29
2.5
VALVE BOLT TORQUES
VALVE SIZE
MINIMUM BOLT LENGTH (mm)
MAXIMUM TORQUE PER BOLT (Nm)
DN200
420
54
DN250
480
91
DN300
540
104
2.6
FLANGE ADAPTORS
a. Follow steps a-d from section 2.4 within the user specified flange adaptors
b. Place flange adaptor/valve assembly into the pipeline and slide the retaining collars onto the
pipework, ensuring the flow direction is correct.
c. Tighten the retaining collars as per the adaptor manufacturer specifications and proceed with
commissioning.
Summary of Contents for NeoFlow DN200
Page 1: ...Operating instructions NeoFlow Pressure Reducing Valve DN200 DN300...
Page 10: ...10 1 7 BILL OF MATERIALS PRESSURE REDUCING ASSEMBLY...
Page 12: ...12 1 8 BILL OF MATERIALS VALVE BODY...
Page 23: ...23 2 2 2 PERMITTED VALVE ORIENTATIONS Horizontal Orientation Vertical Orientation...
Page 42: ...42...