Cleaning / maintenance

9.1 Maintenance

To protect the paintwork, avoid leaning anything against the
device or putting objects on the device. External heat pump
parts can be wiped with a damp cloth and domestic cleaner.

NOTE

ººººº

Never use cleaning agents containing sand, soda, acid or
chloride as these can damage the surfaces.

To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating sys-
tem cannot be contaminated. In the event that operating mal-
functions due to contamination still occur, the system should
be cleaned as described below.

9.2 Cleaning the heating system

CAUTION!

!!

The installed dirt traps must be cleaned at regular intervals.

The maintenance intervals should be defined according to the
degree of soiling in the system. The filter insert should also be
cleaned.
For cleaning, the heating circuit must be made pressureless in
the vicinity of the dirt trap, the filter compartment unscrewed,
and the filter insert removed and cleaned. Assembly carried out
in reverse order requires attention to correct assembly of the
screen inserts and tightness of the screw joints.
The ingress of oxygen into the heating water circuit may result
in the formation of oxidation products (rust), particularly if steel
components are used. They enter the heating system via the
valves, the circulating pumps and/or plastic pipes. It is there-
fore essential - in particular with respect to the entire pipework
- that only diffusion-resistant materials are used.

NOTE

ººººº

We recommend the installation of a suitable corrosion
protection system to prevent the formation of deposits (e.g.
rust) in the condenser of the heat pump. We recommend
equipping diffusion-open heating systems with an
electrophysical anti-corrosion system (e.g. ELYSATOR
system).

Residue from lubricants and sealants may also contaminate the
heating water.
In the case of severe contamination leading to a reduction in
the performance of the liquefier in the heat pump, the system
must be cleaned by a heating technician.
Based on current knowledge, we recommend carrying out the
cleaning with a 5 % phosphor acid or, if more frequent cleaning
is required, with a 5 % formic acid.
In either case, the cleaning fluid should be at room tempera-
ture. We recommend flushing the heat exchanger in the direc-
tion opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating
system circuit, we recommend connecting the flushing device
directly to the flow and return of the liquefier of the heat pump.
It is then important that the system be thoroughly flushed using
appropriate neutralising agents to prevent any damage from
being caused by cleaning agent residue remaining in the sys-
tem.
Acids must be used with care and the regulations of the em-
ployers’ liability insurance associations must be adhered to.
The manufacturer's instructions regarding cleaning agent must
be complied with at all times.

Summary of Contents for LA 60S-TUR

Page 1: ...e und Gebrauchsanweisung Luft Wasser W rmepumpe f r Au enaufstellung Installation and Operating Instruction Air to Water Heat Pump for Outdoor Installation Instuctionsd installation et d utilisation P...

Page 2: ......

Page 3: ...2 Kondensatleitung DE 6 7 Montage DE 6 7 1 Allgemein DE 6 7 2 Heizungsseitiger Anschluss DE 7 7 3 Elektrischer Anschluss DE 8 8 Inbetriebnahme DE 8 8 1 Allgemein DE 8 8 2 Vorbereitung DE 8 8 3 Vorgehe...

Page 4: ...talen F higkeiten oder Mangel an Erfahrung und Wissen benutzt werden wenn sie beaufsichtigt oder bez glich des si cheren Gebrauchs des Ger tes unterwiesen wurden und die daraus resultierenden Gefahren...

Page 5: ...hlt die Luft ab d h er entzieht ihr W rme Die gewonnene W rme wird im Verdampfer auf das Arbeitsmedium K ltemit tel bertragen Mit Hilfe der elektrisch angetriebenen Verdichter wird die auf genommene...

Page 6: ...g und dem L sen der sich links oben befindenden Befestigungsschraube kann der Schaltkasten herausgeklappt werden Im Schaltkasten befinden sich die Netzanschlussklemmen sowie die Leistungssch tze und d...

Page 7: ...ehalten Eine genaue Beschreibung des Einbaus ist der dem Ventil beiliegenden Anweisung zu ent nehmen HINWEIS Bei Nutzung der W rmepumpe mit dem externen 4 Wege Umschaltventil ist es zwingend erforderl...

Page 8: ...r Einzelaufstellung ACHTUNG Der Ansaug und Ausblasbereich darf nicht eingeengt oder zugestellt werden ACHTUNG L nderspezifische Bauvorschriften sind zu beachten ACHTUNG Bei wandnaher Aufstellung sind...

Page 9: ...m 4 Wege Umschaltven til ist es zwingend erforderlich die hydraulischen Anschl sse gem der dem Ventil beiliegenden Anweisung herzustellen Die Anweisung beschreibt die genauere Vorgehensweise beim Aufb...

Page 10: ...rechung mit dem W rmepumpenma nager auch keine Regelung des 2 W rmeerzeuger m glich HINWEIS Der in der W rmepumpe eingebaute R cklauff hler R2 ist bei laufendem Verdichter aktiv und darf nicht abgekle...

Page 11: ...Umw lzpumpen oder Kunst stoffrohre in das Heizsystem Deshalb sollte besonders bei der kompletten Verrohrung auf eine diffusionsdichte Installation geachtet werden HINWEIS Zur Vermeidung von Ablagerun...

Page 12: ...oberen Bleche sind am Deckelblech eingehakt Zur Demon tage werden die beiden Schrauben gel st und die Bleche durch Zur ckziehen ausgeh ngt 10 St rungen Fehlersuche Diese W rmepumpe ist ein Qualit tsp...

Page 13: ...g Ausblasseite 6 Normalbetrieb abgesenkter Betrieb 5 dB A 44 38 4 5 Luftdurchsatz Regelbereich EC L fter m h 0 25000 5 Abmessungen Gewicht und F llmengen 5 1 Ger teabmessungen ohne Anschl sse7 H x B x...

Page 14: ...ngestelltem Mindestheizwasserdurchsatz 3 Die minimal erreichbare Vorlauftemperatur h ngt vom aktuellen Volumenstrom der eingestellten R cklaufsolltemperatur und der aktuellen Leistungsstufe ab 4 Ergib...

Page 15: ...kWh Angegebenes Lastprofil Warmwasserbereitungs Energieeffizienz wh T glicher Stromverbrauch Qelec kWh T glicher Brennstoffverbrauch Qfuel kWh Kontakt Wird der Cdh Wert nicht durch Messung bestimmt g...

Page 16: ...le zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert verg ten Im Fa...

Page 17: ...densate pipe EN 6 7 Assembly EN 6 7 1 General EN 6 7 2 Connection on heating side EN 7 7 3 Electrical connection EN 8 8 Start up EN 8 8 1 General EN 8 8 2 Preparation EN 8 8 3 Procedure EN 8 9 Cleanin...

Page 18: ...sory or mental aptitude or lack of experience and or knowledge providing they are supervised or have been instructed in the safe use of the unit and understand the associated potential dangers Childre...

Page 19: ...e it ex tracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is brought to a higher temperature level by increasing its pressure wit...

Page 20: ...out after removing the lower front cover and loosening the fasten ing screw located in the upper left hand corner The switch box contains the supply connection terminals as well the power contactors...

Page 21: ...its are only fulfilled in combination with this accessory A detailed installation descrip tion can be found in the instructions included with the valve NOTE For operation of the heat pump with the ext...

Page 22: ...or stand alone installation only CAUTION Do not restrict or block the area around the air intake or outlet CAUTION Observe country specific building regulations CAUTION For installation close to walls...

Page 23: ...e it is essential to set up the hydraulic connections accord ing to the instructions included in the scope of supply of the valve The instructions give a description of the precise proce dure for the...

Page 24: ...If a demand sensor is not connected the second heat genera tor can not be controlled with the heat pump manager in the event of an interruption in communication either NOTE The return sensor R2 instal...

Page 25: ...s the circulating pumps and or plastic pipes It is there fore essential in particular with respect to the entire pipework that only diffusion resistant materials are used NOTE We recommend the install...

Page 26: ...r panel Loosen the two screws for dismantling and unhook the panels by pulling them back 10 Faults troubleshooting This heat pump is a quality product and is designed for trouble free operation In the...

Page 27: ...peration reduced operation 5 dB A 44 38 4 5 Air flow controlling range EC fan m h 0 25000 5 Dimensions weight and filling quantities 5 1 Device dimensions without connections7 H x W x L mm 2300 x 1900...

Page 28: ...ies to a set minimum heating water flow 3 The minimum achievable flow temperature depends on the current volume flow the set return set temperature and the current performance level 4 In 2 compressor...

Page 29: ...missions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not d...

Page 30: ...EN 14 452163 66 79 FD 0003 www glendimplex de English LA 60S TUR...

Page 31: ...6 2 Conduite d coulement des condensats FR 6 7 Montage FR 6 7 1 G n ralit s FR 6 7 2 Raccordement c t chauffage FR 7 7 3 Branchements lectriques FR 8 8 Mise en service FR 9 8 1 G n ralit s FR 9 8 2 Pr...

Page 32: ...lance d une personne exp riment e et si elles ont t infor m es des r gles de s curit l utilisation de l appareil et ont compris les risques encourus Ne laissez pas les enfants jouer avec l appareil Ne...

Page 33: ...hermique L vaporateur refroi dit l air par extraction de chaleur La chaleur ainsi obtenue est transmise au fluide utilis fluide frigorig ne dans l vapora teur l aide d un compresseur commande lectriqu...

Page 34: ...nlev l habillage frontal inf rieur et d viss la vis de fixation se trouvant en haut gauche Dans le bo tier lectrique se trouvent les bornes de branchement secteur ainsi que les contacteurs de puissanc...

Page 35: ...e sont respect es qu avec cet accessoire Les instructions jointes la vanne contiennent une description pr cise de son montage ATTENTION En cas d utilisation de la pompe chaleur avec la vanne d inversi...

Page 36: ...uation d air ne doivent tre ni r tr cis ni obtur s ATTENTION Respecter les r gles de construction sp cifiques chaque pays ATTENTION En cas d installation pr s d un mur tenir compte des influences phys...

Page 37: ...tion de chauffage ATTENTION Il faut veiller dans le cas d eau enti rement d min ralis e ce que le seuil inf rieur admis pour la valeur pH minimale de 7 5 valeur minimale admise pour le cuivre ne soit...

Page 38: ...on contre les courts circuits en tenant compte du dimensionnement du c blage interne Les composants concern s de la pompe chaleur in t grent un limiteur de surcharge Lors du raccordement garantir la r...

Page 39: ...ien Il faut viter d appuyer ou de d poser des objets sur l appareil afin de prot ger la peinture Les parties ext rieures de la pompe chaleur peuvent tre essuy es avec un linge humide et des produits n...

Page 40: ...imal des condensats Il est possible de retirer toutes les t les de surface pour acc der l int rieur de l appareil Ouvrir pour cela les deux tourniquets Le couvercle peut ensuite tre sorti par le haut...

Page 41: ...44 38 4 5 D bit d air plage de r gulation ventilateur EC m h 0 25000 5 Dimensions poids et capacit s 5 1 Dimensions de l appareil sans raccordement7 H x l x L en mm 2300 x 1900 x 1000 5 2 Poids de de...

Page 42: ...fage r gl 3 La temp rature d part minimale possible d pend du flux volumique actuel de la valeur consigne de la temp rature retour r gl e et du niveau de puissance actuel 4 En mode de fonctionnement 2...

Page 43: ...sommation journali re de combustible Qfuel kWh Coordonn es de contact Si le Cdh n est pas d termin par des mesures le coefficient de d gradation par d faut est Cdh 0 9 non applicable Pour les disposit...

Page 44: ...FR 14 452163 66 79 FD 0003 www glendimplex de Fran ais LA 60S TUR...

Page 45: ...ooling operation Courbes caract ristiques mode rafra chissement A IV 2 3 Einsatzgrenzendiagramm Heizen Operating limits diagram heating Diagramme des seuils d utilisation chauffage A V 2 4 Einsatzgren...

Page 46: ...l around sur la circonf rence 1 Heizwasservorlauf Ausgang aus W rmepumpe R 2 2 Heizwasserr cklauf Eingang in W rmepumpe R 2 3 Durchf hrungsbereich Elektroleitungen Kondensat 5 Optionale Durchf hrung E...

Page 47: ...ungsanteil Coefficient of performance incl power input to pump Coefficient de performance y compris part de consommation de la pompe 45 55 0 5 10 15 20 25 30 35 40 45 50 55 60 65 25 20 15 10 5 0 5 10...

Page 48: ...Cooling capacity in kW Puissance de refroidissement en kW 0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 0 1 2 3 4 5 6 7 8 9 10 11 Druckverlust in Pa Pressure loss in Pa Perte de p...

Page 49: ...eforderten Mindestheizwasserdurchfluss erreicht The values specified are valid for the hydraulic 4 way reversing valve The operating range is reduced if the 4 way reversing valve is not used Max heati...

Page 50: ...p m e t r e t a w g n i l o o C C t n e m e s s i h c a r f a r e d u a e d e r u t a r p m e T C C W rmesenkeneintrittstemperatur C Heat sink inlet temperature C Temp rature d entr e de dissipation...

Page 51: ...Anhang Appendix Annexes 3 Einbindungsschemen Integration diagram Sch ma d int gration 3 1 Hydraulische Einbindungsschemen Hydraulic integration diagrams Sch mas d int gration hydraulique R3 R2 1 R1 E9...

Page 52: ...r cylinder R servoir d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 1 Tauchheizk rper Immersion heater R sistance immerg e K20 Sch tz 2 W rmee...

Page 53: ...erkl rung Declaration of Conformity D claration de conformit Die aktuelle CE Konformit tserkl rung finden sie als Download unter You can find and download the current CE conformity declaration at Vous...

Page 54: ...A X 452163 66 79 FD 0003 www glendimplex de Anhang Appendix Annexes LA 60S TUR...

Page 55: ...www glendimplex de 452163 66 79 FD 0003 A XI LA 60S TUR Anhang Appendix Annexes...

Page 56: ...hland GmbH Gesch ftsbereich GDTS Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 924545...

Reviews: