Operation
- continued -
Testing MIN/MAX alarm, entering date and time
Screen display 1
Press button to open the information window
Screen display 15
Testing MIN alarm
Press and hold down button
L
for at least
3 sec. After the de-energizing delay the output
contact 17-18 opens and the respective con-
tact icon turns red.
Testing MAX alarm
Press and hold down button
M
for at least
3 sec. After the de-energizing delay the out-
put contact 26-27 opens and the respective
contact icon turns red.
Press button to open the time/date window
Press button to go back to screen display
15.
Screen display 16
Press the green button and use the on-screen
numberpad to enter the day, month, year and
hours, minutes and seconds. To change the
date and time use the +/- keys.
L
M