background image

8

INSTALLATION INSTRUCTIONS

When the installation is completed, the vent terminal 
must be a minimum of two (2) inches (5.1 cm) from the 
exterior surface of the wall (see Figure 8). Make sure 
that all piping is properly braced. If the venting will 
pass through an enclosed area, make sure to leave 
at least one (1) inch (2.5 cm) clearance around the 
piping for air circulation.

Through-the-Roof Venting Installation

Cut or drill a hole through the roof and ceiling, slightly 
larger than the diameter of the vent pipe selected. 
The larger hole will allow for final alignment with the 
water heater. Construct the vent terminal assembly. 
Extend a section of pipe through the hole in the roof 
to the outside and attach the terminal assembly to the 
exterior end of the pipe. Connect and secure all piping 
and elbows from the power venter to the roof. Make 
sure that all horizontal runs have a minimum rise of 

1

/

4

 

inch per foot (21 mm/m) of run (see Figure 8). When 
the installation is completed, the vent terminal must 
be a minimum of eighteen (18) inches (45.7 cm) from 
the exterior surface of the roof (see Figure 8). Make 
sure that all piping is properly braced. If the venting 
will pass through an enclosed area, make sure to 
leave at least one (1) inch (2.5 cm) clearance around 
the piping for air circulation.
Condensation in the Venting System
In some installations, condensation will form in the  
horizontal runs of vent piping. To prevent condensa-
tion from flowing back into the power venter, install a  
condensate trap just past the first elbow of the vent 
piping system. Make sure that the condensate remov-
al tube flows to a suitable free-flowing drain.
Installation of the venting system

ALWAYS read and obey all safety messag-
es printed on the primer, cleaner, and cement 
containers. Primer, cleaner, and cements are 
extremely flammable. DO NOT store these prod-
ucts near heat, sparks, or flames. They are 
harmful or fatal if swallowed. Their vapours are 
also harmful. They may irritate eyes and can be 
absorbed through the skin. Failure to follow these 
instructions can result in property damage, per-
sonal injury, or death.

1)  Adjust the vent pipe length to properly fit the vent sys-

tem adaptor on the blower assembly outlet.

2)  Cut pipe ends squarely, removing all burrs and dirt.
3)  Dry fit the pipe/fitting to be connected to make sure 

they fit properly.

4)  Clean the pipe/fitting with the proper primer or cleaner.

5)  Apply a thin coat of cement to the fitting, avoiding pud-

dling inside.

6)  Apply a liberal coat of cement to the vent pipe, leaving 

no voids.

7)  QUICKLY assemble parts while cement is fluid! If you 

wait too long, re-coat pipe/fitting.

8)  Push the vent pipe completely into the PVC coupling, 

turning as it goes until it bottoms out.

9)  Hold pipe and fitting together for 30 seconds. Then 

carefully clean off any excess material with a cloth. 
Allow connections a sufficient time to cure before dis-
turbing.

10) Loosen the upper hose clamp on the rubber transi-

tion fitting and fully insert the CPVC pipe of the vent 
system adaptor (1.25” deep). Do not apply cement to 
the rubber transition fitting.

11)  Tighten the upper hose clamp to ensure the vent pipe 

is firmly secured and gas tight.

12)  Make sure that the lower hose clamp is firmly seated, 

secured and gas tight. Gently move the vent pipe side 
to side and vertically to ensure that it is securely in 
place and that there is no slippage.

When the installation is complete, visually inspect the 
venting system to make sure that all joints are prop-
erly connected and all instructions have been followed. 
Failure to properly install the venting system could 
result in property damage, personal injury, or death.

Water Piping

Refer to Figure 10 for a typical installation. Use of this 
layout should provide a trouble-free installation for the 
life of the water heater. Before making the plumbing 
connections, locate the COLD water inlet and the 
HOT water outlet. These fittings are both 

3

/

4

” N.P.T. 

male thread. Make sure that the dip-tube is installed in 
the cold water inlet. Install a shut-off valve close to the 
water heater in the cold water line. It is recommended 
that unions be installed in the cold and hot water lines 
so that the water heater can be easily disconnected, 
if servicing is required.

When assembling the hot and cold piping, use a 
good food grade of pipe joint compound, and ensure 
all fittings are tight. It is imperative that open flame is 
not applied to the inlet and outlet fittings, as heat will  
damage or destroy the plastic-lined fittings. This will 
result in premature failure of the fittings, which is 
not covered by the warranty.

Summary of Contents for UG50-59

Page 1: ...sult causing property damage personal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building From a neighbour s phone immediately call your gas supplier Follow the gas supplier s instructio...

Page 2: ...nt of an FVIR technology equipped water heater due to a flammable vapour shutdown is not covered under the terms of the Standard Basic Limited Warranty FVIR technology equipped with a flammable vapour sensor and the flame arrestor Safety Information 3 Installation Instructions 4 Location 4 Minimum Clearances 4 Combustion and Ventilation Air Supply 4 Requirements for Unconfined Spaces 5 Requirement...

Page 3: ... you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER or WARNING Serious injury or death can occur if you do not follow the instructions immediately Serious injury or death can occur if you do not follow the instructions WARNING AVERTISSEMENT DANGER WARNING AVERTISSEMENT DANGER DO NOT use this water heater ...

Page 4: ...um Clearances The minimum clearances from combustible material for this water heater are Two 2 inches 5 1 cm from the sides and rear four 4 inches 10 2 cm from the front and eighteen 18 inches 45 7 cm from the top see Figure 1 Combustion and Ventilation Air Supply In order for the water heater to operate properly it must be supplied with an uninterrupted flow of clean combustion and ventilation ai...

Page 5: ...municates directly with the outdoors by means of a duct This duct shall be sized according to CAN CSA B149 1 and terminate within one 1 foot above and within two 2 feet horizontally from the burner level of the appliance having the largest input In U S A refer to ANSI Z223 1 NFPA 54 1 All Air From Inside the Building see Figure 4 The confined space shall be provided with two per manent openings co...

Page 6: ...ed If the design and free area is not known it may be assumed that wood louvers and grilles will allow 20 25 free area and metal louvers and grilles will allow 60 75 free area Louvers and grilles must be installed in the open position or interconnect ed with the water heater so that they are opened automatically during water heater operation Corrosive Atmospheres If this water heater is to be inst...

Page 7: ...ipe must be supported every three 3 feet 91 cm and vertical runs of vent pipe must be supported every five 5 feet 1 5 m According to the CAN CSA B149 Natural Gas and Propane Installation Code plastic vent systems installed in Canada must be certified to the STANDARD FOR TYPE BH GAS VENTING SYSTEMS ULC S636 Components of the certified vent system must not be interchanged with other vent systems or ...

Page 8: ...embly outlet 2 Cut pipe ends squarely removing all burrs and dirt 3 Dry fit the pipe fitting to be connected to make sure they fit properly 4 Clean the pipe fitting with the proper primer or cleaner 5 Apply a thin coat of cement to the fitting avoiding pud dling inside 6 Apply a liberal coat of cement to the vent pipe leaving no voids 7 QUICKLY assemble parts while cement is fluid If you wait too ...

Page 9: ...es 30 cm B Clearance to window or door that may be opened 12 inches 30 cm C Clearance to outside corner D Clearance to inside corner 3 feet 91 cm E Clearance to service regulator vent outlet 3 feet 91 cm 6 feet 1 82 m F Clearance to each side of center line extended above meter regulator assembly 3 feet 91 cm within a height 15 feet 4 57 m above the meter regulator assembly 3 feet 91 cm within a h...

Page 10: ...er heater Should this relief valve need to be replaced use only a new temperature and pressure relief valve Never install an old or existing relief valve as it may be damaged or inadequate for the working requirements of the new water heater This new relief valve must meet all local codes or at a minimum the requirements listed above Never install any other type of valve between the relief valve a...

Page 11: ...lumbing system Leave the faucets open until a constant flow of water is obtained 4 Check all of the plumbing connections to make sure there are no leaks Gas Connections DO NOT attempt to use this water heater with any gas other than the type of gas shown on the water heater rating plate Failure to follow this instruction can result in property damage per sonal injury or death The gas piping must b...

Page 12: ...a mixing valve must be installed in the potable side of the system This will temper the water and reduce the risk of scalding 6 If the incoming water line to the heater is equipped with a check valve water meter or pressure reducing valve an expansion tank must be installed in the system This will prevent weeping from the water heater relief valve and pre mature failure of the heater due to expans...

Page 13: ...rs la maison Pompe de circulation Évent Figure 11 Wiring Diagram Blower Unit M 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 High Limit Switch Vacuum Switch Red 1 2 3 1 2 3 Yellow Black Blue Orange White Green Black White Green White ON OFF Switch 1 2 3 4 5 6 4 3 2 1 Green White Orange Blue Black Yellow Red Gas Valve Hot Surface Igniter Flame Sensor Flammable Vapor Sensor Green Green Black Power Cord Yellow Gre...

Page 14: ...th a minimum rise of 1 4 inch per foot 21 mm m of run r Has all the vent piping been secured with the appropriate primer and solvent based cement r Has the venting been supported at the proper intervals r Have precautions been taken against condensation flowing into the power venter r Water Piping Is the dip tube installed in the cold water inlet r Has a temperature and pressure relief valve been ...

Page 15: ...eater immediately contact a qualified installer ser vice agency or the gas supplier DO NOT light this water heater if It is not full of water The gas supplied does not match the type listed on the rating plate Gasoline or other flammable vapours and liquids have been stored in the vicinity of the water heater Failure to follow these instructions can result in property damage personal injury or dea...

Page 16: ...The temperature indicators will now display the new temperature setting Press and release the COOLER but ton until you have reached the desired setting HOLDING DOWN THE BUTTON WILL NOT CONTINUE TO LOWER THE SETTING The button must be pressed and released for each tem perature change desired To increase the temperature press and release the HOTTER button once The temperature indicators will now dis...

Page 17: ... function of the FV sensor is to detect the presence of flammable vapours before they enter the combustion chamber and ignite If the FV sensor detects the presence of flammable vapours while the water heater is operating the gas control will switch to lock out mode and the water heater will shut down If the water heater is not operating when the flammable vapours are detected the control will swit...

Page 18: ...ll of the joints are properly sealed If any part of the venting system is damaged it must be replaced by a qualified service technician Anode rods Thiswaterheaterisequippedwithtwo 2 anoderodsthat are designed to prolong the life of the glass lined tank The anode rods are slowly consumed protecting the glass lined tank from corrosion The anode rods should be checked every two 2 years If more than h...

Page 19: ... cold water supply manual shut off valve is open before lighting the burner Getting Service for your Water Heater If you are having problems with your water heater follow these three easy steps 1 Consult the Troubleshooting Guide con tained in this manual see Page 21 It lists the most common problems experienced with your gas fired water heater The solutions you find listed may provide a quick and...

Page 20: ...oor 8 Resettable thermal switch 9 Drain valve 10 Overflow tube 11 Dip tube 12 2 Magnesium anode rods 13 Temperature pressure relief valve 14 Flue baffle 15 Complete blower assembly 16 High limit switch 17 Rubber transition fitting 18 Vacuum switch 19 Plastic lined di electric galvanized nipple 1 2 3 4 7 9 10 11 12 13 14 15 17 18 16 Complete blower assembly 19 5 Complete burner assembly 8 6 ...

Page 21: ... that it is located properly and free from contamination Reposition the flame sensor rod or lightly clean it with an abrasive cloth 3 The hot surface ignitor may not be positioned correctly Reposition as necessary 4 Check that the hot surface ignitor and flame sensor rod are wired correctly and in good work ing condition 5 Low voltage to the water heater Check and repair 7 The gas valve driver cir...

Page 22: ...a confined area Provide fresh air ventilation The burner flame is too high Insufficient secondary air Provide fresh air ventilation Orifice too large Replace with correct orifice Defective gas control valve Replace with new gas control valve The flame burns at the orifice Low gas pressure Check with gas utility company Defective gas control valve Replace with new gas control valve High operating c...

Page 23: ...ets demand Combustion odours Insufficient secondary air Provide fresh air ventilation Heater installed in a confined area Provide fresh air ventilation Flue clogged Clean Check for source of trouble and correct Smoking and carbon formation sooting Insufficient secondary air Provide fresh air ventilation Low gas pressure Check with gas utility company Burner flame yellow lazy Refer to The burner fl...

Page 24: ...a free flowing drain in the event of water leakage 10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable water free to circulate at all times 11 If the heater has experienced the effect of thermal expansion due to excessive pressure exceeding 300PSI The result of excessive pressure usually ...

Reviews: