On  20-30-40  when  the  temperature  of  the

evaporator thermostat bulb reaches the value of

+3

÷

4

°

C their electrical contacts move back to the

previous position activating a new freezing cycle

and deenergizing both the hot gas and the water

inlet valves (closed).

On 50-65-90 as soon as the timer microswitch

completes the bottom part of the cam and it is

pushed again, it activates a new freezing cycle

deenergizing both the hot gas and the water inlet

valves (closed).

NOTE

. On models 20, 30 and 40 the length

of the defrost/harvest cycle (not adjustable)

changes according to the ambient tempe-

rature (shorter for hi ambient temperature

and longer for low one).

COMPONENTS DESCRIPTION

A. WATER PUMP

The water pump operates continually throughout

the freezing cycle. The pump primes the water

from the sump to the spray system and through

the spray nozzles sprays it into the inverted cup

molds to be frozen into crystal clear ice cubes.

B. WATER INLET SOLENOID VALVE -

3/4 MALE FITTING

The water inlet solenoid valve is energized only

during the defrost cycle.

When energized it allows a metered amount of

incoming water to flow over the evaporator cavity

to assist the hot gas in defrosting the ice cubes.

The  water  running  over  the  evaporator  cavity

drops by gravity, through the dribbler holes of the

platen, into the sump reservoir.

On 20-30-40-50 water cooled versions the water

inlet solenoid valve has one inlet and two outlets

with two separate solenoids energized the first

(ice  productioon)  by  the  contacts  3-2  of  the

evaporator  thermostat  and  the  second  (water

cooled  condenser)  by  a  specific  hi  pressure

control.

C. HOT GAS SOLENOID VALVE

The hot gas solenoid valve consists basically in

two parts: the valve body and the valve coil.

During the defrost cycle the hot gas valve coil is

activated so to attract the hot gas valve piston in

order to give way to the hot gas discharged from

compressor to flow directly into the evaporator

serpentine to defrost the formed ice cubes.

D. BIN THERMOSTAT

The bin thermostat control body is located in the

front of control box behind the front panel.

The  thermostat  sensing  tube  is  located  into  a

bulb holder on the side wall of the ice storage bin

where it automatically shuts the icemaker OFF

when in contact with the ice and re-starts the

icemaker  when  the  ice  is  removed.  Factory

settings are 1

°

C (35

°

F) OUT and 4

°

C (39

°

F) IN.

E. CUBE SIZE CONTROL (EVAPORATOR

THERMOSTAT)

20-30-40

The cube size control (evaporator thermostat)

body is located in the control box behind the front

panel; it’s basically a reverse acting temperature

control which closes the contacts 3-2 when its

temperature decreases and closes the opposite

contacts 3-4 when the temperature rises.

The  thermostat  sensing  bulb  is  located  into  a

plastic tube (bulb holder) secured by two clips

directly to the evaporator serpentine.

This control determines the length of the freezing

cycle and correspondingly the size of the cubes.

A  lower  setting  will  produce  a  larger  cube

(oversize) while a higher setting a smaller cuber

(shallow size).

When  closed  on  contacts  3-2  it  activates  the

defrost or harvest cycle components.

The  cube  size  control  is  set  up  in  the  factory

(knob  in  the  black  dot  position)  and  doesn't

require  any  adjustment  when  the  ambient

temperature  remains  between  20  and  30

°

C

(70 and 90

°

F).

50-65-90

The evaporator thermostat with its sensing bulb

intimately in contact with the regrigerant outlet

tube from the evaporator senses the evaporating

refrigerant  temperature  (which  declines  in  the

course of the freezing cycle) and when this one

reaches the pre-set value, it switches its contacts

from 3-4 to 3-2 to activate the finishing cycle (2nd

phase) which has a pre-set extension determined

by the large diameter lobe of the timer cam.

F. FAN MOTOR (Air cooled version)

The  fan  motor  on  20-30-40  is  electrically

connected in parallel to the water pump and it

operates continuously only during the freezing

cycle  keeping  the  proper  head  pressure  by

circulating air through the condenser fins.

On  50-65-95  the  operation  of  fan  motor  is

controlled by a fan pressure control adjusted at

preset values.

G. COMPRESSOR

The  hermetic  compressor  is  the  heart  of  the

refrigerant system and it is used to circulate and

retrieve  the  refrigerant  throughout  the  entire

system.  It  compresses  the  low  pressure

refrigerant vapor causing its temperature to rise

and become high pressure hot vapor (hot gas)

which  is  then  released  through  the  discharge

valve.

H. WATER SPRAY SYSTEM

Through its nozzles it sprays the water in each

individual cup to be frozen into ice.

I.

SAFETY HI TEMPERATURE THERMOSTAT

Located in the control box it is a manual reset

switch that trips OFF the operation of the machine

when  its  bulb  (located  on  the  liquid  line  just

before  the  drier)  reaches  the  temperature  of

70

°

C (158

°

F).

Page 17

Summary of Contents for EH20

Page 1: ...accio a cubetti Machines gla ons Eisw rfelbereiter BEDIENUNGSANLEITUNG C A B nderungen vorbehalten Kopieren Vervielf ltigung Bearbeiten dieser Unterlagen im Ganzen sowie auch in Teilen ohne Genehmigun...

Page 2: ...eck list Controllo finale Liste de contr le final Endkontrolle Installation practice Schema di installazione Schema d installation Installation OPERATING INSTRUCTION ISTRUZIONI DI MISE EN SERVICE BETR...

Page 3: ...inch B 65 90 mm inch A 389 15 5 16 465 18 5 16 529 20 19 32 529 20 53 64 699 27 11 64 B 515 20 9 32 586 23 3 64 525 20 43 64 535 21 1 16 536 21 1 32 C 640 25 13 64 690 27 11 64 815 31 5 8 796 31 17 64...

Page 4: ...c...

Page 5: ...of freezing cycle Fine ciclo di congelamento Cycle de Cong lation Gefrierfas Fin du cycle de cong lation Ende der Gefrierfase 7 a i r a d a r f f a R d e l o o c r i A 0 r a b 1 1 0 1 bar 0 0 1 t l h...

Page 6: ...KOMPRESSOR 5 WATER PUMP POMPA POMPE A EAU WASSERPUMPE 6 FAN MOTOR VENTILATORE MOTOVENTILATEUR L FTERMOTOR 7 WATER SOL VALVE VALV INGR ACQUA VANNE ARRIV E EAU WAISSEREINLASSVENTIL 8 HOT GAS VALVE VALV...

Page 7: ...ERMOTOR 7 WATER SOL VALVE VALV INGR ACQUA VANNE ARRIV E EAU WAISSEREINLASSVENTIL 8 HOT GAS VALVE VALVOLA GAS CALDO VANNE GAZ CHAUDS HEISSGASVENTIL 9 PRESSURE CTRL PRESSOSTATO PRESSOSTAT DRUCKSCHALTER...

Page 8: ...OSTAT TERMOSTATO CONTENITORE THERMOSTAT CABINE SPEICHERTHERMOSTAT 4 COMPRESSOR COMPRESSORE COMPRESSEUR KOMPRESSOR 5 WATER PUMP POMPA POMPE A EAU WASSERPUMPE 6 FAN MOTOR VENTILATORE MOTOVENTILATEUR L F...

Page 9: ...IANT RAUMTEMPERATUR PRODUZIONE GHIACCIO PER 24 ORE ICE PRODUCED PER 24 HRS PRODUCTION DE GLACE PAR 24 HEURES EISW RFELPRODUKTION IN 24 STD 27 21 15 23 22 21 20 19 18 17 16 15 14 13 Kg C 10 21 32 38 21...

Page 10: ...EMP RATURE AMBIANT RAUMTEMPERATUR PRODUZIONE GHIACCIO PER 24 ORE ICE PRODUCED PER 24 HRS PRODUCTION DE GLACE PAR 24 HEURES EISW RFELPRODUKTION IN 24 STD RAFFREDDAMENTO AD ACQUA WATER COOLED MODELS CON...

Page 11: ...aily ice making capacity is directly related to the condenser air inlet temperatu re watertemperatureandageofthemachine To keep your CUBER at peak performance levels periodic maintenance checks must b...

Page 12: ...tothecoldwatersupplylinewithregularplumbing fitting and a shut off valve installed in an accessible position between the water supply line and the unit Water supply Water cooled models 65 90 The wate...

Page 13: ...ted drain 7 Drain fitting 8 Main switch 9 Power line 1 bar 14 psi 7 Check all refrigerant lines and conduit lines to guard against vibrations and possible failure 8 Have the bin liner and cabinet been...

Page 14: ...to the hot gas valve E Switch ON the power line disconnect switch Unit will start up in defrost cycle mode During this cycle the components energized are WATER INLET SOLENOID VALVE HOT GAS SOLENOID VA...

Page 15: ...bes produced will have a jagged rim of ice around the crown If it is thought necessary the above situations can be rectified by in the first case turning the control knob as little or as much as is re...

Page 16: ...caused by the progressive growth of the ice thickness into the inverted cup molds and to the flow of air drown through the air cooled condenser by the fan motor The above values are in relation as wel...

Page 17: ...e ice is removed Factory settings are 1 C 35 F OUT and 4 C 39 F IN E CUBE SIZE CONTROL EVAPORATOR THERMOSTAT 20 30 40 The cube size control evaporator thermostat body is located in the control box beh...

Page 18: ...rost time as required WARNING Never set the defrost time for longer than 4 minutes as this will jeopardize the compressor motor windings It goes without saying that an extension of the defrostperiodwi...

Page 19: ...f a brush dissolve the most resistant and remote scale deposits in the platen 21 31 40 1 On 20 30 40 switch ON again the machine at main power switch to start the icemaking process Allow the ice maker...

Page 20: ...stem for approx 10 minutes NOTE Do not mix descaling with disinfectantsolutiontoavoidthegeneration of a very aggressive acid 9 Flush out the disinfectant solution from the sump reservoir Slowly rotate...

Page 21: ...ri liberamente 6 Usando un panno pulito e umido pulire le pareti interne del contenitore del ghiaccio e le superfici esterne dell apparecchio 7 Osservare i dati riportati sulla targhetta fissata alla...

Page 22: ...bassa pressione dell acqua di alimentazio ne inferiore ad 1 bar pu causare dei disturbi di funzionamento dell apparecchio L uso di acque contenenti una quantit eccessiva di minerali dar luogo ad una p...

Page 23: ...ontrollati i bulloni di ancoraggio delcompressore Permettonoaquestidioscilla re sui propri supporti 9 Le pareti interne del contenitore del ghiac cio e le pareti esterne dell apparecchio sono state pu...

Page 24: ...to al motorino del timer attraverso i contatti normalmente aperti del microinterruttore ISTRUZIONI DI FUNZIONAMENTO AVVIAMENTO Dopo aver correttamente installato l apparec chio ed averlo collegato all...

Page 25: ...clo di congelamento pu essere modificata ruotando la manopola del termostato evaporatore posta nella scatola elettrica fino al raggiungimento della dimensione ottimale Se la temperatu ra del locale in...

Page 26: ...lvola solenoide di ingresso acqua posta sulla linea di alimentazione al condensatore Nei modelli 65 90 raffreddati ad acqua la pres sione di mandata mantenuta a 9 5 bar tramite l ausilio di una valvol...

Page 27: ...suoi contatti 3 2 quando la tempera tura scende ciclo di congelamento e li apre chiudendo i contatti 3 4 quando la temperatura sale ciclo di sbrinamento Questo controllo determina la durata del ciclo...

Page 28: ...ulla morsettiera del timer e attivati da un microinterruttore in fase di congelamento o di sbrinamento attraverso i contatti del rel di co mando Questo microinterruttore comandato da una camma in plas...

Page 29: ...l apparecchio all interruttore ge nerale esterno nei modelli 20 30 e 40 o all inter ruttore generale della macchina nei modelli 50 65 90 3 Prelevare tutto il ghiaccio stivato nel conte nitore in modo...

Page 30: ...vo il gambo del timer onde avere un secondo ciclo di sbrinamento 14 Quando dallo scarico si nota la fuoriuscita dell acqua posizionare l interruttore di lavaggio su funziona 20 30 40 e accendere il co...

Page 31: ...parois ext rieures du meuble 7 S assurer que la tension d alimentation correspond bien aux indications mentionn es sur la plaque signaletique fix e l arri re sur le chassis ATTENTION Tout incident occ...

Page 32: ...d autant plus opaques qu elle contiendra plus de sels Une pression trop basse inf rieure 1 bar peut tre une cause de mauvaise fabrication de la glace Une eau trop fortement chlor e peut tre am lior e...

Page 33: ...s t retir s S assurer que le compresseur est bien cal sur ses silenblocs 9 La cabine et l ext rieur de la machine t elle t essuy s proprement 10 Avez vous bien remis le manuel contenant les instructio...

Page 34: ...oule par les trous bien dans le r servoir d eau pour tre utilis dans le prochain cycle de congelation V RIFICATIONS DE FONCTIONNEMENT A La machine commence sa premier cycle de congelation avec le d ma...

Page 35: ...i par contre la temp rature am biente est sup rieure 30 C les cubes auront ten dence avoir des dentelures de gla ce autour de leur base Page 35 Il est possible de rem dier aux inconv nients illustr s...

Page 36: ...ance s l ve Sur les m mes machines refroidi eau et aussi danslemod l50 lahautepressionder frig rant a une plage de variation qui va de 8 5 10 bars etant contr l e par un pressostat H P qui commande pa...

Page 37: ...l ouverture de sortie glace dans la cabine de stockage NOTA Dans les mod les 20 30 et 40 la dur e du cycle de d givrage non r glable est reli e a la temperature ambiante plus courte avec temperature...

Page 38: ...nt est li la temp rature de l vaporateur par interm diaire de son bulbe plac sur un de ses tubes Cet appareil fixe la dur e du cycle de cong lation et parall lement la dimension des cubes Une coupure...

Page 39: ...u cycle de cong lation et le creux au d moulage La came est compos e de deux disques qui peuvent tre juxtapos s en cons quence pour augmenter ou diminuer la r partition en dur e de chaque phase Page 3...

Page 40: ...30 et 40 ou a l interrupteur du compresseur dans les 50 65 et 90 3 Enlevez toute la glace depos e dans la cabine de stockage pour viter qu elle soit contamin e par la solution de nettoyage 4 Dans les...

Page 41: ...que les microinterrupteurs soient dans la position debut phase de d givrage partie basse de la came Apres a mettre l interrupteur g n ral sur I ON Si faisant ont vient d activer la vanne d arriv e d e...

Page 42: ...gel frei bewegen k nnen 6 Benutzen Sie ein sauberes feuchtes Tuch um die Oberfl chen auf der Innenseite des Vorratsbeh lters sowie die Au enseite der Einheit zu reinigen 7 Beachten Sie das Typenschil...

Page 43: ...erschu an Mineralien enth lt entstehen zumeist tr be Eisw rfel Dar ber hinaus lagert sich Kalk an den Teilen des Wassersystems ab Wasserversorgung Schlie en Sie das 3 4 Steckverbindungsst ck des Wasse...

Page 44: ...der Vorratsbeh lter ausgewischt und die Au enseite des Beh lters gereinigt 10 Hat der Eigent mer Benutzer die Bedienungsanleitungerhaltenundister sie ber die Wichtigkeit der regelm igen Wartungskontr...

Page 45: ...Folgende Bestandteile sind aktiviert Wassereinlassventil Heissgasventil Timer Motor F Nach Beendung der Abtauphase etwa 3 Minuten denKompressorschalteraufONstellen HINWEIS W hrend des Abtauzyklus wird...

Page 46: ...nd Wartungsma nahmen F berpr fen Sie w hrend des ersten Abtau Ausgabezyklus da das Wasser korrekt in die Auffangvorrichtung flie t und diese korrekt aufgef llt wird Das bersch ssige Wasser mu in das b...

Page 47: ...derMaschineineinerRaumtemperaturvon21 C Das Sinken des Drucks h ngt mit der Reduzierung des Verdunstungsdrucks zusammen der von dem progressiven Wachstum der Eisst rke in den Kegelformern unddemvomVe...

Page 48: ...n den Kontakten 3 2 des Verdunster thermostats w hrend des Abtauzyklus aktiviert W hrend des Abtauzyklus wird das die Hei gas Ventilspuleaktiviert undziehtsomitdenKolben desHei gas Magnetventils an Hi...

Page 49: ...0 140 psig sorgt sie daf r da der Druck des K hlmittelsystems gehalten oder gesenkt wird indem sie die Spule des Wassereinla Magnetventils das wiederum den Flu des K hlwassers zum Kondenser steuert ak...

Page 50: ...den 20 30 40 Modelle das Ger t wieder durch dem Hauptschalter einschalten um die Eisproduktion beginnen zu lassen Seite 50 Lassen Sie den Eisbereiter ungef hr 20 Minuten lang arbeiten Drehen Sie dann...

Page 51: ...9 Die Desinfizierungsl sung vom Reservoir Beh lter rausfliessen lassen DerTimerknopflangsamimUhrzeigersinndrehen bis der Mikroschalter die Start Position der Abtauphase erreicht Dann gleich den Haupt...