background image

Setting the values for sun protection, twilight and temperature

Default setting:
Sun protection 

3

 approx. 20,000 Lux (7)

Twilight 

2

 approx. 40 Lux (8)

Temperature 

°C

 = Off (9)

o

Using a small screwdriver, adjust the values for sun protection 

3

 (7), twilight 

2

 (8) and if

necessary, the temperature 

°C

 (9), too.

In test operation, set the current brightness as sun protection threshold

The test operation makes it possible to adjust the sun protection and temperature threshold to
the currently prevailing conditions.

o

Press button 

Prog

 (3) briefly.

The sun sensor is in test operation for approx. 1 minute.

o

Turn adjuster 

°C

 (9) to left stop = Off.

LED lit up = Sun protection threshold undershot
LED flashing = Sun protection threshold exceeded

o

Turn adjuster 

3

 (7) slowly until the LED switches from illuminating to flashing.

The current temperature can also be applied now for temperature-dependent sun protection if
necessary.

i

The temperature threshold can only be set if the sun protection is not active.

o

Turn adjuster 

°C

 (8) slowly to the right until the LED switches from illuminating to flashing.

i

Pressing the button 

Prog

 (3) again exits test operation.

5 Information for electrically skilled persons

5.1 Fitting and electrical connection

Mounting of the sun sensor

To ensure good transmission quality, keep a sufficient distance from any possible sources of
interference, e.g. metallic surfaces, microwave ovens, hi-fi and TV systems, ballasts or
transformers.
Select the mounting location on the window pane in such a way that the sunlight can hit the
sensor without impediment even when sun protection is active. Shadows produce incorrect
measured values or prevent charging of the battery.
The contact surfaces of the sun sensor and the window pane must be clean and free of grease.

o

Moisten the suction pad slightly.

o

Place the sun sensor on the window pane and push it tight.

i

Metallised window panes can restrict the radio range greatly.

Dismantling the sun sensor

In order to avoid damage to the sun sensor, dismantling may only take place using the handle
(1).

o

Pull the handle (1) lightly to release the sensor from the window pane.

5.2 Commissioning

DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.

i

The energy store in the sun sensor is charged in the as-delivered state. Thus,
commissioning can take place even without putting the sun sensor in a light place
beforehand.

32582922

10864960

24.03.2017

3/7

Wireless Solar sun sensor

Summary of Contents for 5461 02

Page 1: ...Solar cell on the rear 3 Button Prog 4 Twilight button 2 5 Sun protection button 3 6 Status LED 7 Sun protection adjuster 3 8 Twilight adjuster 2 9 Temperature adjuster C Position Off no temperature e...

Page 2: ...into the sun protection with the eNet server Sun protection temperature dependent Temperature dependent sun protection cab primarily be used in the colder months of the year The shading of the interio...

Page 3: ...ting and electrical connection Mounting of the sun sensor To ensure good transmission quality keep a sufficient distance from any possible sources of interference e g metallic surfaces microwave ovens...

Page 4: ...e allocated to each actuator The presetting for blinds shutters is the bottom end position Actuators are connected to the scene i With shutter actuators the actual shutter movement time must be saved...

Page 5: ...ield typ 100 m Receiver category 2 6 2 Parameter list The device parameters can be changed with the eNet server Device and channels Parameter name Setting options Basic setting Explanations Function O...

Page 6: ...procedure with the eNet server Put sun sensor in a very bright place for several hours As soon as the energy store is sufficiently charged the device is operational again after pressing the Prog butt...

Page 7: ...ions Systeme Industriegebiet Mermbach Dahlienstra e 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de info gira de 32582922 10864...

Reviews: