Radio-Control Presence Detector

Installation Instructions

Radio-Control Presence Detector

7/07

Page 11 of 15

8. Lightscape operation All-ON / All-OFF

During the retention time, the radio-controlled actua-
tor involved in light control can be integrated together 
with other radio-controlled actuators into lightscapes 
and into the ALL-ON or ALL-OFF function. The re-
called lightscape is statical, i.e. there is no light control 
function.

The lightscapes can be recalled, stored and changed 
with a handheld transmitter ‘Komfort’, a wall-mounted 
transmitter or a multifunction transmitter. Read the 
corresponding transmitter operating instructions.

Lightscape

A recalled lightscape will be switched on for at least 2 
minutes with the actuator integrated into light control.
If no presence is detectec anymore and after elapsing 
of the preset retention time, the actuator switches off 
and returns to automatic operation.

All-ON

When a programmed All-ON key is pressed, the actu-
ator integrated into light control switches on. If no pre-
sence is detected anymore and after elapsing of the 
preset retention time, the actuator switches off and re-
turns to automatic operation.

All-OFF

When a programmed All-OFF key is pressed, the ac-
tuator integrated into light control switches off for at 
least 2 minutes. If no presence is detected anymore 
and after elapsing of a fixed retention time of 2 min-
utes, the actuator switches off and returns to automa-
tic operation.

.

Master key special functions during lightscape 

operation

The special functions during lightscape operation list-
ed below can only be operated with the Master key of 
a handheld transmitter ‘Komfort’ or a wallmounted 
transmitter with 4 channels.

Master key

- Handheld radio-control transmitter ‘Komfort’

When a lightscape key (fig. 8.a 

c

) is programmed,

  the Master key (fig. 8.a 

d

) is automatically stored

  in the radio-control receiver.

8.a)

-  4-channel wall-mounted radio control trans-

mitter

When at least one of channel keys 1 through 3 of
the 4-channel wallmounted transmitter is set for 
lightscape operation and accordingly programmed
in the actuator, channel key 4 (fig. 8.b 

e

) is auto-

matically assigned in the radiocontrolled actuator to
lightscape operation with Master key functions.

8.b)

i

Important

When a multifunction transmitter is used it is neces-
sary after recalling of a lightscape to wait until the 
shut-off delay has passed before it is possible to re-
turn to the light control mode. Switching off the light-
scape earlier with a multifunction transmitter is not 
possible.

Summary of Contents for 0318 02

Page 1: ... If no movements are detected anymore the detector switches off after the preset shut off delay The detec tor is equally switched off when the upper brightness limit is exceeded For monitoring of large areas several presence de tectors can be used in common in the same system In this case one presence detector works as the mas ter unit main unit whereas all other presence detec tors work as slave ...

Page 2: ...ttach the presence detector to the baseplate only af ter having installed the batteries and programmed the presence detector into a radio control receiver To install the presence detector proceed as follows 1 Fasten the baseplate to the room ceiling using the screws supplied fig 2 c c 2 Turn the presence detector on the baseplate ap prox 45 counterclockwise until it is heard to en gage 2 c i Impor...

Page 3: ...ng of a radio control presence de tector the sensitivity of the radio control receivers is reduced to approx 5 m The distance between the re ceiver and the radiocontrol presence detector should therefore be not less than 0 5 m and not more than 5 m Programming procedure 1 When programming the first presence detector into the radiocontrol receiver make sure the brightness control fig 2 f i does not...

Page 4: ...be used to blank out undesired zones of detection The mask is snapped onto the sensor window Cut out the mask only along the marked lines fig 3 c The following data are referred to a fitting height of ca 2 50 m In this case the detection field on the floor has a diameter of ca 8 00 m 3 c Cutting out the mask changes the diameter of the de tection field on the floor as follows Full mask without cut...

Page 5: ...e radio actuator only after activation of the light control test mode After performing the setting put the ornamental ring back in place The protruding light sensor must fit into the corresponding recession in the ornamental ring 5 Setmodes 5 1 Light control test mode The light control test mode is used to preset the refer ence brightness of the presence detector Fine tuning can be done later by r...

Page 6: ...ds Activating the movement test mode To activate the movement test mode for about 10 mi nutes depress the button fig 5 c f shortly 1 s In the movement test mode the LED fig 5 c c flash es 6 times during each transmission Deactivating the movement test mode The movement test ends automatically after about 10 minutes or can be terminated by a brief depression 1 s of the button 6 Light control with a...

Page 7: ... light control manually when the load is switched off without presence detection depress briefly a key on any of the radio control transmitters programmed into the radio control If used with a radio control pushbutton for switching and dimming the light control can also be activated lo cally when the presence detector is programmed into the device the light control can be terminated by de pressing...

Page 8: ...held transmitter programmed into the dimming actuator Depress channel key 8 or of channel group C longer 1 s fig 6 b With a radio control push button for switching and dimming the temporary reference brightness value can be stored as permanent reference brightness value by depressing both rockers together double sided actuation for at least 3 seconds when the lamp is on fig 6 c This storage is con...

Page 9: ...utes has elapsed the dimming actuator switches off and returns to automa tic operation If the additional functions are terminated by switching off the dimming actuator switches off for at least 2 minutes It returns to automatic operation when no presence is detected anymore and after a fixed reten tion time of 2 minutes has elapsed 7 Light control with a switching actuator A radio control switchin...

Page 10: ...ff for 2 hours Switching on and off for 2 hours with a switching ac tuator is the same as described for the dimming actu ator cf section 6 6 7 5 Permanent change of the brightness reference value The current actual brightness can be stored in the dimming actuator as permanent reference brightness This value overwrites the reference brightness adjust ed manually on the presence detector with a hand...

Page 11: ...tion All OFF When a programmed All OFF key is pressed the ac tuator integrated into light control switches off for at least 2 minutes If no presence is detected anymore and after elapsing of a fixed retention time of 2 min utes the actuator switches off and returns to automa tic operation Master key special functions during lightscape operation The special functions during lightscape operation lis...

Page 12: ...ed brief depression of key 4 8 f The lightscape is switched off and remains in this state as long as presence is detected e g slide show This is only possible when the lightscape key last pressed is programmed in the actuator If no presence is detected and after the shut off delay of 2 minutes has passed the actuator involved in light control returns to automatic operation Returning to automatic i...

Page 13: ...s When programming the presence detectors into the radio control receiver cf section 2 Programming a detector into a radio control receiver make sure the presence detector specified as master unit is pro grammed first The brightness reference control must therefore not be set to minimum moon symbol since the detector would otherwise be identified as slave which means that it cannot be programmed a...

Page 14: ... Micro LR03 AAA Alkaline Note Never use carbon zinc batteries R 03 or rechargeable batteries Transmit frequency 433 42 MHz Modulation ASK Transmitting range max 100 m free field Coding 1 billion Angle of detection 360 Nominal range at desk level approx Ø 5 m at floor level approx Ø 8 m Fitting height for nominal range 2 5 m Shut off delay approx 2 min 1 h Brightness approx 3 2000 lx Temperature ra...

Page 15: ...d with the detector 12 Acceptance of guarantee We accept the guarantee in accordance with the corresponding legal provisions Please return the unit postage paid to our central service department giving a brief description of the fault Gira Giersiepen GmbH Co KG Service Center Dahlienstrasse 12 D 42477 Radevormwald Gira Giersiepen GmbH Co KG Postfach 1220 D 42461 Radevormwald Telefon 49 21 95 602 0...

Reviews: