24
Limit switches
Check the final limit positions by opening and closing the door completely. The safety zone
must not be reached.
Brake
Warning – Injury or danger to life possible!
Carry out brake test. Overrun depends on the door and its equipment. The
manufacturer's specifications must be observed.
Warning – Injury or danger to life possible!
Service life of the brake - replacement of the entire brake with motor in the case of:
Operation with mains supply: after 750,000 door cycles
Operation with frequency inverter: after 1,500,000 door cycles