Switch-on brightness

1...100 %
Basic setting: 100 %

During brief operation, the
output switches on at the set
switch-on brightness.
Note: If the value is above the
set maximum brightness or
below the minimum
brightness, then the system
will switch to the appropriate
limit value.

Minimum brightness

1...67 %
Basic setting: 5 %

Specifies the minimum
settable brightness.
Note: If parameters or scene
values are set to a level lower
than the minimum brightness,
then the system will dim to
minimum brightness.

Maximum brightness

75...100 %
Basic setting: 100 %

Specifies the maximum
settable brightness.
Note: If parameters or scene
values are set to a level higher
than the maximum brightness,
then the system will dim to
maximum brightness.

Dimming adjustment time

1…60 s
Basic setting: 4 s

Time from minimum
brightness until reaching
maximum brightness (dimming
speed).

Switch-on delay

0 s … 24 h
Basic setting: 0 s

The load switches on after a
delay. Repeated switch-on
commands restart the delay
time. If the load has not yet
been switched on due to the
delay when a switch-off
command comes, then the
load will remain off.
Note: The set time apply to
operation using radio
transmitters. The device is
switched immediately when
the 

Prog

 button is pressed.

Switch-off delay

0 s … 24 h
Basic setting: 0 s

The load switches off after a
delay. Repeated switch-off
commands restart the delay
time. If the load has not yet
been switched off due to the
delay when a switch-on
command comes, then the
load will remain on.
Note: The set time apply to
operation using radio
transmitters. The device is
switched immediately when
the 

Prog

 button is pressed.

32582722

10864994

27.04.2017

6/15

Wireless switching/dimming top unit, 1-gang

Summary of Contents for 5490 Series

Page 1: ... suitable for disconnection from supply voltage Depending on the insert used the load is not electrically isolated from the mains even when the device is switched off These instructions are an integral part of the product and must remain with the end customer 2 Device components Figure 1 Device components 1 FM insert 2 Frame 3 Radio button 4 Status LED 3 Function Intended use Manual and radio cont...

Page 2: ...ace with radio transmitters please observe the radio transmitter instructions Switch light o Press button for less than 0 4 seconds The light is switched on or off In combination with inserts for dimming switch on takes place at the saved switch on brightness Status LED 4 lights up output is switched on Status LED 4 off output is switched off i In the case of the HVAC insert only the output Kanal ...

Page 3: ...from any possible sources of interference e g metallic surfaces microwave ovens hi fi and TV systems ballasts or transformers The flush mounted insert is correctly fitted and connected see instructions for flush mounted insert o Fit radio button 3 and frame 2 on flush mounted insert 1 o Switch on mains voltage o Carry out commissioning see Commissioning chapter 5 2 Commissioning DANGER Electrical ...

Page 4: ...adio transmitter are disconnected automatically as soon as the last connection to the radio transmitter is disconnected Manual disconnection is not possible Resetting button to the default setting All connections to radio transmitters are disconnected and parameters are reset to default setting i The connections in the radio transmitters are preserved and must be deleted separately Load is switche...

Page 5: ... Continuous off Basic setting Normal Operation Normal operation The output can be operated with radio transmitters and the Prog button Continuous on The output switches to continuously On All operations of radio transmitters and the Prog button are ignored Continuous off The output switches to continuously Off All operations of radio transmitters and the Prog button are ignored Advanced device set...

Page 6: ...60 s Basic setting 4 s Time from minimum brightness until reaching maximum brightness dimming speed Switch on delay 0 s 24 h Basic setting 0 s The load switches on after a delay Repeated switch on commands restart the delay time If the load has not yet been switched on due to the delay when a switch off command comes then the load will remain off Note The set time apply to operation using radio tr...

Page 7: ...actuator will no longer remain on permanently but only for the length of the run on time The run on time is restarted if actuation is repeated This parameter is directly connected to the Manual switch off of run on time parameter Note The set time apply to operation using radio transmitters The device is switched immediately when the Prog button is pressed Manual switch off of the run on time On O...

Page 8: ...the output after voltage return Brightness on voltage return 0 100 Basic setting 100 Brightness value set by the output after voltage return mains voltage The parameter Behaviour after voltage return must be set to Configured brightness Note If the value is above the set maximum brightness or below the minimum brightness then the system will switch to the appropriate limit value Behaviour after th...

Page 9: ... 0 100 Basic setting 0 Defines the behaviour of the output on activating the lock out protection Deactivate lock out protection brightness value 0 100 Basic setting 0 Defines the behaviour of the output on deactivating the lock out protection Only visible when the priority for the lock out protection is 0 Priority restraint 0 4 Basic setting 2 Specifies the priority for recalling and removing a sc...

Page 10: ...utput on activating the twilight function Deactivate twilight brightness value 0 100 Basic setting 0 Defines the behaviour of the output on deactivating the twilight function Only visible when the priority for the twilight function is 0 Switch off brightness overshoot On Off Basic setting On Allows automatic switch off according to the brightness If the parameter is On then the light controller sw...

Page 11: ...s switched immediately when the Prog button is pressed Switch off delay 0 s 24 h Basic setting 0 s The load switches off after a delay Repeated switch off commands restart the delay time If the load has not yet been switched off due to the delay when a switch on command comes then the load will remain on Note The set time apply to operation using radio transmitters The device is switched immediate...

Page 12: ...uous on Continuous off Basic setting Normal Operation see Device and channels Manual commissioning On Off Basic setting On Blocks manual commissioning for the device channel Note In the Off setting the device cannot be reset to the factory setting Local Operation On Off Basic setting On Blocks the output for operation using the Prog button Behaviour on voltage return On Off Last value Basic settin...

Page 13: ...ff Basic setting Off Defines the behaviour of the output on activating the lock out protection Deactivate lock out protection switching state On Off Basic setting Off Defines the behaviour of the output on deactivating the lock out protection Only visible when the priority for the lock out protection is 0 Priority restraint 0 4 Basic setting 2 Specifies the priority for recalling and removing a sc...

Page 14: ...Off Basic setting Off Defines the behaviour of the output on deactivating the twilight function Only visible when the priority for the twilight function is 0 Information window In the Information window the load can be controlled and the information about the device can be displays Channel control channel information Display value Explanations Current dimming value The load can be dimmed using the...

Page 15: ... specialist trade installation company electrical specialist trade They will forward the devices to the Gira Service Center Gira Giersiepen GmbH Co KG Elektro Installations Systeme Industriegebiet Mermbach Dahlienstraße 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de info gira de 32582722 10864994 27 04 2017 15 15 Wireless sw...

Reviews: