40
Commissioning
– continued –
Calibrating the feedback potentiometer of an external control valve
– continued –
Press and hold down button
until the control
valve is closed.
Press button
once briefly to save the current
resistance value of the feedback potentiometer as
0 % setting (valve CLOSED).
Press button
3 times briefly to activate the line
editing mode for calibrating the signal of the feed-
back potentiometer.
P
100%
M
0%
P
NRR 2-40
1
100%
M
0%
P
NRR 2-40
1
E
100%
M
0%
P
NRR 2-40
1
flashing
flashing
3 times briefly
hold down
once briefly