NRR 2-50, NRR 2-51 - USA - Installation & Operating Manual -
850699-00
Operating the level controller
Meaning of codes on the 7-segment display
Code
Meaning
Indicated when rotary knob is turned clockwise:
AL.Hi
Alarm High
MAX switchpoint
Adjustable between 0 and 100%
AL.Lo
Alarm Low
MIN switchpoint
SP
Set point
Set point
Pb
Proportional band Adjustable between 0 and 100%
ti
Time integral
Integral action time, adjustable between 0 and 100 seconds
tt
Motor travel time Valve travel time (NRR 2-50 only), adjustable
between 10 and 600 seconds
tESt
Test
Test of output relays
CAL.L
Calibrate Low Only if NRG 21-.. or
NRG 26-21 level
electrode is connected
Sets lower bound of measuring range
CAL.P
Calibrate %
Adjustable between 25 and 100%
CAL.H
Calibrate High
Sets upper bound of measuring range
Indicated in parameterization mode
quit
Quit
Entry is not confirmed
done
Done
Entry is confirmed
Indicated in the event of errors
E.005
Error
Faulty level electrode/transmitter, measuring voltage/current too low
E.006
Error
Faulty level electrode/transmitter, measuring voltage/current too high
E.013
Error
MIN switchpoint higher than MAX switchpoint