24
NRR 2-50, NRR 2-51 - USA - Installation & Operating Manual -
850699-00
In the plant:
Electrically connecting the level transmitter
Connecting the level transmitter
When used as intended, the NRR 2-50, NRR 2-51 level controller can be combined in a circuit
with the NRGT 26-2 level transmitter.
Please use a shielded, multi-core TC-ER control cable with minimum wire size AWG18, e.g.,
OELFLEX CONTROL TM CY 5G1, to connect the equipment. Max. length 328 ft (100 m).
Connect the shield as shown in the wiring diagram.
Attention
■
Please bring the equipment into service as described in the NRGT 26-2 Installa-
tion & Operating Manual.
■
Route the connecting cable between items of equipment separately from power
lines.
■
The level control system must be connected to its own dedicated supply voltage.