Page 20
open command being given
stop command being given
close command being given
Report Command description
OPERATING STATUS DISPLAY
The control TS956 can display up to threedifferent status conditions one after another. Each
status is displayed with a letter and a number. The letter and the number are flashing alternately,
thereby the control differentiates between a FAULT =
F
and a command =
E.
Report
Description
Measure to solve the problem
Pass door contact open
Check the proper operation of pass door contact, or
whether the supply cable is broken
Emergency stop activated
Check the emergency stop is activated, or whether the
supply cable is broken
Safety open or close limit
operated
Turn mains supply OFF and move the shutter downwards
- with the manual operator- until the safety limit is free
or the open limit should be re-adjusted.
Emergency operator or
motor-winding thermal pro-
tection operated
Check emergency operator or whether the drive unit is
overloaded.
Phase rotation failure
Check main supply phase rotation turns right
Failure pass door contact
X 2.1- X 2.2
Check pass door circuit’s transition resistance and
weather pass door switch works
Failure input pass door
X 2.1- X 2.2
For reset switch control panel OFF-ON
adjusted cycles for maintenance reached
Display off = short circuit or overload at the 24V DC supply