GEZE hold-open system FA GC 150
16
Technical data
4.5.1 “Operating” mode
After the supply voltage has been switched on, the wireless module GC 171 is in “operating” mode.
LED displays
In “operating” mode the GC 171 monitors the set-up wireless connections and signals faults and alarms to the
lintel-mounted smoke switch. Faults and alarms are also indicated on the status LED and the wireless device LEDs
of the GC 171. The following table shows the states for various events which are signalled via the set-up wireless
connections:
ú
of the wireless device LEDs of the GC 171
ú
of the status LED of the GC 171
ú
of the LED of the lintel-mounted smoke switch GC 151
ú
of the alarm output and the hold-open output of the lintel-mounted smoke switch GC 151
The wireless module GC 171 indicates an event until the cause has been eliminated. If the cause of an event is no
longer present, the wireless module GC 171 changes back to normal operation (the displays are deleted and 24 V is
applied to the hold-open output of the lintel-mounted smoke switch again).
Wireless module GC 171
(“operating” mode)
Lintel-mounted smoke switch GC 151
Wireless
connec-
tion
State /
fault
Wireless device LED 1x
Sta-
tus
LED
LED
Alarm output
Hold-open
output
KL1: 3-4 /
KL3: 1-2
GC 171
Connection
quality
flashes green
good
flashes yellow
sufficient
flashes red
poor
Off
Green
10
11
12
AL_NC
AL_COM
AL_NO
24 V
General fault Off
Yellow Red
Off
0 V
GC 172
GC 173
General fault Red
Off
Yellow
Red
Off
10
11
12
AL_NC
AL_COM
AL_NO
0 V
Sabotage
Red
Off
Loss of
connection
Red
Off
Low battery
charge
(warning)
Yellow
Off
Green
24 V
Contamination
(warning)
Red/green short
Contamina-
tion limit
reached
Red/green long
Red
Off
0 V
Wireless detec-
tor alarm
Red
Red Red
10
11
12
AL_NC
AL_COM
AL_NO
GC 175
General
fault,
broken cable
Red
Off
Yellow
Red
Off
10
11
12
AL_NC
AL_COM
AL_NO
0 V
Loss of
connection
Red
Off
Low battery
charge
(warning
)
Yellow
Off
Green
24 V
Contact (nor-
mal
l
y open
contact)
activated,
short-circuit
Yellow
Yellow
0 V
Tab. 4.5.1