TS 5000 R-ISM BG
Initial operation
GB 11
7.3 Adjusting electrical hold-open device
Moving leaf is shown.
X
Open door leaf to desired hold-open angle and fix it there (
1.
).
X
Remove cable protection foils from guide (
2.
).
X
Loosen clamping screws of electrical hold-open device (
3.
).
X
Move electrical hold-open device until catch contacts sliding block (
4.
).
X
Screw down electrical hold-open device securely (
5.
).
X
To prevent loops from forming, tighten cable and fasten cable protection at hold open device end (
6.
).
X
Stow away (
7.
) loose cable in the cable protection and free area.
X
Secure exposed cable with the cable protection film (
8.
).
CAUTION!
X
Check free upward movement of the rocker!
9.
Fig.: 7.3.1
If necessary, the holding force can be adjusted (
9.
). According to EN 1155, the release torque should
amount to 40 Nm - 120 Nm for a door with 90° hold- open angle.
7.4 Mounting cover panel
CAUTION!
X
Do not pinch cable.
Fig.: 7.4.1
X
Clip on middle cover panel and moving-leaf cover panel (
1.
).
Check whether the smoke detector opening is located directly over the smoke detector.
X
Insert inspection caps between cover panels (
2.
).