6
NRS 19
Technical Data
Type approval no.
TÜV · WR/WB · 04-70
EG 0 0 9-B0-0075
Input
8 connections for one level electrode NRG 6-6, PN 40
Output contacts
For level limiter part:
Two volt-free relay contacts
For level controller part:
One volt-free working contact for feedwater on-off control.
One volt-free relay contact for high level alarm.
Contact material silver, hard gold plated.
Max. contact rating with switching voltages of 4 V, 5 V and 0 V a.c.:
4 A resistive, 0.75 A inductive at cos
j
0.5
Max. contact rating with switching voltage of 4 V d.c.: 4 A
Delay of response
The low water level alarm signal is factory set to react after a time delay of
or seconds (up to 5 sec. delay is possible).
The controller as well as the high water level alarm signal is factory set to react after a time delay of
seconds.
Sensitivity
Range : 0
µ
S/cm at 5 °C
Range : 0.5
µ
S/cm at 5 °C
The selection of the above range is done via a code switch.
Indicators and adjustors
One green LED “Power”, two LEDs “Low level alarm”, one test button “TEST ”, one toggle switch
“TEST /INSPECTION”, one LED “Feedwater control on”, one LED “High level alarm” and one four-
pole code switch.
Mains supply
0 V +/– 0 %, 50/60 Hz (please state voltage when ordering)
Special voltage: 5 V +/– 0 %, 50/60 Hz or 4 V +/– 0 %, 50/60 Hz;
4 V d. c. supply is also possible with the inverter type URN-.
Protection
IP 0 in accordance with DIN 40050
Admissible ambient temperature
0 to 55 °C
Case materials
Base: ABS plastic, black. Cover: polystyrene, highly shock resistant, stone grey.
Weight
0.6 kg
Summary of Contents for NRS 1-9
Page 2: ... Diese Seite bleibt absichtlich frei ...
Page 3: ... Deutsch D Seite 4 21 English Page 22 39 ...
Page 10: ...10 Technische Daten Fortsetzung Maße Fig 2 Fig 3 D 5 120 75 37 5 158 95 ...
Page 11: ...11 Aufbau Fig 6 E B C F D D Fig 4 Fig 5 F A NRS 1 9 D D ...
Page 12: ...12 Funktionselemente NRS 1 9 Fig 7 D G 1 2 3 4 5 6 ...
Page 15: ...15 H C I B A Einbau Fortsetzung Fig 9 Fig 8 Einbaubeispiele F F D ...
Page 28: ...28 Technical Data continued Dimensions Fig 2 Fig 3 5 120 75 37 5 158 95 ...
Page 29: ...29 Design NRS 1 9 Fig 6 E B C F D D Fig 4 Fig 5 D F A ...
Page 30: ...30 Functional Elements NRS 1 9 Fig 7 G 1 2 3 4 5 6 ...
Page 33: ...33 Installation continued Examples of installation H C I B A Fig 9 Fig 8 F F ...
Page 35: ...35 Wiring continued Wiring diagram Fig 10 NRS 1 9 NRG 16 36 1 4 3 2 1 4 3 2 ...