background image

o

Press the top or full-surface of the 2-wire extension or installation button for less than
0.4 seconds.
Light is switched on depending on brightness and motion. Movements are evaluated
according to the brightness and prolong the run-on time.

Switching the light off for a period of 3 minutes

i

This function can only be used in presence detector operation.

A 2-wire extension or an installation button is connected.
Light is switched on.

o

Press the bottom 2-wire extension or installation button.
The light is switched off for the period of 3 minutes. When movements are detected, the
time is restarted.

Switch on the light for 2 hours

Motions are not evaluated during this time. It is not possible to switch off via a 2-wire extension
or installation button.

o

Press 

2 h On

 button of the IR remote control.

Light is switched on for 2 hours. The motion detector is in automatic operation again after
the 2 hours have elapsed.

i

The time is restarted if actuation is repeated.

i

Automatic operation is switched on again using the 

ů

 button.

Switch on the light continuously

Motions are not evaluated during this time. It is not possible to switch off via a 2-wire extension
or installation button.

o

Press the 

Ű

 button for shorter than 0.4 seconds.

Light is switched on continuously. The blue LED lights up.

i

Automatic operation is switched on again using the 

ů

 button.

Switch off the light for 2 hours

Motions are not evaluated during this time. It is not possible to switch on via a 2-wire extension
or installation button.

o

Press the 

2 h Off

 button.

Light is switched off for 2 hours. The device is in automatic operation again after the time
has elapsed.

i

The time is restarted if actuation is repeated.

i

Automatic operation is switched on again using the 

ů

 button.

Switch off the light continuously

Motions are not evaluated It is not possible to switch on via a 2-wire extension insert or
installation button.

o

Press the 

ű

 button for shorter than 0.4 seconds.

Light is switched off continuously. The red LED lights up.

i

Automatic operation is switched on again using the 

ů

 button.

Adjusting the switch-on brightness

The switch-on brightness is set during commissioning. The switch-on brightness can be
adjusted at a later time using the supplied IR remote control.

o

Press 

Ų

 button briefly.

o

Within 10 seconds, press the 

Ű

 or 

ű

 button briefly.

Each button press extends or shortens the brightness threshold by 10 % of the set value,
but by at least 1 lux.

82593212

12.01.2017

5/18

Presence detector and motion detector 360° compact

Summary of Contents for 2399 02

Page 1: ...count which support dangerous voltages to the device and or load Do not press on the sensor window Device can be damaged Keep button cells out of reach of children If button cells are swallowed get me...

Page 2: ...ion area through parallel switching of multiple devices i The extension of the detection area with 3 wire extensions is not possible Automatic operation The device detects heat motions of people anima...

Page 3: ...ted motions prolong the run on time or the light is switched on depending on brightness Times are not saved Function as twilight switch The function is active as soon as all the PIR sensors have been...

Page 4: ...s the brightness threshold Set 2 Pressing for longer than 10 seconds Activating the settings saved by the installation engineer Pressing for longer than 10 seconds Switching the presence simulation on...

Page 5: ...ire extension or installation button o Press the button for shorter than 0 4 seconds Light is switched on continuously The blue LED lights up i Automatic operation is switched on again using the butto...

Page 6: ...longer required o Press the Set 2 button for longer than 10 seconds Settings saved by the installation engineer are active again Switching the presence simulation on or off o Press the button for lon...

Page 7: ...ement on the ground 2 Range for radial movement on the ground 3 Range for typical movements at desks e g torso movement 4 Range of fine detection at desks e g mouse movements When used as a presence d...

Page 8: ...Aligning the device The device has three independent PIR sensors for motion detection Figure 5 Figure 5 Detection field areas A B and C installation height 2 50 m Figure 6 Arrangement of the areas A B...

Page 9: ...ins 10 Screws o Pull off the decor ring 5 Figure 7 o Loosen the screws 10 Figure 7 Installing the connection box Figure 8 Connection box 11 Fastening holes 12 Cable entry surface mounted 13 Thin point...

Page 10: ...appliance box The screws are not included in the scope of delivery Connecting the device Figure 9 Connection diagram single device Figure 10 Connection diagram parallel circuit for expanding the detec...

Page 11: ...only necessary if manual operation is also desired i Lit installation buttons may only be connected if they have an N terminal i In the case of single devices a 2 wire extension can be used as an alte...

Page 12: ...30 s 2 min 5 min 30 min Set run on time Pressing for longer than 10 seconds Saving ambient brightness as brightness threshold Setting the brightness threshold 0 1 h Setting individual run on time Dyn...

Page 13: ...there is no distinct demarcation of the blocked out detection area If all the PIR sensors have been switched off then the device works as a twilight switch o Press the PIR A PIR B or PIR C button for...

Page 14: ...ff once To cancel a running run on time set the special function Continuous on for example and then switch back to Automatic operation see Operation Setting the dynamic run on time The device adapts t...

Page 15: ...function press the Reset button for between 4 and 10 seconds Saving settings Save the settings so that if necessary the end customer can recall them using the Set 2 button No values are saved in the a...

Page 16: ...AC 230 V and 35 C Incandescent lamps 2300 W HV halogen lamps 2000 W Electronic transformers 1500 W Inductive transformers 1000 VA HV LED lamps typ 400 W Compact fl lamp typ 400 W Fluorescent lamps un...

Page 17: ...vice detects motions constantly Remove interference sources if possible Reduce sensitivity Limit detection area Cause 2 On for 2 hours Continuous on or On for 100 hours is activated Switch on automati...

Page 18: ...eme Industriegebiet Mermbach Dahlienstra e 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de info gira de 82593212 12 01 2017 18...