19
Operating the conductivity controller
Key to codes on seven-segment display
Fig. 5
Rotary button
with integrated
push-button
MAX LED red
5432
Seven-segment
display
LED 1
Valve opens
LED 2
Valve closes
Code
Description
Indicated when rotary button is turned to the right:
AL.Hi
Alarm High
MAX switchpoint, adjustable between 1 and 9999 μS/cm
SP
Setpoint
Setpoint, adjustable between 1 and 9999 μS/cm
HySt
Hysteresis
Reset hysteresis, adjustable between 1 and 25 % of the setpoint
Indicated when in parameterization mode:
quit
Quit
Input not confirmed
done
Done
Input confirmed
Indicated if malfunctions occur:
E.001
Error
Temperature sensor defective, temperature reading too low
E.002
Error
Temperature sensor defective, temperature reading too high
E.005
Error
Sensor defective, measured value too low
E.006
Error
Sensor defective, measured value too high
Only LRR 1-50
CF
Correction
Factor
Correction factor, adjustable between 0.05
and 5,000, adjustable in increments of 0.001
inP input Pt 100 Temperature compensation YES (no)
tC
Temperature
coefficient
Temperature coefficient Tk 0.0 – 3.0 %
per °C, adjustable in increments of 0.1
Only LRR 1-51
Sin.L Lower end of measuring range, adjustable
0.0 - 0.5 - 100.0 μS/cm
Sin.H
Upper end of measuring range, adjustable
20.0 - 100.0 - 200.0 - 500.0 -1000.0 -
2000.0 - 3000.0 - 5000.0 - 6000.0 -
7000.0 - 9999.0 μS/cm
Sout
Standardization of current output adjustable between 1 and
9999 μS/cm
Si
Purging pulse, adjustable between 0 and 24 hrs in steps of 1 h.
Sd
Purging duration, adjustable between 1 and 4 minutes, in steps
of 1 min.
tESt
Test
Tests output relays