Operation
24
06.2017/V 1.2
3.4
Status display and display of faults in the call module
3.5
Setting of acoustic signalling in the call module
The acoustic call signalling in the radio call module can be activated or deactivated via DIP
switch (see 2.9).
3.6
Power failure
A call that was active before power failure is retained.
3.7
Maintenance and care
The operability of all system components must be checked regularly (once yearly). DIN VDE
0834 also specifies replacing batteries once yearly.
If batteries must be replaced, the batteries can be ordered with the Gira order number:
• Battery (type CR2, 3 V, 800 mAh) for the radio call module,
order number: 5988 00
• Battery (type
1
/
2
AA, 3.6 V, 1,200 mAh) for pull-cord button and switch-off button,
order number: 5989 00
Call type
Type and cycle sequence of the calls
Visual display
Colour
Acoustic signal when
buzzer is ON
Call
Continuous light
Red
Tone sequence
t
on
approx. 1 sec.
t
off
approx. 10 ... 20 sec.
Signalling with
"no connection"
Flashing light,
long interval
on/off
approx. 1 sec.
each ...
Red
Signalling with
"weak battery"
Flashing light,
short interval
on/off
approx. 0.5 sec.
each ...
Red
Important:
Danger of explosion in case of improper replacement of the battery.
Observe the regulations on the disposal of used batteries.
Summary of Contents for 834 Plus
Page 1: ...Gira radio emergency set 5914 Gira radio emergency set Installation start up operation...
Page 2: ......
Page 10: ...Introduction 10 06 2017 V 1 2...
Page 27: ......