Establishing a Bluetooth connection
Proceed as follows to pair a data collector and the
Com box for data transfer via Bluetooth:
Switch on the data collector.
Make sure that Bluetooth transmission is
enabled on the data collector.
Launch the VKP 42 app.
Switch on the Com box.
Tap the “Menu” button.
Select the “Bluetooth” submenu.
The “Pair VKPC” submenu opens.
To find Bluetooth sources within receiving
range, tap “Start Bluetooth scan”.
“Finding VKPC…” appears on the display. The data
collector searches for Bluetooth sources within
receiving range.
When the search is over, Com boxes are displayed
with their name and serial number. The name of the
Com box is always “VKPxyz”. The serial number
“xyz” is the same as that shown on the name plate
of the Com box.
To pair the data collector with the desired Com
box, tap the relevant Com box entry.
You can only produce a data connection
between the Com box and one data
collector.
Tap “Continue”.
You will be asked to enter a password. The Com
box password is either “1234” or “0000”.
Enter the password as described in the data
collector Installation & Operating Manual.
The two devices are paired. “Connected VKP” and
the Com box type and serial number appear on the
display. The charge status of the Com box is
displayed.
If an error occurs during pairing, the message
“Pairing error!” is displayed.
In this case, repeat the pairing process for the
two devices.
Using the app to analyse the test data
You can find information on using the data
analysis app in the supplied operating
instructions.
Performing tests
Launch the VKP 42 app.
The main menu is displayed. You will find
information on the main menu on page 16.
To start a test, tap the “Test jobs” or “Perform
test” button.
To find out how to test a steam trap, see page 18.
To perform a rapid test, tap the “Quick Check”
button.
To find out how to perform a rapid test, see
page 23.
To switch the Com Box on briefly press the
ON/OFF button.
For information on the indicating facilities of the
Com Box see page 16.
The measuring probe is switched on as soon as it is
connected to the Com Box and the Com Box is
switched on.
For a test, the following information is required:
Operation
Plant
Plant section
Place of installation
Location
Type
Manufacturer
Installation description
Working pressure (required for measuring the
banking up of condensate)