background image

7

GF U3000 V2 Ultrasonic Flowmeter

Modbus Supplement to the operating instructions

The management system programmer may choose to use the Time and Date associated with the GF U3000 V2 Ultrasonic Flowmeter, 
or use the Time and Date associated with their system time by simply reading a block of registers starting at either offset 100 or 
offset 104.

All data in the register set changes once each second. All registers should be read at the same time; however, it is possible to halt 
the update of these registers before reading to allow the management system to read individual registers at its leisure. In this way, 
it is guaranteed that all data points during the read will pertain to the same set (the same second).

It should be noted that if reading these registers takes more than a second, the time and Date stamp will jump and data for the mis-
sing second will be lost. Readings must be made in real time.

GF U3000 V2 Ultrasonic Flowmeter Modbus Register Map.

Reg
Num

Reg
Idx

Use

Type

Notes

Access1 Source/Comment

1

0

Check 
value / 
Interface 
version

uint16

0x5A00

R

This is a check value and an interface 
version number. This version is zero. All 
values start at the base 0x5A00.

2

1

Device ID uint16

GF U3000 V2 Ultrasonic 
FlowmeterC=0x0035
GF U3000 V2 Ultrasonic 
FlowmeterHC=0x0036
GF U3000 V2 Ultrasonic 
FlowmeterCO=0x0037
GF U3000 V2 Ultrasonic 
FlowmeterHCO=0x0038

R

GF U3000 V2 Ultrasonic Flowmeter 
variant.

3,4

2,3

Serial 
Number

uint32

E.g., 20111
0x0000, 0x4E8F

R

Unit Serial Number

5

4

Regime

uint16

Measurement Regime:3

RW

0 = Metric1
1 = Imperial
2 = US Imperial
3 = Metric2
> 3 = reserved (defaults to Metric1)

Temperature Regime: 1

0 = ⁰C,
1 = ⁰F

Reserved:11

For future use.

6

5

Instru-
ment 
Control 
Flags

uint16

Lock-out updates:1

RW

Writable from MBM only. 1= stop 
updating registers (excludes action/
response bits)

Lock screen mode:1

Can be set/reset from MBM. Set Lock 
screen mode active= 1

Update Lock Screen Mode:1

Action/Response bit. 1=update; set to 0 
by instrument when complete.

Save Measurement Regime:1

Save the current measurement 
regimes. (including temperature)

Reserved:12

7

6

Instru-
ment 
General 
Flags

uint16

Screen lock mode active:1

R

Local screen is locked

Remote Lockout:1

Local device has locked out remote 
(MBM) write updates (excluding regime 
changes)

Summary of Contents for U3000 V2

Page 1: ...er 2026161 F U3000 V2 Modbus Supplement MA_00138 EN 00 07 2022 Georg Fischer Piping Systems Ltd CH 8201 Schaffhausen Switzerland 41 52 631 30 26 info ps georgfischer com www gfps com 7 Units 4 Velocit...

Page 2: ...dentification 13 3 9 Status Flags 14 4 GLOSSARY 14 Original instruction manual Disclaimer The technical data are not binding It does not constitute expressly warranted characteristics and neither guar...

Page 3: ...the next unit It is the responsibility of the user to install cable and wire to the MULTICOMP MP002510 Modbus plug connector The connection diagram is shown below in Figure 1 Note that the connection...

Page 4: ...for the GF U3000 V2 Ultrasonic Flowmeter The Modbus specification for RTU mode defines an 11 bit character frame containing an 8 bit character If Parity is used then only one stop bit is required If...

Page 5: ...ssages The following message types are supported from the Modbus Application Protocol Specification Message Type Message Number Notes READ HOLDING REGISTERS 03 0x03 Read a contiguous block of register...

Page 6: ...of the mantissa are stored in the higher address Some registers below contain bit mappings These values may be manipulated via the MASK WRITE REGISTER command 22 as outlined in Table 1 Bit fields are...

Page 7: ...value Interface version uint16 0x5A00 R This is a check value and an interface version number This version is zero All values start at the base 0x5A00 2 1 Device ID uint16 GF U3000 V2 Ultrasonic Flow...

Page 8: ...12 MBM to control digital output s on a unit 12 100 Reserved uint16 Sec 6 RZ 0 to 59 101 102 100 101 Date Time uint32 Min 6 R 0 to 59 Hour 5 0 to 23 Day 5 1 to 31 1st 1 Month 4 1 to 12 Jan 1 Year 6 b...

Page 9: ...d 13 Reserved allocation of 13 LS bits of reg 133 Hot probe fault 1 Faulty or disconnected hot probe Cold probe fault 1 Faulty or disconnected cold probe Signal Loss 1 Device is online and has lost si...

Page 10: ...Registers Registers highlighted as RW are updateable They provide the ability to update the unit s configuration Except for the Regime regis ter register 5 offset 4 all updateable registers can be up...

Page 11: ...lags associated with them Values can be written into these registers but no action will be taken until the associated flag is activated There are three key flags that must be considered when updating...

Page 12: ...uint16 year month day hour minute second Read the time and date starting at register offset 8 timeNdate Read2HoldingRegisters 8 Extract elements second timeNdate mod 2 6 timeNdate timeNdate div 2 6 m...

Page 13: ...address 136 with the AND mask being set to 0xFFEF and the OR mask being 0x0010 This will start the update 5 Send a MASK WRITE REGISTER message command 22 or 0x16 to register address 5 with the AND mas...

Page 14: ...entry for the moment Status Flags Online The unit is currently reading flow This flag is reset when the unit stops reading flow and enters the configuration mode Status Flags Urgent Error An urgent er...

Page 15: ...15 GF U3000 V2 Ultrasonic Flowmeter Modbus Supplement to the operating instructions...

Page 16: ...td Unit 2501 U Tower 120 Heungdeok Jungang ro Yeongdeok dong Giheung gu Yongin si Gyeonggi do Phone 82 31 8017 1450 Fax 82 31 217 1454 kor ps georgfischer com www gfps com kr Malaysia George Fischer M...

Reviews: