System 3000

speed regulator insert

Power loss

max. 4 W

Ambient temperature

-5 ... +45 °C

Switching current at 25 °C

60 mA ... 1.8 A

max. motor current (Imax)

1.8 A

Reduction of switching current
per 5 °C in excess of 25 °C

-10%

when installed in wooden or dry construction walls

-15%

when installed in multiple combinations

-20%

Number of extension units
3-wire rotary extension

10

2-wire, push-button

unlimited

Total line length

pwr cable

max. 100 m

Extension

max. 100 m

7

Troubleshooting

Motor stops at lowest speed setting

Cause: The set minimum speed is too low.

Increase the minimum speed.

Motor speed is too fast at lowest speed setting

Cause 1: The set minimum speed is too high.

Reduce the minimum speed.

Speed controller has switched off and cannot be switched on again.

Cause 1: overheating protection has tripped.

Reduce the connected load.
Disconnect the speed controller from the mains by switching off the circuit breaker.
Let the speed controller cool down for at least 15 minutes.
Switch on the circuit breaker and speed controller again.

Cause 2: short-circuit protection has tripped.

Disconnect the speed controller from the mains by switching off the circuit breaker.
Eliminate short-circuit.
Switch on the circuit breaker and speed controller again.

Short-circuit protection is not based on a conventional fuse, no metallic separation of the
operational current.

8

Warranty

The warranty is provided in accordance with statutory requirements via the specialist trade.
Please submit or send faulty devices postage paid together with an error description to your re-
sponsible salesperson (specialist trade/installation company/electrical specialist trade). They will
forward the devices to the Gira Service Center.

4 / 5

82404702

01.04.2021

Summary of Contents for System 3000 2460 00

Page 1: ...tion with suitable cover 3 Product characteristics Product characteristics Device is operating in leading edge phase control Operation without neutral conductor possible Switch on via soft start to maximum speed Minimum speed can be saved permanently Connection of extensions possible Electronic short circuit protection with permanent switch off after approx 100 ms Electronic over temperature prote...

Page 2: ...N 1 1 N L 4 2 1 5 6 3 Figure 1 Connection diagram with optional extensions 1 Button Test 2 LED display 3 Rotary axle 4 3 wire rotary extension 5 2 wire extension 6 Push button NO contact The connection of a central extension is not possible Operation without neutral conductor possible Only connect illuminated push buttons if they have a separate N terminal Precondition The maximum motor current Im...

Page 3: ...insulated tools for the work Cover up live parts in the working environ ment The minimum speed must be set so that the motor does not stop at the lowest speed set ting Prerequisites Speed controller is ready for operation and the central plate is not mounted Press the button Test 1 until LED 2 lights up The current operating state remains the same After 45 seconds without an actuation the LED 2 go...

Page 4: ... 1 overheating protection has tripped Reduce the connected load Disconnect the speed controller from the mains by switching off the circuit breaker Let the speed controller cool down for at least 15 minutes Switch on the circuit breaker and speed controller again Cause 2 short circuit protection has tripped Disconnect the speed controller from the mains by switching off the circuit breaker Elimina...

Page 5: ...rsiepen GmbH Co KG Elektro Installations Systeme Industriegebiet Mermbach Dahlienstraße 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de info gira de 5 5 82404702 01 04 2021 ...

Reviews: