HD50CR-AS
- 15 -
V1.1
F700 submenu
(AN OUT MENU)
Setting of the analog outputs.
F710
:
analog output 1
F711
: 0-20 mA / 4-20 mA selection for the current output {default=4-20 mA}
F712
: 0-5 V / 0-10 V selection for the voltage output {default=0-10 V}
F713
: value of the quantity associated with the analog output corresponding to 0/4
mA and 0 V {default=-100 Pa}
F714
: value of the quantity associated with the analog output corresponding to 20
mA and 5/10 V {d100 Pa}
F715
: analog output test mode. The current output goes to the value entered. Set
OFF to exit the test mode.
F716
: analog output test mode. The voltage output goes to the value entered. Set
OFF to exit the test mode.
F720
:
analog output 2
F721
: 0-20 mA / 4-20 mA selection for the current output {default=4-20 mA}
F722
: 0-5 V / 0-10 V selection for the voltage output {default=0-10 V}
F723
: value of the quantity associated with the analog output corresponding to 0/4
mA and 0 V {default=0.0 °C}
F724
: value of the quantity associated with the analog output corresponding to 20
mA and 5/10 V {default=100.0 °C}
F725
: analog output test mode. The current output goes to the value entered. Set
OFF to exit the test mode.
F726
: analog output test mode. The voltage output goes to the value entered. Set
OFF to exit the test mode.
F730
:
analog output 3
F731
: 0-20 mA / 4-20 mA selection for the current output {default=4-20 mA}
F732
: 0-5 V / 0-10 V selection for the voltage output {default=0-10 V}
F733
: value of the quantity associated with the analog output corresponding to 0/4
mA and 0 V {default=0.0 %RH}
F734
: value of the quantity associated with the analog output corresponding to 20
mA and 5/10 V {default=100.0 %RH}
F735
: analog output test mode. The current output goes to the value entered. Set
OFF to exit the test mode.
F736
: analog output test mode. The voltage output goes to the value entered. Set
OFF to exit the test mode.
F800 submenu
(MODBUS MENU)
Modbus settings.
F801
: Modbus address {1…247, default=1}
F802
: RS485 baud rate in kbps {9.6 / 19.2 / 38.4 / 57.6 / 115.2, default=19.2}
F803
: RS485 communication mode {8N1 / 8N2 / 8E1 / 8E2 / 8O1 / 8O2, default=8E1}
F804
: waiting of 3.5 characters after transmission with Modbus protocol {nO=violate
protocol and go in receiving mode right after transmission / YES=respect pro-
tocol and wait 3.5 characters after transmission, default=nO}
F805
: enabling of the password for changing the configuration via Modbus {On/OFF,
default=OFF}