Functions and properties
2.4.2 Modules
à
Power module
PM
:
à
24 A or 10 A (depending on switching power supply unit), with MBZ300 N8 max. 8 A possible
à
Power module extension
PME
:
à
24 A or 10 A additionally (depending on switching power supply unit) for the 2nd or 3rd switching power
supply unit
à
Control module
CM
(exactly 1 required for the first fire section):
à
Detector lines (max. 3) and connection for ventilation control
à
USB port
à
Ventilation control commands take priority over the sensor modules (the other fire sections)
à
Sensor module
SM
(for further fire sections) (max. 16 per control panel):
à
Detector lines (max. 3) and connection for ventilation control units (additional)
à
Ventilation control commands have a lower priority than the control module
à
Drive module
DM
or
DME
:
à
Drive line up to a max. of 10 A/20 A (with a corresponding software configuration pressure-gas generators
or hold-open magnets can be triggered, for example)
à
Connection of ventilation control units and operating status displays
à
Weather module
WM
(max. 1 required):
à
Connection of wind and rain sensor and/or of wind direction sensor
à
Relay module
ERM
:
à
6 potential-free status contacts for the notification of error and operating statuses
2.5 Standard control units
The following standard control units are available from GEZE:
MBZ300 standard control units
N8
N10
N24
N48K
N48G
N72
Control cabinet
dimensions
W x H x D [mm]
300 × 400 × 200 400 × 500 × 200 600 × 600 × 250 600 × 600 × 250 600 × 800 × 250 600 × 800 × 250
Mat. no.
185684
137016
137017
137017
137018
137018
Output current for
drives (max.)
8 A
10 A
24 A
48 A
48 A
72 A
Power supplies
(installed)
1×10A
1× 10 A
1× 24 A
2× 24 A
2× 24 A
3× 24 A
Modules (installed) 1×PM
1×CM
1×DM
1× PM
1× CM
1× DM
1× PM
1× CM
3× DM
1× PME
1× PM
1× CM
6× DM
1× PME
1× PM
1× CM
6× DM
2× PME
1× PM
1× CM
9× DM
Fire sections
1
1
1
1
1
1
Ventilation groups 1
1
3
6
6
9
Slots for further
modules
1
8
18
5
13
8
Batteries (can be
inserted)
7 Ah
12 Ah
17 Ah, 24 Ah,
38 Ah
24 Ah, 38 Ah
24 Ah, 38 Ah
38 Ah
Battery connection Tab connector
4.8 mm
Tab connector
6.3 mm
Ring cable lug
M5
Ring cable lug
M5
Ring cable lug
M5
Ring cable lug
M5
Extension options:
à
Further ventilator groups through installation of additional drive modules DM
à
Further fire sections or alarm lines through installation of additional sensor modules SM (not possible with
MBU300 N8)