55
URB 60 - Installation & Operating Manual -
819699-00
Configuring the conductivity controller
Setting the control parameters
Open the control parameter
screen
.
Guide to setting control parameters
Parameter
Control deviation
Continuous blowdown valve
Proportional
band Pb
Pb
> higher
Large offset
Responds slowly
< lower
Small offset
Responds quickly and may open/close
continually
Example:
Measuring range 0 - 6000 µS/cm
Setpoint SP = 3000 µS/cm
Proportional band Pb = +/- 20 % of setpoint = +/- 600 µS/cm
With the measuring range and setpoint mentioned above, the proportional band is
then +/- 600 µS/cm or in the range 2400 µS/cm to 3600 µS/cm.
Reset time
Ti
> higher
Slow correction of deviations
Responds quickly
< lower
Fast correction of deviations, the control
loop may tend to overshoot
Responds slowly
Neutral
zone
> higher
Correction of deviations starts with a
delay
In this range, the control point does
not change.
Responds only if the control
deviation is larger than the neutral
zone.
< lower
Correction of deviations starts rapidly
Valve runtime
Establish the real valve runtime, e.g.
from Closed to Open (0 - 100 %).
Fig. 10