Gira 834 Plus Installation, Start-Up, Operation Download Page 8

Introduction

8

06.2017/V 1.2

1.3 

Area of application

The Gira radio emergency set is used to signal emergency situations and for alarming 
personnel. Signalling of an emergency situation is via a red signal light in the radio call 
module as well as acoustically via an optionally activated buzzer, also in the radio call module 
(factory setting: off). 
The Gira radio emergency set is suited to all areas of application in which the installation of 
a call system according to DIN VDE 0834 is not expressly required, but where use of a call 
system is still expedient and is also thoroughly recommended due to high risk factors. Thus 
installation is possible in locations such as public outdoor facilities (e.g. toilet rooms in public 
baths), in public buildings such as administrative authorities, museums, department stores 
and also at places of work with especially high risk potential.
The range of application therefore covers for example all rooms in which persons who are 
alone (without visual or acoustic contact to their surroundings) may become subject to an 
emergency situation.
Gira assumes neither legal responsibility nor provides a guarantee for errors and damage of 
any kind as a result of improper use and/or unprofessional installation of the emergency set.

1.4 Functional 

description

A call is triggered if a person in need of help pulls the cord of the radio pull-cord button. The 
triggered call is signalled by a reassurance light in the housing of the radio pull-cord button. 
The red signal light of the radio call module simultaneously signals outside the room that 
help is required.

The radio switch-off button is located in the room where the call was triggered and is 
installed adjacent to the door. A triggered call can be deactivated by the person hurrying 
to give help pressing the green switch-off button.

Visual call signalling is with a red continuous light.

Acoustic call signalling in the radio call module can be switched on or off via the DIP switch 
on the circuit board (see Figure 2.3:) (factory setting: buzzer off).

The radio call module features a zero-voltage relay contact (see 2.7). The relay functions as 
a zero-voltage NC contact. This can be used for example for connection of a Gira TeleCoppler 
(optional).

After power failure, the function of the emergency set is maintained as all devices in the radio 
emergency set are battery-buffered (please see the technical data for precise designations 
of the battery types used).

The radio emergency set can be expanded by purchasing further components:

• Radio pull-cord button (Order No.: 5932 ..

• Radio switch-off button (Order No.: 5931 ..)

Summary of Contents for 834 Plus

Page 1: ...Gira radio emergency set 5914 Gira radio emergency set Installation start up operation...

Page 2: ......

Page 3: ...with one or several devices 14 2 6 2 Deleting device assignment to a radio emergency set 15 2 6 3 Testing the connection quality of the installation 16 2 7 Relay in the radio call module 17 2 8 Start...

Page 4: ...t of these documents may be duplicated or transmitted for any purpose regardless of the manner and means used electronic or mechanical without the expressed written consent of Gira Giersiepen GmbH Co...

Page 5: ...rol electronics for the radio emergency set as well as the signal light and buzzer 1 Power supply 2 Relay connection 3 RS 834 connection 1 Programming button 2 Antenna 3 LED display 4 Battery 5 DIP sw...

Page 6: ...Programming button 2 Antenna 3 LED display 4 Battery 5 Pull cord button Function Call triggering Triggers calls by pulling the cord Reassurance light in the housing Battery operated Device view Rear...

Page 7: ...art order number 5930 Device view Power supply unit for flush mounted installation Function Power supply of the radio call module 230 V 12 V 1 A Power supply of the call module Can also be used for su...

Page 8: ...proper use and or unprofessional installation of the emergency set 1 4 Functional description A call is triggered if a person in need of help pulls the cord of the radio pull cord button The triggered...

Page 9: ...m in the free field 1 5 Interfaces and connection options The radio emergency set features the following interface The radio call module has a zero potential relay contact NC A Gira TeleCoppler Order...

Page 10: ...Introduction 10 06 2017 V 1 2...

Page 11: ...to the ground at least 0 5 m above the ground Basic rule the higher a radio component is installed the longer its range Attenuation of radio signals is achieved by reinforced concrete metal grids thic...

Page 12: ...g up of the housing during operation is normal and safe Recommendation Position the power supply unit to partition the cables Recommendation Install the power supply unit and radio call module in deep...

Page 13: ...ed or taught in 2 5 1 Removing the battery discharge protection Batteries are placed in the intended battery holder in the factory To avoid discharge during storage delivery a strip separates the batt...

Page 14: ...ther For each device implement steps 2 to 3 in succession Step Set the device into programming mode Response signalling of the device during teach in 1 1 Device radio call module Press and hold the pr...

Page 15: ...deleted Press and hold the program ming button for longer than 3 seconds 3 Result The device assignment to the set is deleted and the status LEDs on both devices flash rapidly The device deleted from...

Page 16: ...the connection quality of several devices one after another For each device implement steps 1 and 2 in succession Step Set the device into test mode Visual and acoustic display of the connection qual...

Page 17: ...asure the 12 V DC supply voltage of the power supply unit The power supply must not drop below 11 8 V DC Pull the cord of the radio pull cord button The red light in the housing of the radio pull cord...

Page 18: ...ed signal light of the call module outside adjacent to the door of the WC The call is switched off with the switch off button in the WC area next to the door when the danger situation has been dealt w...

Page 19: ...The factory setting is All 4 switches are in the left position all options are OFF Figure 2 3 DIP switch in the call module DIP switch in the call module Symbol meanings Buzzer off buzzer on Factory s...

Page 20: ...ation e g unsuitable climatic conditions humidity e g unsuitable distance between the call module and the other devices Eliminating the cause e g select a suitable installation location e g create sui...

Page 21: ...itable distance between the call module and the other devices Eliminating the cause e g select a suitable installation location e g create suitable climatic conditions low humidity e g ensure suitable...

Page 22: ...ld for longer than 10 seconds 2 10 5 Device defect If all other fault sources have been excluded and a device is still unable to establish a radio connection then a device reset must be carried out wi...

Page 23: ...l light of the radio call module 3 2 Call signalling Radio pull cord button The call is signalled with a lighting up of the reassurance light in the housing of the radio pull cord button Radio call mo...

Page 24: ...batteries can be ordered with the Gira order number Battery type CR2 3 V 800 mAh for the radio call module order number 5988 00 Battery type 1 2 AA 3 6 V 1 200 mAh for pull cord button and switch off...

Page 25: ...cord button 1 x 1 2 AA 3 6 V 1 200 mAh Radio switch off button Installation in installation box DIN 49073 Lithium battery in radio switch off button 1 x 1 2 AA 3 6 V 1 200 mAh Transmission frequency 8...

Page 26: ...evices 5 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade Please submit or send faulty devices postage paid together with an error description to yo...

Page 27: ......

Page 28: ...10231058 I02 06 17 Gira Giersiepen GmbH Co KG Electrical installation systems P O Box 12 20 42461 Radevormwald Germany Phone 49 0 2195 602 0 Fax 49 0 2195 602 191 www gira com info gira com...

Reviews: