Air-to-water heat pump 16 kW with cooling and domestic hot water
2 Intended use of the heat pump
2.1 Area of application
The air-to-water heat pump is to be used exclusively for heating
and cooling of heating water and domestic hot water. It can be
used in new or existing heating systems.
The heat pump is suitable for mono energy and bivalent opera-
tion in outside air temperatures of up to -22 °C.
Proper defrosting of the evaporator is guaranteed by maintain-
ing a heating water return temperature of more than 20 °C dur-
ing continuous operation.
It is not designed for the increased heat consumption required
when a building is being dried out. For this reason, the addi-
tional heat consumption should be met using special devices
provided by the customer.
In cooling operation, the heat pump is suitable for air tempera-
tures ranging from +15 °C to + 45 °C.
It can be used for silent and dynamic cooling. The minimum
water temperature is +7 °C.
2.2 Operating principle
Heating
Surrounding air is drawn in by the fan and fed through the evap-
orator (heat exchanger). The evaporator cools the air, i.e. ex-
tracts heat from it. This extracted heat is then transferred to the
working medium (refrigerant) in the evaporator.
The heat is "pumped" to a higher temperature level by increas-
ing its pressure with the aid of the electrically driven compres-
sors. It is then transferred to the heating water via the liquefier
(heat exchanger).
Electrical energy is used to raise the temperature level of the
heat from the environment. Because the energy extracted from
the air is transferred to the heating water, this type of device is
referred to as an air-to-water heat pump.
The air-to-water heat pump consists of the main components
evaporator, fan and expansion valve, as well as the compres-
sors, the liquefier and the electrical control system.
At low ambient temperatures, humidity accumulates on the
evaporator in the form of frost, reducing the transfer of heat.
Uneven accumulation during this process does not indicate a
fault. The evaporator is defrosted automatically by the heat
pump as required. Under certain atmospheric conditions,
steam may be emitted from the air outlet.
Cooling
The functions of the evaporator and the liquefier are reversed in
the "Cooling" operating mode.
The heating water transfers its heat to the refrigerant via the liq-
uefier, which is now functioning as an evaporator. The refriger-
ant is brought to a higher temperature level using the compres-
sor. Heat is transferred to the surrounding air via the liquefier
(which, in heating operation, functions as an evaporator).