GGM GUF Series Operation Manual Download Page 8

9-4 Operating by I/O signals

  The motor can be operated and stopped from the external signals.

① Setting the “External operation signal input” parameter

 Set the parameter (PAr-> io.En-> on / oFF) to "on" (page 14)
"on"-External I / O enabled, "oFF"-External I / O disabled / The factory setting is "oFF".

② Run command [Run when FWD or REV input is ON]

 Forward rotation when FWD (No. 2) + LCOM (No. 7)
 connected / Reverse rotation when REV (No. 3) + LCOM (No. 7) connected
 (Operation should be made with front control Run position, no operation at stand-by) 

③ Pin allotment of CN4

8

Applicable lead wire AWG 26~20 ( 0.14~0.5mm² )

※ Function in [ ] is assigned at shipment
※ Can be assigned required functions to 5 input signals(X0~X4) and 3 output signals(Y0~Y2)

  

 Input signals : Can be used 5 functions out of FWd(CW rotation), rEv(CCW rotation), P0 (operation

 data 1), P1(operation data 2), P2(operation data 2), A.rst(Alarm reset), E.Err(External alarm)
  

 Output signals : Can be used 3 functions out of SPd(Speed output), AL.on( Alarm output),   

  AL.ov(Overvoltage alarm output), OvLd(Overload alarm output), MovE(Motor operation output)

Pin

No.

1

2

3

4

5

6

7

8

9

10

11

12

13

X0

X1

X2

X3

X4

LCOM

Y0+

Y0-

Y1+

Y1-

Y2+

Y2-

Terminal

Name

HCOM

Input

Output

Common

Signal
Name

                                          Description

Input signal common : Sink Logic : +24V,
Source Logic : 0V (GND)

Input

Input

Input

Input

Input

Common

Output

Output

Output

Output

Output

Output

[FWD]

[REV]

[P0]

[P1]

[A.rst]

-

[SPD]

[AL.on]

[MovE]

The motor rotates is FWD direction during signal “ON

The motor rotates is REV direction during signal “ON”

Select the operating data

Select the operating data

Reset the alarm

Input signal common

For every rotation of the motor, 30 pulses are output

It turns off when an alarm is generated (Normally closed)

It turns on when the motor is operated (Normally opened)

Motor

Drive

I/O Signal

AC power input

Summary of Contents for GUF Series

Page 1: ...TION MANUAL Headquarters 1st Factory 22 Gyeongin ro 3beon gil Bucheon si Gyeonggi do Republic of Korea Tel 82 32 664 7790 Fax 82 32 611 7791 Attached research institute No 2 factory 180 Oksan ro Buche...

Page 2: ...t is being applied Be sure to only perform repair or installationwork after cutting off the power supply Failure to do so may cause an electric shock Have a qualified person with relevant knowledge in...

Page 3: ...0V three phase 200 240V Permissible range 10 50 60 Hz Permissible range 5 Rated Output Current Rated Torque Maximum Instantaneous Torque Rated Speed Speed Control Range Speed Regulation Power input Te...

Page 4: ...240V Three phase 200 240V F Series Unit Type GGM Co LTD 4 58 90 4 111 116 STAND BY RUN FWD REV GGM GGM CN3 SENSOR CN2 MOTOR CN4 I O CN1 200 240V 80 52 2 4 5 HOLE 98 2 4 5 THRU 2 M3 DP8 64 5 104 5 124...

Page 5: ...l buttons 5 Operation by external I O PLC etc Start Stop change of rotational direction multi level speed operation by external I O etc 6 Display indication load ratio actual speed etc Display of load...

Page 6: ...r turning on the alrarm code AL oP Pervention of operation at power on alarm is displayed and the do not operated motor Set the operation switch from RUN to STAND BY for release an alarm before use mo...

Page 7: ...Lock When pressing the S button the rotation speed is determined When the display is blinking the rotation speed has not set Can lock the operation by pressing the S button for more than 5 seconds in...

Page 8: ...P0 operation data 1 P1 operation data 2 P2 operation data 2 A rst Alarm reset E Err External alarm Output signals Can be used 3 functions out of SPd Speed output AL on Alarm output AL ov Overvoltage a...

Page 9: ...sistor output type programmable controller Attention For the Y0 Y1 and Y2 be sure to keep the current value at 100mA or less If the current exceeds this value connect the limiting resistor R 1 Limited...

Page 10: ...side 2 Select the operation data number suing the P0 P1 and P2 inputs 3 When the FWD or REV input is turned ON the motor will rotate 4 Switch the operation data number using the P0 P1 and P2 inputs 5...

Page 11: ...11 10 Setting and 7 segments display 10 1 Monitor mode...

Page 12: ...12 10 2 Input Output setting mode...

Page 13: ...10 3 Parameter setting mode 1page 13...

Page 14: ...10 3 Parameter setting mode 2page 14...

Page 15: ...10 3 Parameter setting mode 3page 15...

Page 16: ...10 3 Parameter setting mode 4page 16...

Page 17: ...or is calculated and input the conveyor speed can also be displayed When increasing the motor rotation speed using the external input the converted speed can be displayed After the power is turning on...

Page 18: ...on alarm External I O function External input function X0inputfunctionselection X1inputfunctionselection X2inputfunctionselection X3inputfunctionselection X4inputfunctionselection Externaloutputfuncti...

Page 19: ...gnable alternative input functions Description For every rotation of the motor 30 pulses are output SPEED RPM SPEED OUT Hz 60 Sec 30 pulses It is output when an alarm is generated Normally closed It i...

Page 20: ...T ERROR Stop input Check the power supply voltage If this alarm occurs during operation reduce the load or make the acceleration deceleration time longer Review the ambient temperature Check the wirin...

Reviews: