Glen Dimplex 16CHCIAOC6 Installation And Operating Instructions Manual Download Page 27

www.gdts.one

DOK4x HCIAO CxDEN · FD 9912

25

Air-to-water heat pump 16 kW with cooling and domestic hot water

English

5

Electrical connection

5.1

Supply voltage / fusing / RCD type

Compressor

1~/N/PE 230 V (50 Hz) / C25A / B 3~/N/PE 400 V (50 Hz) / C10A / B

Pipe heater

1~/N/PE 230 V (50 Hz) / B32A / A 3~/N/PE 400 V (50 Hz) / B10A / A

5.2

Control voltage / fusing via WPM

1~/N/PE 230 V (50 Hz) / C13A

1~/N/PE 230 V (50 Hz) / C13A

5.3

Degree of protection according to EN 60 529 indoors / outdoors

IP 21 / IP 24

IP 21 / IP 24

5.4

Starting current limiter

Inverter

Inverter

5.5

Starting current

A

Inverter

Inverter

5.6

Nominal power consumption A2/W35 / max. consumption

2

kW

1.55 / 4.4

1.55 / 4.9

5.7

Nominal current A2/W35 / cos 

φ

A / --

6.8 / 0.99

2.3 / 0.99

5.8

Power consumption of fan

W

up to 200

up to 200

6

Complies with the European safety regulations

see CE declaration of conformity

see CE declaration of conformity

7

Additional model features

7.1

Type of defrosting

Reverse circulation

Reverse circulation

7.2

Condensate tray frost protection / Water in device is protected from freezing

7

yes

yes

7.3

Max. operating overpressure (heat sink)

bar

2.5

2.5

8

Heat output / COP 

2

 

6

8.1

Heat output / COP

EN 14511

EN 14511

with A-7 / W35

kW / --

9.4 / 2.9

9.4 / 2.9

with A2 / W35

kW / --

6.5 / 4.2

6.5 / 4.2

with A7 / W35

kW / --

8.1 / 4.9

6.8 / 4.8

9

Cooling capacity / COP

9.1

Cooling capacity / CO

2

 

6

 

8

EN 14511

EN 14511

with A27 / W18

kW / --

10.4 / 4.2

10.4 / 4.2

with A27 / W7

kW / --

8.0 / 3.1

8.0 / 3.1

with A35 / W18

kW / --

9.3 / 2.9

9.3 / 2.9

with A35 / W7

kW / --

6.9 / 2.2

6.9 / 2.2

1. For air temperatures between -22 °C and -5 °C, flow temperature increasing from 45 °C to 60 °C
2. These data indicate the size and capacity of the system according to EN 14511.

For an analysis of the economic and energy efficiency of the system, other parameters, in particular the defrosting capacity, the bivalence point and

regulation, should also be taken into consideration. These figures are only achieved with clean heat exchangers.

Information on maintenance, commissioning and operation can be found in the respective sections of the installation and operating instructions.

The specified values, e.g. A2 / W35, have the following meaning: outside air temperature 2 °C and heating water flow temperature 35 °C.

3. The heat output and COP is reduced by approx. 5 % in lower operation.
4. The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the instal-

lation location.

5. Note that additional space is required for pipe connections, operation and maintenance.
6. Indoor and outdoor component must be connected with two refrigerant pipes (high and low pressure). The length information refers to one section.

The specified technical data applies to a refrigerant pipe length of 3m per section (minimum permissible).

For longer refrigerant pipes, the heat output is reduced by 2 % and the coefficient of performance (COP) is reduced by 3 % per meter section length.

The maximum permissible section length (without adjusting the refrigerant quantity) is 7 m. The refrigerant quantity pre-filled at the factory is sufficient

up to this length.

From a single pipe length of 7 m, the refrigerant quantity must be adjusted. The maximum permissible length of the pipe with refrigerant top-up is

10 m.

The specified directives for routing refrigerant pipes and topping up refrigerant can be found in the installation and operating instructions.

7. The heat circulating pump and the heat pump controller must always be ready for operation.
8. The maximum sound power level under full load can increase by up to 5 dB(A).

Type and order code

16CHCIAOC6

16IHCIAOC6

Summary of Contents for 16CHCIAOC6

Page 1: ...no DOK4x HCIAO CxDEN EN FD 9912 System M Comfort Plus C 16 kW Installation and Operating Instruction Air to Water Heat Pump in Integral Design Glen Dimplex Thermal Solutions Dimplex 16CHCIAOC6 16IHCI...

Page 2: ......

Page 3: ...rant line and electric wire 13 6 2 Condensate drain 13 6 3 Connection on heating side 13 6 4 Domestic hot water connection 14 6 5 Temperature sensor connection 15 6 6 Electrical connection 16 6 7 Refr...

Page 4: ...domestic hot water 13 Diagrams 32 13 1 Characteristic curves heating 16 kW 32 13 2 Characteristic curves cooling 16 kW 33 14 Product information as per Regulation EU No 813 2013 Annex II Table 2 34 1...

Page 5: ...tions must also be adhered to This unit can be used by children aged 8 and over and by per sons with limited physical sensory or mental aptitude or lack of experience and or knowledge providing they a...

Page 6: ...working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increas ing its pressure with the aid of the electrically driven compres sors It is then transferred to...

Page 7: ...pump 5 Switch box with heating controller 6 Electric additional heater 2 4 or 6 kW for higher domestic hot water temperatures and for heating support 7 Safety valve start to leak pressure 2 5 bar 8 Ex...

Page 8: ...W with cooling and domestic hot water 3 2 Domestic hot water cylinder 3 2 1 MDHW 232 220 litres 1 Magnesium anode 2 Maintenance opening 3 Drainage domestic hot water cylinder 4 Purging pipe heat excha...

Page 9: ...gnesium anode 2 Maintenance opening 3 Drainage domestic hot water cylinder 4 Purging pipe heat exchanger 5 Domestic hot water sensor pipe high output capacity 6 Connection kit included 7 Alternative d...

Page 10: ...CxDEN FD 9912 www gdts one English Air to water heat pump 16 kW with cooling and domestic hot water 3 3 Outdoor unit 1 Evaporator 2 Fan 3 Expansion valve 4 Switch box 5 Connection for refrigerant lin...

Page 11: ...ps can be passed directly underneath the pallet To lift from the pallet the indoor unit can be tilted back by up to 45 and lifted by the handles on the back at the top Tilting more than 45 is not perm...

Page 12: ...transport fastening must be re moved 4 3 Domestic hot water cylinder A pallet should be used to transport the heat pump to its final installation location To lift from the pallet the cylinder can be t...

Page 13: ...lways be fixed in place at the installation location Cap 12 1 on page 27 The responsibility for the heat pump in stallation lies with the specialist system construction company During the installation...

Page 14: ...unit must be inserted in the designated immersion sleeve on the rear of the cylinder On domestic hot water cylinders MDHW 335 with an additional electric heater two immersion sleeves are located at d...

Page 15: ...tions of the countries in question must be observed 6 3 Connection on heating side Before connecting the heating system to the heat pump the heating system must be flushed to remove any impurities res...

Page 16: ...e operated with a suitable frost protection if heat pump systems are implemented in buildings where a power failure can not be detected holiday home 6 4 Domestic hot water connection Installation and...

Page 17: ...ted in such a way that all weather conditions are taken into consideration and the meas ured value is not falsified Mount on the external wall on the north or north west side where possible Do not ins...

Page 18: ...D 9912 www gdts one English Air to water heat pump 16 kW with cooling and domestic hot water 6 6 Electrical connection 6 6 1 Circuit diagram Symbol legend see cap 6 6 2 on page 17 Equipment marking se...

Page 19: ...0 Domestic hot water A441 Bivalent A442 Renewable A451 Cooling active B3 domestic hot water thermostat B4 Swimming pool water thermostat E10 1 Electrical heater E10 2 3 Oil gas boiler H5 Remote fault...

Page 20: ...ason it should be tapped upstream from the utility blocking con tactor or be connected to the household current because otherwise important protection functions could be lost during a utility block Ut...

Page 21: ...ee device information 6 7 2 Pipe connection The connection points for the refrigerant lines must be estab lished using the brazing process All generally applicable instal lation and work steps must be...

Page 22: ...vacuum is reached An absolute pressure of at least 0 2 mbar must be achieved during evacuation Pressures below 0 2 mbar are advisable however Close the vacuum pump and start filling immediately Step 4...

Page 23: ...ely filled and purged Ensure that the condensate drain functions properly The outflow from the heating water pressure relief valve must also function correctly The system must be completely filled wit...

Page 24: ...em must be cleaned by a heating technician Based on current information we recommend using a 5 phosphoric acid solution for cleaning purposes However if cleaning needs to be performed more frequently...

Page 25: ...re discon nected from the power supply HINWEIS NOTE Personal protective equipment protective goggles safety shoes and gloves where necessary must be used when work ing on the device Components with pl...

Page 26: ...18 23 m h Pa 1 6 33000 1 6 33000 Minimum cooling water flow rate m h Pa 1 6 33000 1 6 33000 3 4 Sound power level according to EN 12102 with A7 W55 outdoors Normal operation reduced operation3 dB A 55...

Page 27: ...ency of the system other parameters in particular the defrosting capacity the bivalence point and regulation should also be taken into consideration These figures are only achieved with clean heat exc...

Page 28: ...rating overpressure bar 10 10 10 5 Dimensions without connections H x W x L mm 1400 x 600 x 600 2100 x 600 x 600 10 6 Connections Cold water domestic hot water circulation inches R 1 external thread R...

Page 29: ...intake 0 4 m 1 m 0 5 m 0 5 m Direction of air flow Minimum clearances 460 39 710 40 790 Hatched area footprint 850 1231 600 206 790 538 695 995 95 55 105 40 538 39 4x 17 5 Fixing holes base frame for...

Page 30: ...lish Air to water heat pump 16 kW with cooling and domestic hot water 12 2 Dimension drawing indoor unit 2 8 2 9 2 1 2 10 2 3 2 2 2 7 2 12 2 11 600 1400 544 722 750 113 125 95 0 117 187 490 560 840 91...

Page 31: ...N FD 9912 29 Air to water heat pump 16 kW with cooling and domestic hot water English 12 3 Dimension drawing domestic hot water cylinder MDHW 232 1360 600 1400 B 20 1305 410 37 38 600 70 70 240 56 3 3...

Page 32: ...one English Air to water heat pump 16 kW with cooling and domestic hot water 12 4 Dimension drawing domestic hot water cylinder MDHW 335 600 2060 600 37 38 1265 410 2100 B 20 980 1400 230 70 70 240 5...

Page 33: ...2 3 Feed through refrigerant line indoor unit 2 7 Flow heating G 1 1 4 2 8 Return heating G 1 1 4 2 9 Flow domestic hot water cylinder G 1 1 4 2 10 Return domestic hot water cylinder G 1 1 4 2 11 Flow...

Page 34: ...0 15 20 25 30 35 40 max min 0 1 2 3 4 5 25 20 15 10 5 0 5 10 15 20 25 30 35 40 max min 10 15 20 25 30 35 40 45 50 55 60 65 25 20 15 10 5 0 5 10 15 20 25 30 35 40 at the specified minimum heating water...

Page 35: ...15 20 25 30 35 40 45 50 max min 0 1 2 3 4 5 10 15 20 25 30 35 40 45 50 max min 0 5 10 15 20 25 10 15 20 25 30 35 40 45 50 Cooling capacity in kW Air intake temperature in C Air intake temperature in...

Page 36: ...45 55 dB m h Emissions of nitrogen oxides NOx mg kWh Declared load profile XL Water heating energy efficiency wh 89 Daily electricity consumption Qelec 8 86 kWh Daily fuel consumption Qfuel kWh Contac...

Page 37: ...xides NOx mg kWh Declared load profile XL Water heating energy efficiency wh 89 Daily electricity consumption Qelec 8 86 kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined b...

Page 38: ...up plier are not covered by the warranty If it was not possible to remedy the defect the manufacturer shall either deliver a replacement free of charge or issue a reimburse ment for the reduced value...

Page 39: ...g state of the art en cryption methods III Use of service providers Personal data required for maintenance purposes such as your address contact details and framework data on the contract is made avai...

Page 40: ...CxDEN FD 9912 www gdts one English Air to water heat pump 16 kW with cooling and domestic hot water 17 Declaration of conformity You can find and download the current CE conformity declaration at htt...

Page 41: ...www gdts one DOK4x HCIAO CxDEN FD 9912 39 Air to water heat pump 16 kW with cooling and domestic hot water English...

Page 42: ...40 DOK4x HCIAO CxDEN FD 9912 www gdts one English Air to water heat pump 16 kW with cooling and domestic hot water...

Page 43: ...www gdts one DOK4x HCIAO CxDEN FD 9912 41 Air to water heat pump 16 kW with cooling and domestic hot water English...

Page 44: ...9 dimplex gdts one www gdts one Gesch ftsstelle sterreich Glen Dimplex Austria GmbH Hauptstra e 71 A 5302 Henndorf am Wallersee T 43 6214 20330 F 43 6214 203304 info dimplex at www dimplex at Office F...

Reviews: