FD 10
0549-990-01---10a_2019.11.indd
0549-990/02a
Page 52 of 69
Mounting and operating instructions
9.1.3
Safety elements
9.1.4 Feeding
No.
Description
Cause
Elimination
Checking time
Reaction
E20
01
SER Test
SER Test signal unsuccessful.
SER short-circuit to the earth.
Check the cabling of the sensor or the
jumper.
Prior to closing.
A
02
SER too slow.
SER reacts too slowly.
Check the cabling of the sensor.
Check for polarity reversal/test signal.
E21
01
SES Test
SES Test signal unsuccessful.
SES short-circuit to the earth.
Check the cabling of the sensor or the
jumper.
Prior to opening.
A
02
SES too slow.
SES reacts too slowly.
Check the cabling of the sensor.
Check for polarity reversal/test signal.
E22
01
EMY Test
EMY input on 24 V.
Check the jumper EMY.
Check the cabling of EMY.
Permanent.
H
No.
Description
Cause
Elimination
Checking time
Reaction
E30
01
30 V Error
30 V too low.
Mains failure, overload motor. Check the feed-in.
Replace the hardware.
Permanent.
A
02
30 V too high.
03
Error upon switching-on.
E31
01
24 V General
Error upon switching-on.
Overload 24 VDC onto terminals X101, X104, X108,
X110, X113.
Permanent.
A
Restart after 10 s.
02
Over- resp. under-voltage.
E32
01
24 V Safety
Over- resp. under-voltage.
Overload, short-circuit 24 VDC onto terminals
X108 or X110.
E33
01
24 V E-Lock
Error:
Over- resp. under-voltage.
Overload, short-circuit 24 VDC onto terminal X113.
02
Premonition:
Over- resp. under-voltage.
E34
01
24 V CAN
Over- resp. under-voltage.
Overload, short-circuit external power supply CAN.
9.1.6
Options
9.1.5 System
9.1.7
Closing sequence / Interlock function
No.
Description
Cause
Elimination
Checking time
Reaction
E50
01...99
System error
Unexpected hard
-
ware or software
event.
Switch the drive mechanism off/on.
Carry out a Factory Reset, carry out a Software Update,
inform the manufacturer.
Permanent.
W or H or F
E51
01...99
E52
01...99
No.
Description
Cause
Elimination
Checking time
Reaction
E60
00
Relay PCB 0
Option PCB has been remo
-
ved, its address changed or
become defective.
Check if the option is provided.
If defective: Replace or remove from the configu
-
ration.
Note:
Deleting of error 60
see chapter 13.5.1.
Permanent.
W
10
Relay PCB 1
Permanent.
W
20
Relay PCB
Permanent.
W
30
Fire-protection PCB
Permanent.
A
No.
Description
Cause
Elimination
Checking time
Reaction
E70 xx Bus setting
Address xx existing twice.
Correctly define the role of the closing sequence or the
interlock function.
Permanent.
W
E71
01
Connection
No connection.
Connect the terminals, check or replace the cable.
Check if all the participants are switched on.
Permanent.
W