background image

11

GF U3000 V2 Ultrasonic Flowmeter

Modbus Supplement to the operating instructions

Regime

Property

Metric1

Imperial

US Imperial

Metric2

Velocity

m/s

ft/s

ft/s

m/s

Volumetric Flow

l/s

gallons/s

US gallons/s

m

3

/hr

Volume

litres

gallons

US gallons

m

3

Energy

KWH

BTU

BTU

KWH

Power

KWH

BTU/sec

BTU/sec

KWH

Acceleration

m/s

2

ft/sec

2

ft/sec

2

m/s

2

All other updateable registers can be set by either the unit, or by the MBM. A simple example are the Totals registers. In normal 
operation they are updated and may be read by the MBM, but they may also be used to rest the totals using the procedure outlined 
in the ensuing paragraphs.

Updateable unit functionality includes:

• 

Updating forward and reverse flow totals, 

• 

Updating forward and reverse energy totals (reverse energy totals are not yet implemented), 

• 

Updating the lock screen mode, 

• 

Updating the damping mode and time, and 

• 

Updating the dynamic damping acceleration threshold.

Changes to these registers need to be specifically allowed by the unit. Changes to totals may be disallowed by setting the “Block 
remote total changes” setting to Yes in the Modbus settings menu. Blocking all updates by the MBM is accomplished by setting “Block 
all remote changes” to “Yes”. The status of these settings is reflected in register 8 (offset 7) bit 2 and register 7 (offset 6) bit 1 res-
pectively (see the Map).

3.5 

General Procedure for Updating Unit Settings

Other than the Modbus measurement regime, all registers that result in settings or values in the local unit being updated, have flags 
associated with them. Values can be written into these registers, but no action will be taken until the associated flag is activated.

There are three key flags that must be considered when updating these registers.

The first and most important is the Lock-out Updates (bit 0) in the Instrument Control flags register number 6 (address 5). This bit 
ensures that registers will not be updated by the device until the flag is reset. The purpose is to ensure that the values being updated 
are not overwritten with updated values from the unit. For example, imagine resetting a total only to have its value overwritten by an 
update from the unit before it can be set in the unit. More examples will follow, but in general it is good practice to set this flag befo-
re writing and reset it after the operation is complete. It is important to remember that values will not be updated until this bit is 
reset.

The other two bits that are important are the Remote Total Changes Disabled flag (bit 2) of the Instrument Status flags register 8 
(address 7), and the Remote Lockout flag (bit 1) of the Instrument General Flags register 7 (address 6). Together these are referred 
to as the inhibit bits.

The Inhibit flags are controlled by the local unit. If the “Remote Total Changes Disabled” flag is set, it blocks the ability of the MBM to 
update or reset the totalling registers. If the “Remote Lockout” flag is set, it blocks the ability to write and update any registers that 
may change the unit’s settings. This includes all writeable registers. This allows a field technician to stop the unit’s settings being 
changed remotely while maintenance or fault finding is being undertaken. This setting should be reset once the task is complete.

Summary of Contents for U3000 V2

Page 1: ...er 2026161 F U3000 V2 Modbus Supplement MA_00138 EN 00 07 2022 Georg Fischer Piping Systems Ltd CH 8201 Schaffhausen Switzerland 41 52 631 30 26 info ps georgfischer com www gfps com 7 Units 4 Velocit...

Page 2: ...dentification 13 3 9 Status Flags 14 4 GLOSSARY 14 Original instruction manual Disclaimer The technical data are not binding It does not constitute expressly warranted characteristics and neither guar...

Page 3: ...the next unit It is the responsibility of the user to install cable and wire to the MULTICOMP MP002510 Modbus plug connector The connection diagram is shown below in Figure 1 Note that the connection...

Page 4: ...for the GF U3000 V2 Ultrasonic Flowmeter The Modbus specification for RTU mode defines an 11 bit character frame containing an 8 bit character If Parity is used then only one stop bit is required If...

Page 5: ...ssages The following message types are supported from the Modbus Application Protocol Specification Message Type Message Number Notes READ HOLDING REGISTERS 03 0x03 Read a contiguous block of register...

Page 6: ...of the mantissa are stored in the higher address Some registers below contain bit mappings These values may be manipulated via the MASK WRITE REGISTER command 22 as outlined in Table 1 Bit fields are...

Page 7: ...value Interface version uint16 0x5A00 R This is a check value and an interface version number This version is zero All values start at the base 0x5A00 2 1 Device ID uint16 GF U3000 V2 Ultrasonic Flow...

Page 8: ...12 MBM to control digital output s on a unit 12 100 Reserved uint16 Sec 6 RZ 0 to 59 101 102 100 101 Date Time uint32 Min 6 R 0 to 59 Hour 5 0 to 23 Day 5 1 to 31 1st 1 Month 4 1 to 12 Jan 1 Year 6 b...

Page 9: ...d 13 Reserved allocation of 13 LS bits of reg 133 Hot probe fault 1 Faulty or disconnected hot probe Cold probe fault 1 Faulty or disconnected cold probe Signal Loss 1 Device is online and has lost si...

Page 10: ...Registers Registers highlighted as RW are updateable They provide the ability to update the unit s configuration Except for the Regime regis ter register 5 offset 4 all updateable registers can be up...

Page 11: ...lags associated with them Values can be written into these registers but no action will be taken until the associated flag is activated There are three key flags that must be considered when updating...

Page 12: ...uint16 year month day hour minute second Read the time and date starting at register offset 8 timeNdate Read2HoldingRegisters 8 Extract elements second timeNdate mod 2 6 timeNdate timeNdate div 2 6 m...

Page 13: ...address 136 with the AND mask being set to 0xFFEF and the OR mask being 0x0010 This will start the update 5 Send a MASK WRITE REGISTER message command 22 or 0x16 to register address 5 with the AND mas...

Page 14: ...entry for the moment Status Flags Online The unit is currently reading flow This flag is reset when the unit stops reading flow and enters the configuration mode Status Flags Urgent Error An urgent er...

Page 15: ...15 GF U3000 V2 Ultrasonic Flowmeter Modbus Supplement to the operating instructions...

Page 16: ...td Unit 2501 U Tower 120 Heungdeok Jungang ro Yeongdeok dong Giheung gu Yongin si Gyeonggi do Phone 82 31 8017 1450 Fax 82 31 217 1454 kor ps georgfischer com www gfps com kr Malaysia George Fischer M...

Reviews: