background image

 

GHIELMETTI AG | 

www.ghielmetti.ch | [email protected] | 02/2017 

 

Technical Data

 

 

Voltage supply 

U

H

 = +250 V

DC

 

+250 VDC 

 

Range of voltage supply: 

+176 ... 288 V

DC

 

Superposed AC peak-to-peak voltage: 

 12% @ rated voltage 

 

   

6% @ voltage limits 

Power consumption: 

1 W in standby 

 

6 W max. 

Bridging period on auxiliary voltage failure: 

 

50ms to U

H

 

 

250 V

DC

 

 

 

Display memory 

 

Number of indication memories input 

60 

Number of indication memories output 

20 

Number of group memories 

Indication delay time 

 5 ms 

 

 

Alarm contacts 

 

Alarm relays for «tripping command dis-

patched» indication 

2 NO contacts 

Switching capacity make/break 

20 VA 

Switching voltage 

250 V

AC/DC

 

Permission current 

0,1 A @ 250 V

DC

 

 

 

Matrix 

 

Number of columns (inputs) 

60 

Number of input taps 

60 

Number of input indication LED 

60 

Number of rows (outputs) 

20 

Number of output discontinuities 

20 

Number of output indication LED 

20 

 

 

Diode plugs 

 

Type 

GDS 621 ZS/20 sw 

(part. no. 674.212.002.00) 

Max. reverse voltage 

1000 V 

Max. permissible current 

1 A 

Current flow direction 

from column (+) to row (-) 

 

 

Insulation 

 

 

Specification: 

IEC 255-5  

Max. voltage (input, output) 

2,8 kV

eff

,  50 Hz 

Max. over voltage 

5 kV

peak

 

, 1,2/50 μs, 0,5 J,

 

3 positive and 3 negative pulse 

within 5 sec. each 

 

 

Climate conditions 

 

Operation temperature           

  -5 °C to +55 °C 

Storage temperature 

-25 °C to +55 °C 

 

 

Construction 

 

Mechanical dimensions  

19“, 6U 

W/H/D = 482,6 x 266.3 x 

154,58 mm 

Weight: 

approx. 7 kg 

 

 

Connectors 

 

Clamp-connectors  

max. wire section 2,5 mm² 

 

 

Summary of Contents for GKV 20x60 621 AM ELDP

Page 1: ...pping Matrix GKV 20x60 621 AM EALDP Matrix for 60 input to 20 output signals Input and Output signalling by LED indication Storing of LED indication by solid state memory Power supply 250 VDC 20 19 6U rack ...

Page 2: ... terminal is provided An uninterrupted safety earth ground must be provided from the main power source to the product input wiring terminals power cord or supplied power cord set Whenever it is likely that the protection has been impaired the product must be made inoperative and secured against any unintended operation Installation Initial Inspections Check the contents of the shipment for complet...

Page 3: ...pted or when the red central connecting plug is removed The memories can be reset directly by a push button Reset or by remote reset The function of all LED s may be checked by pressing the LED Test button The power supply of the relays and memory functions is 250VDC and feed an additional 5 VDC voltage for the LED function The monitoring of the power supply is done by two relay contacts A lockabl...

Page 4: ...i ch 02 2017 Interconnecting the Tripping Matrix Auxiliary screw mount connectors Connecting and Diode Plugs Input screw mount connectors max 60 input signals Output screw mount connectors max 20 output signals Auxiliary output screw mount connectors ...

Page 5: ...GHIELMETTI AG www ghielmetti ch info ghielmetti ch 02 2017 5 Block Diagram ...

Page 6: ...6 GHIELMETTI AG www ghielmetti ch info ghielmetti ch 02 2017 Front View ...

Page 7: ...GHIELMETTI AG www ghielmetti ch info ghielmetti ch 02 2017 7 Back View ...

Page 8: ...8 GHIELMETTI AG www ghielmetti ch info ghielmetti ch 02 2017 Side View ...

Page 9: ...itching voltage 250 VAC DC Permission current 0 1 A 250 VDC Matrix Number of columns inputs 60 Number of input taps 60 Number of input indication LED 60 Number of rows outputs 20 Number of output discontinuities 20 Number of output indication LED 20 Diode plugs Type GDS 621 ZS 20 sw part no 674 212 002 00 Max reverse voltage 1000 V Max permissible current 1 A Current flow direction from column to ...

Page 10: ...10 GHIELMETTI AG www ghielmetti ch info ghielmetti ch 02 2017 ...

Page 11: ...GHIELMETTI AG www ghielmetti ch info ghielmetti ch 02 2017 11 ...

Page 12: ...ice Switzerland 41 32 671 13 13 Phone 41 32 671 13 14 Fax info ghielmetti ch www ghielmetti ch GERMANY GHIELMETTI AG Office Germany 49 3371 402 754 Phone 49 3371 610 548 Fax deutschland ghielmetti ch www ghielmetti ch GHIELMETTI offices ...

Reviews: