38
URB 60 - Installation & Operating Manual -
819699-00
Device settings
Calibrating the display:
1.
Tap “
Calibrate”
next to Display.
2.
You will then be prompted to tap the “
Calibra-
tion
” button in the “
Touch Properties
” menu
(
see “Calibrating the display 1”
).
3.
A blank window with a target in the centre
then opens (see
“Calibrating the display 2”
).
4.
Press the target for approx. 3 seconds using a
long, blunt object (stylus).
5.
The target then automatically marks the four
corner coordinates.
6.
To calibrate them, press and hold the target
(cross cursor) on each corner and hold for
approx. 3 seconds.
7.
Apply this calibration within 30 seconds by
tapping the display.
8.
Finally, you will see the message “
Recalibra-
tion was successful
”.
9.
OK
Tap “OK” to confirm, and then
again to quit the
“
Touch Properties
” menu.
Calibrating the display 1
Calibrating the display 2