GEZE hold-open system FA GC 150
29
Wiring diagram
5
Wiring diagram
ú
Note the requirements for selection and installation of the fire detectors and manual trigger switches in chapter 3.5.
ú
In addition, heed the installation instructions for the respective hold-open system.
ú
The connection of the hold-open system to the mains voltage must be carried out by a qualified electrician.
ú
Before working on the electrical system interrupt the power supply and check for safe isolation from the sup-
ply. When an Uninterruptible Power Supply is used, the system will still be under voltage even when discon-
nected from the mains.
ú
Only use the specified cable types.
ú
Marking of on-site cables in these instructions:
1
NYM-J, 3 × 1.5 mm
2
2
NYM-O, 2 × 1.5 mm
2
or NYM-J, 3 × 1.5 mm
2
3
J-Y(ST)Y, 2 × 0.6 mm or J-Y(ST)Y, 2 × 0.8 mm, maximum length smaller than 15 m
4
J-Y(ST)Y, 2 × 0.6 mm or J-Y(ST)Y, 2 × 0.8 mm, maximum length smaller than 6 m
5
J-Y(ST)Y, 2 × 2 × 0.6 mm or J-Y(ST)Y, 2 × 2 × 0.8 mm, maximum length smaller than 15 m
6
J-Y(ST)Y, 2 × 2 × 0.6 mm or J-Y(ST)Y, 2 × 2 × 0.8 mm, maximum length smaller than 6 m
7
J-Y(ST)Y, 2 × 0.6 mm or J-Y(ST)Y, 2 × 0.8 mm, maximum length smaller than 3 m
8
J-Y(ST)Y, 2 × 2 × 0.6 mm or J-Y(ST)Y, 2 × 2 × 0.8 mm, maximum length smaller than 3 m
Non-marked connections are system cables, only these may be used.
ú
The cables must be sufficiently mechanically protected and attached.
ú
Insulate wires that are not used.
5.1 Mains connection
ú
The GEZE hold-open systems are devices of protection rating I
or protection rating II
in accordance
with DIN EN61140.
ú
A 16 A circuit breaker must be provided on site (suitable for the electrical installation).
ú
The 230 V supply must be introduced into the connecting space doubly insulated (with cable sheath) at least 8 mm.
ú
Total power consumption at the power supply max. 260 mA.
5.1.1 Mains connection for protection rating I
Power supply for
TS 4000 R, TS 4000 RFS, TS 4000 R-IS, TS 5000 RFS KB
ID
103354
Cable length 230V / 24V
90 mm / 65 mm
ú
Devices of protection rating I
are connected using a three-core cable NYM-J, 3x1.5 mm
2
.
The protective earth conductor is connected to the PE terminal.
Power supply
GC 151
maximum
1
Fig. 5.1.1.1