Glen Dimplex LA 60S-TUR Installation And Operating Instruction Download Page 23

www.glendimplex.de

452163.66.79 · FD 0003

EN-7

LA 60S-TUR 

English

7.2 Connection on heating side

The heating system connections on the heat pump are to be
made inside the device. Refer to the device information for the
connection sizes. Route the connection hoses out of the device
in a downwards direction. An optional pipe kit is available as an
accessory, which can be used to lead the connections out to
the side. 
Use a spanner to firmly grip the transitions when connecting
the heat pump.
Before connecting the heating water system to the heat pump,
the heating system must be flushed to remove any impurities,
residue from sealants, etc. Any accumulation of deposits in the
liquefier could cause the heat pump to completely break down.
Once the heat pump has been connected to the heating sys-
tem, it must be filled, de-aerated and pressure-tested.
Consideration must be given to the following when filling the
system:

Untreated filling water and make-up water must be of
drinking water quality (colourless, clear, free from sedi-
ments)

Filling water and make-up water must be pre-filtered (pore
size max. 5 µm).

Scale formation in domestic hot water heating systems cannot
be avoided, but in systems with flow temperatures below 60 °C,
the problem can be disregarded. With high-temperature heat
pumps and in particular with bivalent systems in the higher per-
formance range (heat pump + boiler combination), flow tem-
peratures of 60 °C and more can be achieved. The following
standard values should therefore be adhered to with regard to
the filling and make-up water according to VDI 2035, sheet 1:
The total hardness values can be found in the table.

Fig. 7.1:Guideline values for filling and make-up water in accordance with

VDI 2035

For systems with an above-average specific system volume of
50 l/kW, VDI 2035 recommends using fully demineralized
water and a pH stabiliser to minimize the risk of corrosion in the
heat pump and the heating system.

CAUTION!

!!

With fully demineralized water, it is important to ensure that
the minimum permissible pH value of 7.5 (minimum
permissible value for copper) is complied with. Failure to
comply with this value can result in the heat pump being
destroyed.

Note:

For operation of the heat pump with the four-way reversing
valve, it is essential to set up the hydraulic connections accord-
ing to the instructions included in the scope of supply of the
valve. The instructions give a description of the precise proce-
dure for the correct assembly of hydraulics. Non-observance of
this will lead to restrictions in the operation of the heat pump.

Important:

The notes/settings in the instructions of the heat pump man-
ager must always be observed and carried out accordingly; not
doing so will lead to malfunctions.

Minimum heating water flow

The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished, for example, by installing either a
dual differential pressureless manifold or an overflow valve. The
procedure for setting an overflow valve is described in the
chapter "Start-up". When the minimum heating water flow rate
is undershot, the plate heat exchanger in the refrigeration cir-
cuit can freeze, which can lead to total loss of the heat pump.
The nominal flow rate is specified depending on the max. flow
temperature in the device information and must be taken into
account during planning. With design temperatures below 30 C
in the flow, the design must be based on the max. volume flow
with 5 K spread for A7/W35.
The specified nominal flow rate (See “Device information” on
page 11.) m
ust be guaranteed in every operating status. An in-
stalled flow rate switch is used only for switching off the heat
pump in the event of an unusual and abrupt drop in the heating
water flow rate and not to monitor and safeguard the nominal
flow rate.

Antifreeze

Heat pump systems, which cannot be guaranteed to be frost-
free, should be equipped with a drainage option (see Fig.). The
antifreeze function of the heat pump manager is active when-
ever the heat pump manager and the heat circulating pump are
ready for operation. The system has to be drained if the heat
pump is taken out of service or in the event of a power failure.
The heating circuit should be operated with a suitable anti-
freeze if heat pump systems are implemented in buildings
where a power failure cannot be detected (holiday home).

Total heat 

output in kW

Total alkaline earths 

in mol/m³ and/or 

mmol/l

Specific system volume 

(VDI 2035) in l/kW

< 20



20  < 50



50

Total hardness in °dH

< 50



2,0



16,8



11,2

< 0,11

1

50 - 200



2,0

 11,2



8,4

200 - 600



1,5



8,4

< 0,11

1

 > 600

< 0,02

< 0,11

1

1. This value lies outside the permissible value for heat exchangers in heat

pumps.

Summary of Contents for LA 60S-TUR

Page 1: ...e und Gebrauchsanweisung Luft Wasser W rmepumpe f r Au enaufstellung Installation and Operating Instruction Air to Water Heat Pump for Outdoor Installation Instuctionsd installation et d utilisation P...

Page 2: ......

Page 3: ...2 Kondensatleitung DE 6 7 Montage DE 6 7 1 Allgemein DE 6 7 2 Heizungsseitiger Anschluss DE 7 7 3 Elektrischer Anschluss DE 8 8 Inbetriebnahme DE 8 8 1 Allgemein DE 8 8 2 Vorbereitung DE 8 8 3 Vorgehe...

Page 4: ...talen F higkeiten oder Mangel an Erfahrung und Wissen benutzt werden wenn sie beaufsichtigt oder bez glich des si cheren Gebrauchs des Ger tes unterwiesen wurden und die daraus resultierenden Gefahren...

Page 5: ...hlt die Luft ab d h er entzieht ihr W rme Die gewonnene W rme wird im Verdampfer auf das Arbeitsmedium K ltemit tel bertragen Mit Hilfe der elektrisch angetriebenen Verdichter wird die auf genommene...

Page 6: ...g und dem L sen der sich links oben befindenden Befestigungsschraube kann der Schaltkasten herausgeklappt werden Im Schaltkasten befinden sich die Netzanschlussklemmen sowie die Leistungssch tze und d...

Page 7: ...ehalten Eine genaue Beschreibung des Einbaus ist der dem Ventil beiliegenden Anweisung zu ent nehmen HINWEIS Bei Nutzung der W rmepumpe mit dem externen 4 Wege Umschaltventil ist es zwingend erforderl...

Page 8: ...r Einzelaufstellung ACHTUNG Der Ansaug und Ausblasbereich darf nicht eingeengt oder zugestellt werden ACHTUNG L nderspezifische Bauvorschriften sind zu beachten ACHTUNG Bei wandnaher Aufstellung sind...

Page 9: ...m 4 Wege Umschaltven til ist es zwingend erforderlich die hydraulischen Anschl sse gem der dem Ventil beiliegenden Anweisung herzustellen Die Anweisung beschreibt die genauere Vorgehensweise beim Aufb...

Page 10: ...rechung mit dem W rmepumpenma nager auch keine Regelung des 2 W rmeerzeuger m glich HINWEIS Der in der W rmepumpe eingebaute R cklauff hler R2 ist bei laufendem Verdichter aktiv und darf nicht abgekle...

Page 11: ...Umw lzpumpen oder Kunst stoffrohre in das Heizsystem Deshalb sollte besonders bei der kompletten Verrohrung auf eine diffusionsdichte Installation geachtet werden HINWEIS Zur Vermeidung von Ablagerun...

Page 12: ...oberen Bleche sind am Deckelblech eingehakt Zur Demon tage werden die beiden Schrauben gel st und die Bleche durch Zur ckziehen ausgeh ngt 10 St rungen Fehlersuche Diese W rmepumpe ist ein Qualit tsp...

Page 13: ...g Ausblasseite 6 Normalbetrieb abgesenkter Betrieb 5 dB A 44 38 4 5 Luftdurchsatz Regelbereich EC L fter m h 0 25000 5 Abmessungen Gewicht und F llmengen 5 1 Ger teabmessungen ohne Anschl sse7 H x B x...

Page 14: ...ngestelltem Mindestheizwasserdurchsatz 3 Die minimal erreichbare Vorlauftemperatur h ngt vom aktuellen Volumenstrom der eingestellten R cklaufsolltemperatur und der aktuellen Leistungsstufe ab 4 Ergib...

Page 15: ...kWh Angegebenes Lastprofil Warmwasserbereitungs Energieeffizienz wh T glicher Stromverbrauch Qelec kWh T glicher Brennstoffverbrauch Qfuel kWh Kontakt Wird der Cdh Wert nicht durch Messung bestimmt g...

Page 16: ...le zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert verg ten Im Fa...

Page 17: ...densate pipe EN 6 7 Assembly EN 6 7 1 General EN 6 7 2 Connection on heating side EN 7 7 3 Electrical connection EN 8 8 Start up EN 8 8 1 General EN 8 8 2 Preparation EN 8 8 3 Procedure EN 8 9 Cleanin...

Page 18: ...sory or mental aptitude or lack of experience and or knowledge providing they are supervised or have been instructed in the safe use of the unit and understand the associated potential dangers Childre...

Page 19: ...e it ex tracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is brought to a higher temperature level by increasing its pressure wit...

Page 20: ...out after removing the lower front cover and loosening the fasten ing screw located in the upper left hand corner The switch box contains the supply connection terminals as well the power contactors...

Page 21: ...its are only fulfilled in combination with this accessory A detailed installation descrip tion can be found in the instructions included with the valve NOTE For operation of the heat pump with the ext...

Page 22: ...or stand alone installation only CAUTION Do not restrict or block the area around the air intake or outlet CAUTION Observe country specific building regulations CAUTION For installation close to walls...

Page 23: ...e it is essential to set up the hydraulic connections accord ing to the instructions included in the scope of supply of the valve The instructions give a description of the precise proce dure for the...

Page 24: ...If a demand sensor is not connected the second heat genera tor can not be controlled with the heat pump manager in the event of an interruption in communication either NOTE The return sensor R2 instal...

Page 25: ...s the circulating pumps and or plastic pipes It is there fore essential in particular with respect to the entire pipework that only diffusion resistant materials are used NOTE We recommend the install...

Page 26: ...r panel Loosen the two screws for dismantling and unhook the panels by pulling them back 10 Faults troubleshooting This heat pump is a quality product and is designed for trouble free operation In the...

Page 27: ...peration reduced operation 5 dB A 44 38 4 5 Air flow controlling range EC fan m h 0 25000 5 Dimensions weight and filling quantities 5 1 Device dimensions without connections7 H x W x L mm 2300 x 1900...

Page 28: ...ies to a set minimum heating water flow 3 The minimum achievable flow temperature depends on the current volume flow the set return set temperature and the current performance level 4 In 2 compressor...

Page 29: ...missions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not d...

Page 30: ...EN 14 452163 66 79 FD 0003 www glendimplex de English LA 60S TUR...

Page 31: ...6 2 Conduite d coulement des condensats FR 6 7 Montage FR 6 7 1 G n ralit s FR 6 7 2 Raccordement c t chauffage FR 7 7 3 Branchements lectriques FR 8 8 Mise en service FR 9 8 1 G n ralit s FR 9 8 2 Pr...

Page 32: ...lance d une personne exp riment e et si elles ont t infor m es des r gles de s curit l utilisation de l appareil et ont compris les risques encourus Ne laissez pas les enfants jouer avec l appareil Ne...

Page 33: ...hermique L vaporateur refroi dit l air par extraction de chaleur La chaleur ainsi obtenue est transmise au fluide utilis fluide frigorig ne dans l vapora teur l aide d un compresseur commande lectriqu...

Page 34: ...nlev l habillage frontal inf rieur et d viss la vis de fixation se trouvant en haut gauche Dans le bo tier lectrique se trouvent les bornes de branchement secteur ainsi que les contacteurs de puissanc...

Page 35: ...e sont respect es qu avec cet accessoire Les instructions jointes la vanne contiennent une description pr cise de son montage ATTENTION En cas d utilisation de la pompe chaleur avec la vanne d inversi...

Page 36: ...uation d air ne doivent tre ni r tr cis ni obtur s ATTENTION Respecter les r gles de construction sp cifiques chaque pays ATTENTION En cas d installation pr s d un mur tenir compte des influences phys...

Page 37: ...tion de chauffage ATTENTION Il faut veiller dans le cas d eau enti rement d min ralis e ce que le seuil inf rieur admis pour la valeur pH minimale de 7 5 valeur minimale admise pour le cuivre ne soit...

Page 38: ...on contre les courts circuits en tenant compte du dimensionnement du c blage interne Les composants concern s de la pompe chaleur in t grent un limiteur de surcharge Lors du raccordement garantir la r...

Page 39: ...ien Il faut viter d appuyer ou de d poser des objets sur l appareil afin de prot ger la peinture Les parties ext rieures de la pompe chaleur peuvent tre essuy es avec un linge humide et des produits n...

Page 40: ...imal des condensats Il est possible de retirer toutes les t les de surface pour acc der l int rieur de l appareil Ouvrir pour cela les deux tourniquets Le couvercle peut ensuite tre sorti par le haut...

Page 41: ...44 38 4 5 D bit d air plage de r gulation ventilateur EC m h 0 25000 5 Dimensions poids et capacit s 5 1 Dimensions de l appareil sans raccordement7 H x l x L en mm 2300 x 1900 x 1000 5 2 Poids de de...

Page 42: ...fage r gl 3 La temp rature d part minimale possible d pend du flux volumique actuel de la valeur consigne de la temp rature retour r gl e et du niveau de puissance actuel 4 En mode de fonctionnement 2...

Page 43: ...sommation journali re de combustible Qfuel kWh Coordonn es de contact Si le Cdh n est pas d termin par des mesures le coefficient de d gradation par d faut est Cdh 0 9 non applicable Pour les disposit...

Page 44: ...FR 14 452163 66 79 FD 0003 www glendimplex de Fran ais LA 60S TUR...

Page 45: ...ooling operation Courbes caract ristiques mode rafra chissement A IV 2 3 Einsatzgrenzendiagramm Heizen Operating limits diagram heating Diagramme des seuils d utilisation chauffage A V 2 4 Einsatzgren...

Page 46: ...l around sur la circonf rence 1 Heizwasservorlauf Ausgang aus W rmepumpe R 2 2 Heizwasserr cklauf Eingang in W rmepumpe R 2 3 Durchf hrungsbereich Elektroleitungen Kondensat 5 Optionale Durchf hrung E...

Page 47: ...ungsanteil Coefficient of performance incl power input to pump Coefficient de performance y compris part de consommation de la pompe 45 55 0 5 10 15 20 25 30 35 40 45 50 55 60 65 25 20 15 10 5 0 5 10...

Page 48: ...Cooling capacity in kW Puissance de refroidissement en kW 0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 0 1 2 3 4 5 6 7 8 9 10 11 Druckverlust in Pa Pressure loss in Pa Perte de p...

Page 49: ...eforderten Mindestheizwasserdurchfluss erreicht The values specified are valid for the hydraulic 4 way reversing valve The operating range is reduced if the 4 way reversing valve is not used Max heati...

Page 50: ...p m e t r e t a w g n i l o o C C t n e m e s s i h c a r f a r e d u a e d e r u t a r p m e T C C W rmesenkeneintrittstemperatur C Heat sink inlet temperature C Temp rature d entr e de dissipation...

Page 51: ...Anhang Appendix Annexes 3 Einbindungsschemen Integration diagram Sch ma d int gration 3 1 Hydraulische Einbindungsschemen Hydraulic integration diagrams Sch mas d int gration hydraulique R3 R2 1 R1 E9...

Page 52: ...r cylinder R servoir d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 1 Tauchheizk rper Immersion heater R sistance immerg e K20 Sch tz 2 W rmee...

Page 53: ...erkl rung Declaration of Conformity D claration de conformit Die aktuelle CE Konformit tserkl rung finden sie als Download unter You can find and download the current CE conformity declaration at Vous...

Page 54: ...A X 452163 66 79 FD 0003 www glendimplex de Anhang Appendix Annexes LA 60S TUR...

Page 55: ...www glendimplex de 452163 66 79 FD 0003 A XI LA 60S TUR Anhang Appendix Annexes...

Page 56: ...hland GmbH Gesch ftsbereich GDTS Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 924545...

Reviews: