background image

pg 2 of 12

‡ SIGNET

 5900 Salinity Monitor

PPT

PPT

Low setpoint =

Adjustable hysteresis =

Relay active =

Relay inactive =

High setpoint =

Adjustable hysteresis =

Relay active =

Relay inactive =

5.  Relay Operation

5.1  LOW alarm mode

The relay is active when the solution salinity in Parts Per Thou-
sand (PPT) drops below the setpoint, and is inactive when the
solution salinity rises above the setpoint plus hysteresis.

4.  Relay Connections

Two internal relay contact sets (COM, NO, and NC) may be used
for external device control.  Front panel LED annunciators indicate
the activation status of each relay.  Each relay can control up to
two devices simultaneously.  Relay operation modes include Low
alarm, High alarm, and Proportional Pulse.

Common device connections include:
• Pulse mode - metering pump control
• Pulse mode - solenoid valve control
• Low or High mode - warning lamps
• Low or High mode - bells or sirens
• Low or High mode - external heavy-duty relay

Wiring Example (right)

Device A is powered when relay 2 is inactive (front panel LED
"off").  Power is discontinued when the relay 2 setpoint is reached
(front panel LED "on").  Device B is not powered when relay 2 is
inactive.  Power is applied after the relay 2 setpoint is reached.

+

-

-

Device

A

External AC/DC
power

+

-

+

Device

B

Relay 1

Relay 2

NC

C

NO

NC

C

NO

5900 Terminals

NO  C   NC

Relay 
Inactive

Relay 
Active

NO  C   NC

Technical Notes:

Maximum relay contact ratings:  5 A @ 30 VDC, 5 A @ 125
VAC, or 3 A @ 250 VAC

An external heavy-duty relay must be used for devices with
surge currents or operating currents that exceed the above
specifications.

5.2  HIGH alarm mode

The relay is active when the solution salinity (PPT) rises above
the setpoint, and is inactive when the solution salinity drops below
the setpoint plus hysteresis.

5.3  Proportional PULSE mode

The proportional pulse relay configuration is primarily designed for metering pump control.  The operator is prompted to enter a minimum
and maximum salinity setpoint and maximum pulse rate for the assigned relay.  Relay pulse width is fixed at 130 ms.

Metering pump chemical addition (dry contact activation type required)

Relay 1 

or Relay 2

10

PPT

30
PPT

0 pulses

PPT

Relay 1
or Relay 2

30
PPT

10

PPT

PPT

300 pulses

300 pulses

0 pulses

Relay 1 Rate:

    300 Pulses/min >

Relay 1: Pulse

10.0000  30.0000>

Relay 1: Pulse

30.0000  10.0000>

Relay 1 Rate:

300 Pulses/min >

Example 1:

  As the process salinity (PPT) rises above the

minimum pulse setpoint (10 PPT) the relay begins pulsing,
triggering the metering pump for deionized water addition.  As the
process salinity continues to rise, pulsing accelerates proportion-
ally until the maximum programmed pulse rate of 300 pulses/
minute and setpoint (30 PPT) is reached, forcing the process
salinity back down to intended levels (e.g. < 10 PPT).

Example 2:

  As the process salinity (PPT) falls below the minimum

pulse setpoint (30 PPT) the relay begins pulsing, triggering the
metering pump for chemical addition.  As the process salinity
continues to decrease, pulsing accelerates proportionally until the
maximum programmed pulse rate of 300 pulses/minute and
setpoint (10 ppt) is reached, forcing the process salinity back up to
intended levels (e.g. < 30 PPT).

Summary of Contents for SIGNET 5900

Page 1: ...ered non isolated maximum loop impedance 350 with a 12 V instrument supply voltage 950 with a 24 V instrument supply voltage To isolate output and prevent ground loop problems 1 Use monitor device wit...

Page 2: ...ents or operating currents that exceed the above specifications 5 2 HIGH alarm mode The relay is active when the solution salinity PPT rises above the setpoint and is inactive when the solution salini...

Page 3: ...0 100 See dial kit for additional information 6 1 VIEW Menu Menu Displays A G Factory default displays shown in menu column 1 A Active display of salinity PPT and temperature in degrees celsius C or f...

Page 4: ...int 00 0000 999999 units G Sets relay hysteresis 00 0000 999999 units Set to zero to disable feature H Sets relay minimum and maximum pulse setpoint 00 0000 999999 units I Sets relay pulse rate 000 30...

Page 5: ...any test solution for calibration purposes The 2 step WET CAL process first allows for verification or calibration of temperature followed by verification or calibration of salinity PPT using a known...

Page 6: ...A Adjust 3 88 mA Low High ENTER SAVING displayed A B C D E F Contrast 3 Display Decimal Display Average Low Set 4 mA 0 0000 PPT Set 20 mA 40 000 PPT 4 mA Adjust 4 00 mA 4 mA Adjust 4 00 mA Display Dec...

Page 7: ...acts Max voltage rating 5 A 30 VDC 5 A 125 VAC or 3 A 250 VAC power factor 1 0 Hysteresis User adjustable Current output 4 to 20 mA non isolated internally powered fully adjustable and reversible Upda...

Page 8: ...40 0000 WET CAL Relay 1 Low 10 0000 PPT Relay 1 Hys 4 0000 Relay 1 Pulse 10 0000 30 0000 Relay 1 Rate 120 Pulses min Last CAL 01 01 98 Sensor type and cell constant Process Units Min Max meter dial r...

Page 9: ...age 0 5 Off 0 sec Low 4 sec High 8 sec 00 0000 999999 00 0000 999999 3 0 5 0 mA 19 21 mA Celsius or Fahrenheit 0 00 9 99 3 Low 4 sec 00 0000 PPT 40 0000 PPT 4 00 mA 20 00 mA C 2 00 A B C D E F G H I M...

Page 10: ...fy sensor wiring B Verify instrument temperature input Remove Black and White sensor wires from rear Temp IN and Iso Gnd terminals then place a 1100 resistor across terminals Power instrument and veri...

Page 11: ...Pg 11 of 12 SIGNET 5900 Salinity Monitor...

Page 12: ...nue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website www gfsignet com Or call in the U S 800 854 4090 GEORGE FISCHER Piping Systems 3 59...

Reviews: