Air-to-water heat pump 4 - 6 kW

English

1 Please read immediately

1.1 Intended use

This device is only intended for use as specified by the manu-
facturer. Any other use beyond that intended by the manufac-
turer is prohibited. This requires the user to abide by the rele-
vant project planning documents. Please refrain from
tampering with or altering the device.

1.2 Legal regulations and directives

This heat pump is designed for use in a domestic environment
according to Article 1, Paragraph 2 k) of EC directive 2006/42/
EC (machinery directive) and is thus subject to the require-
ments of EU directive 2014/35/EU (low-voltage directive). It is
thus also intended for use by non-professionals for heating
shops, offices and other similar working environments, agricul-
tural establishments and hotels, guesthouses and other resi-
dential buildings.
The construction and design of the heat pump complies with all
relevant EU directives, DIN and VDE regulations.
When connecting the heat pump to the power supply, the rele-
vant VDE, EN and IEC standards are to be adhered to. Any fur-
ther connection requirements stipulated by local utility compa-
nies must also be observed.
When connecting the heating system, all country-specific reg-
ulations must also be adhered to.
This unit can be used by children aged 8 and over and by per-
sons with limited physical, sensory or mental aptitude or lack of
experience and/or knowledge, providing they are supervised or
have been instructed in the safe use of the unit and understand
the associated potential dangers. 
Children must not play with the device. Cleaning and user
maintenance must not be carried out by children without su-
pervision.

!!

ATTENTION!

Work on the heat pump must only be performed by author-
ised and qualified after-sales service technicians!

HINWEIS

ºº

º

ºº

º

NOTE

When operating or maintaining a heat pump, the legal require-
ments of the country where the heat pump is operated apply.
Depending on the refrigerant fill quantity, the heat pump
must be inspected for leaks at regular intervals by a certified
technician, and these inspections must be recorded.

1.3 Energy-efficient use of the heat 

pump

By operating this heat pump you are helping to protect our en-
vironment. The heating system must be properly designed and
dimensioned to ensure efficient operation. It is particularly im-
portant to keep water flow temperatures as low as possible in
heating operation. All connected heat consumers should there-
fore be suitable for low flow temperatures. Raising the heating
water temperature by 1 K corresponds to an increase in electric
energy consumption of approx. 2.5 %. Low-temperature heat-
ing systems with flow temperatures between 30 °C and 50 °C
are particularly well-suited for energy-efficient operation.

Summary of Contents for 041HOIAOW2

Page 1: ...der no DOK41 HOIAO WxDEN EN FD 9912 System M Compact 4 6 kW Installation and Operating Instruction Air to water heat pump in integral design Glen Dimplex Thermal Solutions Dimplex 041HOIAOW2 061HOIAOW...

Page 2: ......

Page 3: ...11 6 2 Condensate drain 11 6 3 Connection on heating side 11 6 4 Domestic hot water connection 12 6 5 Temperature sensor connection 13 6 6 Electrical connection 14 6 7 Refrigerant pipe connections 17...

Page 4: ...2 DOK41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW 16 Information on the use of data 33 17 Declaration of conformity 34...

Page 5: ...to This unit can be used by children aged 8 and over and by per sons with limited physical sensory or mental aptitude or lack of experience and or knowledge providing they are supervised or have been...

Page 6: ...s the air i e ex tracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increas ing its pre...

Page 7: ...alve for generating domestic hot water 9 Switch box with heating controller 10 Overflow valve to guarantee the minimum heating water flow rate to be set by the installer 11 Universal hardware interfac...

Page 8: ...6 DOK41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW 3 2 Outdoor unit 1 Evaporator 2 Fan 3 Expansion valve 4 Switch box 5 Connection for refrigerant line 1 2 3 4 5...

Page 9: ...be tilted back by up to 45 and lifted by the handles on the back at the top Tilting over 45 is not permitted without removing the refrigeration circuit beforehand To remove the refrigeration circuit...

Page 10: ...connection 2 Disconnect the plug connections on the refrigeration cir cuit switch box 3 Loosen the mounting screws 4 Pull the refrigeration circuit out at the side and transport it to the intended loc...

Page 11: ...5 The responsibility for the heat pump in stallation lies with the specialist system construction company During the installation local requirements such as building reg ulations static load of the bu...

Page 12: ...ion location at any time of the year The minimum volume of the room where the heat pump is in stalled must be no less than the following value depending on the refrigerant quantity in the device If th...

Page 13: ...n and shut off option must be im plemented upstream and downstream of the indoor unit Once the heat pump has been connected to the heating sys tem it must be filled purged and pressure tested When doi...

Page 14: ...re ready for op eration The system must be drained if the heat pump is taken out of service or in the event of a power failure The heating cir cuit should be operated with a suitable frost protection...

Page 15: ...hat all weather conditions are taken into consideration and the meas ured value is not falsified Mount on the external wall on the north or north west side where possible Do not install in a sheltered...

Page 16: ...K41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW 6 6 Electrical connection 6 6 1 Circuit diagram Symbol legend see cap 6 6 2 on page 15 Equipment marking see cap 6 6 3 on pag...

Page 17: ...Hydraulics WPM A210 Master unit A220 Expansion module WPM A300 Electrical distribution system A350 Router A400 Hydraulic installation general A420 Domestic hot water B3 domestic hot water thermostat E...

Page 18: ...30 V 50 Hz must have a continuous voltage A300 For this reason it should be tapped upstream from the utility blocking contactor or be connected to the household cur rent because otherwise important pr...

Page 19: ...75 g 225 g HINWEIS NOTE If the indoor unit is mounted 2 5 m or more metres higher or lower than the outdoor unit a cooling technology specialist must perform a separate check to ensure that the devic...

Page 20: ...the system Step 1 Preparation Ensure that every pipe liquid and intake side between the in door and outdoor unit is connected correctly Ensure that both maintenance valves on the liquid and intake of...

Page 21: ...ess varies with differ ent lengths of the pipework and the pump output The follow ing table shows the time required for pumping empty Step 4 Filling Once the leakage tightness test and evacuation have...

Page 22: ...wing procedure to set the over flow valve correctly Close all heating circuits that may also be closed during opera tion depending on how the heat pump is being used so that the most unfavourable oper...

Page 23: ...by a heating technician Based on current information we recommend using a 5 phosphoric acid solution for cleaning purposes However if cleaning needs to be performed more frequently a 5 formic acid so...

Page 24: ...from the power supply HINWEIS NOTE Personal protective equipment protective goggles safety shoes and gloves where necessary must be used when work ing on the device Components with plastic parts must...

Page 25: ...m indoors dB A 33 33 3 7 Air flow Normal operation reduced operation3 m h 3000 2600 3000 2600 4 Dimensions weight and filling quantity 4 1 Device dimensions5 indoors without connections H x W x L mm...

Page 26: ...ysis of the economic and energy efficiency of the system other parameters in particular the defrosting capacity the bivalence point and regulation should also be taken into consideration These figures...

Page 27: ...r intake 0 3 m 1 0 m 0 5 m 0 5 m Minimum clearances Direction of air flow 358 40 460 40 17 5 4x Fixing holes base frame for M12 438 540 Hatched area footprint 600 871 500 165 40 40 53 36 676 472 99 16...

Page 28: ...www gdts one English Air to water heat pump 4 6 kW 12 2 Dimension drawing indoor unit 2 1 2 6 2 8 2 7 2 3 2 4 2 5 2 2 544 600 600 2100 0 40 142 212 282 352 422 573 652 880 63 572 37 ca 0 68 118 195 2...

Page 29: ...ough refrigerant line 1 6 Optional feedthrough electric wires 1 7 External dimensions wood design variant 1 8 Included pipe set for optional rear connection of the re frigerant lines 2 Indoor unit 2 1...

Page 30: ...h 0 2 4 6 8 25 20 15 10 5 0 5 10 15 20 25 30 35 40 Air intake temperature in C Coefficient of performance incl proportion of pump output 35 45 55 0 1 2 3 25 20 15 10 5 0 5 10 15 20 25 30 35 40 Air in...

Page 31: ...47 0 6 m h 0 2 4 6 8 25 20 15 10 5 0 5 10 15 20 25 30 35 40 Air intake temperature in C Coefficient of performance incl proportion of pump output 35 45 55 0 1 2 3 25 20 15 10 5 0 5 10 15 20 25 30 35 4...

Page 32: ...ons of nitrogen oxides NOx mg kWh Declared load profile L Water heating energy efficiency wh 97 Daily electricity consumption Qelec 5 12 kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is...

Page 33: ...clared load profile L Water heating energy efficiency wh 89 Daily electricity consumption Qelec 5 51 kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined by measurement nthen...

Page 34: ...covered by the warranty If it was not possible to remedy the defect the manufacturer shall either deliver a replacement free of charge or issue a reimburse ment for the reduced value In cases in which...

Page 35: ...t en cryption methods III Use of service providers Personal data required for maintenance purposes such as your address contact details and framework data on the contract is made available to after sa...

Page 36: ...34 DOK41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW 17 Declaration of conformity You can find and download the current CE conformity declaration at https gdts one m...

Page 37: ...www gdts one DOK41 HOIAO WxDEN FD 9912 35 Air to water heat pump 4 6 kW English...

Page 38: ...36 DOK41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW...

Page 39: ...www gdts one DOK41 HOIAO WxDEN FD 9912 37 Air to water heat pump 4 6 kW English...

Page 40: ...9 dimplex gdts one www gdts one Gesch ftsstelle sterreich Glen Dimplex Austria GmbH Hauptstra e 71 A 5302 Henndorf am Wallersee T 43 6214 20330 F 43 6214 203304 info dimplex at www dimplex at Office F...

Reviews: