 Amps Two auxillirary output relays are provided both equipped with a set of changeover contacts One is used to signal fault conditions The Output relay which is only available for addressable versions can be used when included in an IO Group FEATURES l Battery Charger Monitored by Addressable Panel l Fa...

Page 3: ...al for further details Fault Relay Terminal Connections A single pole changeover relay is provided Activation of relay is caused by any fault detected within the monitoring circuitry of the module When device is in fault condition the analogue value reported to the panel is 2 and it is indicated by the panel as a supply fault In these cases both the GENERAL and SUPPLY FAULTS LEDs are ON Location o...

Page 4: ... manual Maximum battery capacity for boxed units is 2 x 12V 7Ah batteries Supply Output Terminal Connections This output supplies a nominal voltage value of 28V DC Current drive capacity depends on module specification Supply Input Terminal Connections Fault Relay Terminal Connections A single pole changeover relay is provided Activation of relay is caused by any fault detected within the monitori...

Page 5: ...ly by the panel When fitted these units will be displayed as IO units and its analogue value monitored by the panel When there are no faults on the BCM unit the analogue value reported by the device to the panel is 16 and when in fault condition is 2 When the device is showing a fault condition which is always associated with either a fault in the battery charger or battery voltage as monitored by...

Page 6: ...primary supply should fail it also provides a charging output to maintain the batteries in a fully charged state Before connecting the batteries check the voltage across the battery connection terminals It should be 28 0V 0 5V Note arcing and fire risk Never short circuit the battery terminals Always connect the blue wire between the batteries last BLACK RED BLUE F1 Battery Fuse BAT OUT 24V IN A B...

Page 7: ...5 6 7 8 1 2 3 4 5 6 7 8 113 114 115 116 117 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 100 101 102 103 104 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 109 110 111 112 1 2 3 4 5 6 7 8 55 1 2 3 4 5 6 7 8 56 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 46 47 48 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 37 38 39 40 1 2 3...

Page 8: ...y Lead Acid VRLA 2 x 12V DC 7 AH CONTROL MODULE GFE BCM 3 Electronic Module Fixing Holes Electrical Mains Fused Connector Manufacturers of Fire Detection Equipment GFE BCM Manufacturers of Fire Detection Equipment GFE BCM K1 F1 Battery Fuse L2 L1 SPLY IN CN2 ADDRESS 1 2 3 4 5 6 7 8 BAT K2 BAT FLT CHAR FLT OUT 24V IN NC C NO FAULT RELAY OUTPUT RELAY NC C NO 1 2 3 INSTALLATION MANUAL Version 2 0 12 ...

Page 9: ... 7A OR 2 4A 28 V DC nominal 1A max Max 2 x 12V 7 AH Lead Acid VRLA YES 3A 1 7mA Quiescent 2 4mA Fault 1 125 Changeover 30V DC 1A Resistive Changeover 240V AC 10A Resistive 0ºC to 40ºC 10 to 50ºC max 85 no condensation IP21 242 W x 404 H x 107 D mm 1 7 Kg 7 Kg inc 2 x 7AH Bat GFE BCM 3 GFE BCM 10 10 to 50ºC Order Code BATTERY CHARGER MODULE INCLUDING CHASSIS BATTERY CHARGER MODULE I O INC 28V DC 1 ...