GEZE PERLAN AUT-2 Wiring Diagram Download Page 21

PERLAN AUT-2

21

Fehlerbeseitigung / Fault clearance

If the safety functions recognize a fault, the controller changes to the fault state. 

In this case the driver block and the safety relay are deactivated first.

A fault state is indicated by flashing codes of the two LEDs on the controller:

First the red LED flashes rapidly, then it lights up continuously for approx. 20 seconds. During these 20 seconds 

the green LED flashes in accordance with the fault code x times. The cycle repeats until the user resets the fault.

Example: Green LED flashes 4 times, i.e. Fault code 4. This corresponds to a defective oscillator.

Red LED:

Green LED

The following system states have been defined for the fault recognition:

Fault 

code

Name

Description

Fault elimination

0

System OK

No fault

1

Unknown fault

Unknown cause of fault

 

X

Switch mains voltage off/on.

 

X

Carry out a reset as described in 

Chapter 16.2 .

 

X

Replace the controller if neces-

sary.

2

Self-test – several faults

The self-test has recognised several faults

4

Self-test – oscillator fault

The self-test has recognised a defective 

oscillator

 

X

Replace the controller.

5

Self-test – relay defective

The self-test has recognised a defective 

relay

6

Self-test – driver defective

The self-test has recognised a defective 

driver

7

Self-test – current measure-

ment defective

The current measurement does not func-

tion properly

 

X

Switch mains voltage off/on.

 

X

Carry out a reset as described in 

Chapter 16.2 .

 

X

Replace the motor and/or con-

troller if necessary.

8

Self-test – driver fault recog-

nition defective

The power driver no longer outputs a fault 

message

9

Hardware – encoder fault

The encoder is not connected correctly or 

is defective

 

X

Check the encoder connection.

 

X

Replace the motor or controller.

10

Hardware – voltage impos-

sible

The supply voltage lies outside the per-

missible range

 

X

Replace the power pack.

 

X

Replace the controller if neces-

sary.

11

Memory – RAM defective

A defect has been recognised in the RAM

 

X

Replace the controller.

12

Memory – ROM defective

The programme memory has been 

changed or is defective

13

Memory – EEPROM defec-

tive

The data memory is defective

Summary of Contents for PERLAN AUT-2

Page 1: ...1 GEZE PERLAN AUT 2 DE Set Steuerung GB Set control DE Anschlussplan GB Wiring diagram...

Page 2: ...nted controller with integrated power pack 10 11 Kontaktgeber ffnen Contactor open 12 11 1 Taster potenzialfreier Kontakt Switch floating contact 12 11 2 Funkansteuerung Wireless control 12 12 Kontakt...

Page 3: ...en zum Verst ndnis oder zum Optimieren der Arbeitsabl ufe bedeutet Zus tzliche Information X X Symbol f r eine Handlung Hier m ssen Sie etwas tun X X Halten Sie bei mehreren Handlungsschritten die Rei...

Page 4: ...as defined in the German Produkthaftungs gesetz Product Liability Act the information contained in these instructions product information and proper use misuse product performance product maintenance...

Page 5: ...ktrischer Ger te f r den Hausgebrauch und hnliche Zwecke Unfallverh tungsvorschriften insbesondere BGV A1 VBG1 Allgemeine Vorschriften BGV A3 VBG4 Elektrische Anlagen und Betriebsmittel To ensure pers...

Page 6: ...osed can open too wide and can hit an ob struction If this danger may occur a stop buffer has to be mounted in the open position 5 3 Sicherheitsbewusstes Arbeiten Safety conscious working X X Den Arbe...

Page 7: ...electri cian X X In the case of a power connection carry out a test of the power connection in accordance with VDE 0100 Part 610 Lay the conductors so that single insulation power conductors do not c...

Page 8: ...e Abschalttoleranz des Schiebet rantriebs eingestellt werden Mit dem DIP Schalter kann die genaue Funktionalit t des Schiebet rantriebes gew hlt werden Nach korrektem Anschluss und Inbetriebnahme ist...

Page 9: ...Mat Nr 140101 1 Flush mounted standard connecting box to DIN 49073 provided by customer 2 Controller with integrated power pack 230 V 24 V Mat No 147757 3 1 fold cover frame for vertical installation...

Page 10: ...Unterputzdose 1 verlegen X X Lay the power supply cable for control ler with integrated power pack 2 in the flush mounted box 1 X X Netzzuleitung an die Sicherungsklemm leiste 2 5 mm mit Glassicherun...

Page 11: ...ahmen 1 fach alpinwei UP Mat Nr 115376 Rahmen 2 fach alpinwei UP Mat Nr 115377 Rahmen 3 fach alpinwei UP Mat Nr 115378 Abdeckung AS500 Mat Nr 118480 Aufputzdose 1 fach alpinwei Mat Nr 120503 Aufputzdo...

Page 12: ...utton LS990 flush mounted Mat No 128583 11 2 Funkansteuerung Wireless control X X Montage und Serviceanleitung GEZE Funkpro gramm Automatik beachten Mat Nr 132159 X X Observe the mounting and service...

Page 13: ...at No 139994 Um nicht buskompatible Antriebe an den GEZE Bus anzuschlie en muss das Modul IO220 zwischengeschaltet werden Das Modul IO22 wandelt die Bussignale um X X Bei Anbindung nicht buskompatible...

Page 14: ...button is pressed Semi automatic When the Semi automatic function is activated the drive closes automatically in the desired direction until an obstacle or the end of the system is recognised even if...

Page 15: ...Power switch off Niedrigenergiet ren werden in der Regel nicht mit zus tzlichen Schutzeinrichtungen ausgestattet da die kineti schen Energiewerte als ungef hrlich angesehen werden Im Fall einer Stromu...

Page 16: ...quired for commissioning the functions which have to be set and how to carry out the commissioning step by step The controller is configured at Potentiometer P1 as well as at the DIP switches The func...

Page 17: ...FF the driver closes with half the speed At full closing speed ON the drive closes with full speed Motor generation function Set the DIP switches depending on the motor used Perlan AUT 2 or AUT 1 16 1...

Page 18: ...ekunden dr cken Die rote Leuchtdiode beginnt kontinuierlich zu blinken Laufrichtung pr fen X X Mit Taste AUF Auf fahren bzw mit Taste ZU Zu fahren Wenn Laufrichtung falsch X X Motorkabel drehen Laufri...

Page 19: ...X Swap the motor cables check the direction of movement again X X Press the Reset button again for approx 2 seconds The red LED lights up permanently the yellow LED lights up at motor activity The sli...

Page 20: ...de Systemzust nde definiert worden Fehler code Name Beschreibung Fehlerbehebung 0 System ok Kein Fehler 1 Unbekannter Fehler Unbekannte Fehlerursache X X Netzspannung aus einschalten X X Reset ausf hr...

Page 21: ...lf test has recognised several faults 4 Self test oscillator fault The self test has recognised a defective oscillator X X Replace the controller 5 Self test relay defective The self test has recognis...

Page 22: ...geschraube Aluminium Laufschiene Blende Kunststoff Rollenwagen Elektronikteile Steuerung Taster Kabel Die Teile k nnen beim rtlichen Wertstoffhof oder durch ein Schrottverwertungsunternehmen entsorgt...

Page 23: ...PERLAN AUT 2 23...

Page 24: ...Hungary GEZE Hungary Kft Bart k B la t 105 113 Budapest H 1115 Tel 36 1 481 4670 Fax 36 1 481 4671 E Mail office hungary geze com Iberia GEZE Iberia S R L Pol Ind El Pla C Comerc 2 22 Nave 12 08980 Sa...

Reviews: