background image

5

263X Series Chlorine Electrodes

pH Compensation for Free Chlorine

Amperometric free chlorine sensors measure only hypochlorous 
acid. As noted in the text above and in Figure 3, the ratio 
of hypochlorous acid and hypochlorite is pH dependent. In 
many applications the process pH is relatively stable and no 
correction is needed. However, where the pH of the water 
changes signi

fi

 cantly, accurate free chlorine measurement 

requires pH compensation. With the addition of a pH sensor, the 
Signet 8630 transmitter will automatically compensate the free 
chlorine reading for changes in pH.

5.0  5.5     6.0     6.5     7.0    7.5     8.0     8.5     9.0     9.5  10.0

100

90

80

70

60

50

40

30

20

10

0

HOCl

OCl

Ø

%  free chlorine

pH  at 25 °C

Chlorine Measurement by Amperometric Sensors

Signet chlorine sensors are membrane-covered amperometric 2-electrode sensors. A gold or platinum cathode acts as the working 
electrode with a silver halide acting as the counter electrode. Depending on the species to be analyzed, a polarization voltage is 
applied between the two electrodes. When placed into service, the chlorine species of interest diffuses across the membrane and 
is reduced at the cathode surface. For the case of total chlorine, the analyte reacts with the 

fi

 ll solution to produce an intermediate, 

which is subsequently reduced at the cathode surface. At the same time, the silver anode is oxidized to form a silver halide. The 
current generated at the cathode is proportional to the rate of diffusion through the membrane and the concentration of chlorine in the 
sample. The current from the cathode to the anode is conditioned, digitized and transmitted by the associated electronics.

 9.  Overview

Chlorine in Water

Various forms of chlorine are used to disinfect water. Each form of chlorine has bene

fi

 ts and limitations which help determine the 

speci

fi

 c application. The predominant categories used in disinfection are Free Chlorine, Total Chlorine and Chlorine Dioxide. Free 

Chlorine is the sum of chlorine gas (Cl

2

), hypochlorous acid (HOCl) and hypochlorite (OCl

-

). Above pH 4.0 all of the molecular 

chlorine is converted to HOCl and OCl

-

. Hypochlorous acid is a more potent disinfectant than hypochlorite and exists in a pH 

dependent equilibrium as shown in Figure 3.
Free chlorine also combines with naturally occurring or human-introduced nitrogen compounds in the water to form chloramines, also 
known as combined chlorine. Treatment operators introduce ammonia into the water to form monochloramine (NH

2

Cl), dichloramine 

(NHCl

2

) and trichloramine (NCl

3

). Chloramines are a less effective disinfectant but have a longer residence time than the free chlorine 

species. Total chlorine is the sum of free chlorine (Cl

2

, HOCl and OCl

-

) and combined chlorine (NH

2

Cl, NHCl

2

, NCl

3

).

Mount the 

fl

 ow cell where the sensor will be easily accessible.

To avoid air bubble entrapment, do not mount with downward 

fl

 ow.

 8.  Mounting Position continued

Automatic pH Compensation and Free Chlorine

In many applications, the process pH does not signi

fi

 cantly 

fl

 uctuate and only a chlorine sensor and instrument are 

necessary for accurate chlorine measurement.
It is when the pH varies that free chlorine concentration can 
not accurately be determined without the use of automatic pH 
compensation.

The addition of the Signet 3-2724-00 (159 001 545) pH 
electrode along with its 3-2750-7 (159 001 671) preampli

fi

 er 

to the system makes pH compensation extremely easy and 
automatic even with wide 

fl

 uctuations or high pH.

See Figure 4 for pH variation recommendations.

Example

:

If the pH nominal value is 7.5 and the pH variation is ±0.2 then 
automatic pH compensation is recommended.
If the pH nominal value is 7.0 and the pH variation is ±0.2 then 
automatic pH compensation is not required.

                6.5          7.0          7.5            8.0           8.5           9.0

0

±0.3

±0.1

±0.2

=

  pH variation

Sample pH 

   Automatic pH compensation recommended
   in ranges within shaded area

NO

Flow

Figure 3

Figure 4

Summary of Contents for Signet 3-2630 Series

Page 1: ...vice time chlorine range high and low pH with optional Signet pH electrode temperature limits and more are stored on the chip This information is accessible via the Signet 8630 transmitter Signet s pa...

Page 2: ...rane caps carry no warranty Diluted HCl can irritate the eyes and skin use proper safety equipment Do not use surface tension reducing chemicals detergents or solvents on the membrane Electrode Range...

Page 3: ...greater than 2 months 4 If the sensor still fails to work properly continue with steps 11 17 Storage periods greater than 2 months If the sensor has been in storage for a long period of time or used...

Page 4: ...MERGE THE SENSOR See Figure 2 13 Apply power to the system 14 Monitor the nA of the sensor press the down arrow once on the 8630 transmitter The nA reading should start to rise Response time and nA re...

Page 5: ...The predominant categories used in disinfection are Free Chlorine Total Chlorine and Chlorine Dioxide Free Chlorine is the sum of chlorine gas Cl2 hypochlorous acid HOCl and hypochlorite OCl Above pH...

Page 6: ...n water See technical data Surfactants in water Remove surfactants and replace cap Membrane cap coated Clean or replace membrane cap Membrane cap loose Tighten or replace membrane cap pH outside worki...

Page 7: ...Replacement Parts Mfr Part No Code Description 3 2630 391 159 001 674 Free Chlorine electrolyte 30 mL 3 2632 391 159 310 160 Chlorine Dioxide electrolyte solution 30 mL 3 2630 394 159 310 164 Free Chl...

Page 8: ...trode range Sensor Conditioning New first start up 4 hours maximum before calibration Subsequent start ups 2 hours maximum Temperature Element PT1000 Operational Ranges and Limits Free Chlorine Range...

Reviews: