LRS 1-50 - USA - Installation & Operating Manual -
850704-01
Factory default settings
DANGER
There is a risk of electric shock during work on electrical systems.
■
Switch off the voltage to the plant before you install the equipment.
■
Check that the plant is not carrying live voltage before commencing work.
Conductivity Switch LRS 1-50
■
MAX switchpoint AL.Hi = 3000 ppm (6000 µS/cm)
■
MIN AL.Lo = 250 ppm (500 µS/cm)
■
Switching hysteresis: +/– 3% (factory default)
■
Correction factor CF: 1
■
Temperature compensation inP: No
■
Temperature coefficient tC: 2.1% / °C
■
Damping FiLt: oFF
■
Password PW: oFF
■
Code switch
a
: All switches OFF.