Table 8.6 Blocking error codes
‘c’
code
Error
Int
no
Description
1
T_FLOW_OPEN
48
Flow sensor, S1, open
2
T_RETURN_OPEN
47
Return sensor, S2, open
8
T_FLUE_OPEN
51
Flue sensor, S3, open
11
T_FLOW_SHORTED
56
Flow sensor, S1, shorted
12
T_RETURN_SHORTED
55
Return sensor, S2, shorted
18
T_FLUE_SHORTED
59
Flue sensor, S3, shorted
13 REFHI_TOO_LO_ERROR
28
Temperature
measurement
incorrect
14 REFHI_TOO_HI_ERROR
29
Temperature
measurement
incorrect
15 REFLO_TOO_LO_ERROR
30
Temperature
measurement
incorrect
16 REFLO_TOO_HI_ERROR
31
Temperature
measurement
incorrect
19
E2PROM_READ_ERROR
0
Not able to read e2prom contents
20
FLAME_ERROR_2
33
Flame detected with a closed gas valve
21 PHASE_ERROR
41
Mains
supply
live and neutral are reversed
22
50HZ_ERROR
42
Mains frequency is not 50Hz
42 WD_COMUNICATION_ERROR 44
problems with communicating with watchdog
51 RESET_BUTTON_ERROR
65
Reset
button
pressed to many times in a short time
8.3. SERIAL
SOFTWARE
In order to check the control and to set the parameters in its E2PROM, serial software is provided. To use
this software a windows PC with serial port (COMP port) or a USB port is needed.
8.4. INTERNAL WIRING DIAGRAM
The appliance wiring diagram is shown in diagram 8.3. Ensure that wiring details are followed when a PCAB,
wiring harness or components are changed.