6
System components
NRG 26-40
Level electrode NRG 2640, PN 40
Design
NRS 2-40
Enclosure made from insulating material with box terminals for installation in control cabinets.
The terminals are externally accessible.
Mounting on a standardised supporting rail TS 35 x 15 DIN EN 50022.
External dimensions: 73 x 100 x 118
Scope of supply
NRS 2-40
1 Level switch type NRS 240 (plugin unit in plastic case with box terminals)
1 Terminating resistor 120 Ω
1 Installation & Operating manual
Description
Use level switch type NRS 240 in combination with level electrode type NRG 2640 for level
monitoring. The level switch has the following functions:
n
Four liquid levels with one switchpoint each.
n
Highlevel alarm, lowlevel alarm, pump ON, pump OFF, with one switchpoint each.
n
Continuous level monitoring within control band defined by two preset limits.
n
Actualvalue output 420 mA
n
Contact multiplication by connecting in parallel a second level switch NRS 240 without actual
value output.
The level data are transmitted via CANbus from the electrode NRG 2640 to the level controller or
further system components.
Explanatory Notes
Function
At regular intervals the level electrode type NRG 2640 sends a data telegram to the level switch
NRS 240. The data transfer is effected by means of a CAN bus according to DIN ISO 11898. The
transferred measuring data are then evaluated and assigned to the manually adjusted switchpoints.
To guarantee the correct functioning and safety of the system the data transmitting cycle is constantly
monitored by the level switch. When the CAN bus line is interrupted the level switch sends a visual
signal to indicate a malfunction and the relays 1 and 4 will be instantaneously deenergized (alarm
position).
Additional functions, e.g. (de)energizing delay times of the output relays (1 to 25 sec.) can be adjusted
with the control terminal and display unit URB 1 / URB 2.