7
Normal display (n)
This parameter is used to select the normal display of the controlling
device. This information is always displayed on the display whenever no
menu has been selected and no holiday settings are active.
1. The
+
and
-
buttons can be used to change to one of the operating
modes listed below.
2.
S
activates it.
* Preset in our works
Operating mode (b)
This parameter allows individual selection of the function for the room
temperature controller. This is used to specify the sensor selection for
temperature controlling, the mode of operation (heating/cooling) and the
limiting function.
1. The
+
and
-
buttons can be used to change to one of the operating
modes listed below.
2.
S
activates it.
* Preset in our works
Differential gap (d)
This parameter defines the differential gap (hysteresis) of the controlling
function.
1. The
+
and
-
buttons can be used to select the value.
2.
S
activates the value.
The relay is switched off if the current temperature lies over the setpoint
temperature by the value set here (Heating operating mode).
The relay is activated again if the actual temperature lies below the
setpoint value by the value set here (Heating operating mode).
The switching difference is set in our works to ±0.2 °C
Limiting temperature (G)
This parameter allows the setting of an individual limitation of the floor
temperature. If the limiting function is activated (operating mode with
limiting function selected), the relay is deactivated as soon as the
temperature measured at the external sensor exceeds the temperature
set here (heating).
In cooling mode the relay is deactivated as soon as the measured
temperature lies below the set limiting temperature.
1. The
+
and
-
buttons can be used to set the limitation.
2.
S
activates the limitation.
The setting range amounts to +5 °C to +55 °C. The limiting temperature
is set in our works to +45 °C
The limiting function does not have a differential gap, so that switching is
carried out immediately if the value exceeds the upper or lower limit.
Temperature at the external sensor (F)
If an operating mode which requires an external sensor is selected, the
current temperature value is displayed under this menu item.
No change can be carried out at this value.
If an operating mode which only operates with the internal sensor is
selected, "
--.--
" is displayed.
Normal display
Display
Current time of day
Clock *
Current setpoint temperature
SETPOINT
Current actual temperature
Actual
Reference
variable
Operating
mode
Floor temperature limit
Display
Internal sensor
Heating
---
I.H*
Internal sensor
Cooling
External sensor
IE.C
External sensor
Cooling
---
E.C
Internal sensor
Cooling
---
I.C
Internal sensor
Heating
External sensor
IE.H
External sensor
Heating
---
E.H