10
PVC AND CPVC PIPES:
PolyPro
®
InnoFlue
®
Make sure that all horizontal runs have a minimum rise of 1/4
inch per foot (21 mm/m) of run
(see Figure 2)
. Horizontal
runs of vent pipe must be supported every three (3) feet
(91 cm) and vertical runs of vent pipe must be supported every
five (5) feet (1.5 m).
CENTROTHERM
™
POLYPROPYLENE PIPE
(InnoFlue
®
single wall vent system):
PolyPro
®
InnoFlue
®
Make sure that all horizontal runs have a minimum rise of
5/8 inch per foot (56 mm/m) of run. Follow instruction of the
vent pipe manufacturer for proper vent support.
DURAVENT
®
POLYPROPYLENE PIPE
(PolyPro
®
single wall vent system):
PolyPro
®
InnoFlue
®
Make sure that all horizontal runs have a minimum rise of 1/4
inch per foot (21 mm/m) of run. Follow instruction of the vent
pipe manufacturer for proper vent support.
Concentric Vent Termination Kit Installation
(vertical)
A two (2) inch (5.1 cm) Concentric Vent Termination Kit (IPEX
model #196005 or #197040) (with a two [2] inch [5.1 cm]
restrictor screen from minimum lenght to twenty-five (25)
feet (7.6 m)), or a three (3) inch (7.6 cm) Concentric Vent
Termination Kit (IPEX model #196006 or #197009) (with
a three [3] inch [7.6 cm] restrictor screen from minimum
lenght to eighty (80) feet (24.4 m)) may be used for through
the roof termination installations. Using this Concentric Vent
Termination Kit will reduce the maximum allowable equivalent
vent pipe length for both air intake and exhaust systems (see
Table 1
).
Figure 9
and
Figure 10
illustrate the Concentric
Vent Termination Kit for through the roof installation. See
manufacturer’s instructions for complete installation details.
Solin
(Non inclus,
fourni par un tier)
Coude
de terminaison
Conduit court
Coude mâle et femelle
Toiture
Attache ou courroie
(Non inclus,
fourni par un tier)
*
Minimum de 18 po. (46 cm)
au-dessus de la toiture, ou
12 po. (30,5 cm) au-dessus du
niveau anticipé de neige, selon
le plus élevé des deux, et maximum
de 24 po. (61 cm) au-dessus
de la toiture pour l'entrée d'air
(sans soutien additionnel)
Flashing
Vent Termination elbow
*
Short piece of pipe
Street Elbow
*
Clamp or strap
Air intake
Roof
*
Min. 18 in. (46 cm) above roof,
or 12 in. (30.5 cm) above anticipated
snow level; whichever is the highest,
and max. 24 in. (61 cm) above roof
(without additional support)
*
*
Entrée d’air
Air intake
Exhaust
Entrée d’air
Sortie
(Not included,
field Supplied)
(Not included,
field Supplied)
Figure 9
* Minimum de 18 po. (46 cm)
au-dessus de la toiture, ou
12 po. (30,5 cm) au-dessus du
niveau anticipé de neige, selon le
plus élevé des deux, et maximum
de 24 po. (61 cm) au-dessus de la
toiture pour l'entrée d'air
(sans soutien additionnel)
Coude
de terminaison
Conduit court
Conduit mâle et femelle
Pente de 1/4 po. par pied
(20,8 mm par mètre) ou
tel que spécifié par le
manufacturier du conduit.
Toiture
Attache ou courroie
(Non inclus,
fourni par un tier)
Flashing
Short piece of pipe
Street Elbow
*
Minimum slope 1/4"/foot
(20.8 mm/m)
or as specified by
the pipe manufacturer.
*Min. 18 in. (46 cm) above roof, or
12 in. (30.5 cm) above anticipated
snow level; whichever is the
highest, and max. 24 in. (61 cm)
above roof (without additional support)
Roof
*
Clamp or strap
*
*
Vent Termination elbow
Air intake
Air intake
Exhaust
Entrée d’air
Entrée d’air
Sortie
Solin
(Non inclus,
fourni par un tier)
(Not included,
field Supplied)
(Not included,
field Supplied)
Figure 10
Pipe Assembly
DANGER
WARNING
CAUTION
AVERTISSEMENT
ATTENTION
ALWAYS
read and abide by all safety messages printed on
the primer, cleaner, and cement containers. Primer, cleaner,
and cements are extremely flammable.
DO NOT
store these
products near heat, sparks, or flames. They are harmful, or
fatal if swallowed. Their vapours are also harmful. They may
irritate eyes and can be absorbed through the skin. Failure
to follow these instructions can result in property damage,
personal injury, or death.
PVC AND CPVC VENT SYSTEM:
PolyPro
®
InnoFlue
®
Primers, cleaners, solvents, and cements are available for
PVC and CPVC pipe/fittings. When cementing the pipe/fittings,
make sure to use only materials approved for the type of
pipe/fittings to be installed and in all cases, follow the vent
pipe/fittings manufacturers joining instructions. Never use all-
purpose cements, commercial glues, and adhesives to join PVC
or CPVC pipe/fittings.
1) Adjust the vent pipe length to properly fit the vent system
adaptor on the blower assembly outlet.
2) Cut pipe ends squarely, removing all burrs and dirt.
3) Dry fit the pipe/fitting to be connected to make sure they fit
properly.
4) Clean the pipe/fitting with the proper primer or cleaner.
5) Apply a thin coat of cement to the fitting, avoiding puddling
inside.
6) Apply a liberal coat of cement to the vent pipe, leaving no
voids.
INSTALLATION INSTRUCTIONS