22
LRS 1-50 - USA - Installation & Operating Manual -
850704-01
Operating the conductivity switch
Meaning of codes on the 7-segment display
Code Meaning
Indicated when rotary knob is turned clockwise:
AL.Hi Alarm High
MAX switchpoint
Adjustable from 0.5 to 5000 ppm
(1 to 9999 µS/cm)
AL.Lo Alarm Low
MIN switchpoint
CAL
Electrode calibration
Electrode calibration, last reading is shown
CF
Correction factor
Adjustable from 0.05 to 5.000
in increments of 0.001
inP
Input for Pt100
Temperature compensation YES (no)
tC
Temperature
coefficient
T
k
0.0 – 3.0% per °C, adjustable in increments of 0.1
tESt
Test
Test of output relays
FiLt
Filter
Switching the filter on/off (damping)
PW
Password
on = password protection is enabled oFF = password protection is disabled
Factory default
settings
1902 (cannot be changed)
Indicated in parameterization mode
quit
Quit
Entry is not confirmed
done Done
Entry is confirmed
Indicated in the event of errors
E.001 Error
Faulty temperature sensor, temperature reading too low
E.002 Error
Faulty temperature sensor, temperature reading too high
E.005 Error
Faulty measured value acquisition, reading too low
E.006 Error
Faulty measured value acquisition, reading too high
E.013 Error
MIN switchpoint higher than MAX switchpoint