Taking out of service/Disassembly
DANGER
Danger to life from scalding caused by the sudden escape of hot steam.
Hot steam or hot water can escape suddenly if the conductivity electrode is unscrewed while
under pressure.
■
■
Reduce the boiler pressure to 0 bar and check the pressure before you unscrew the
conductivity electrode.
■
■
Only remove the conductivity electrode at a boiler pressure of 0 bar.
WARNING
The hot conductivity electrode can cause severe burns.
The conductivity electrode becomes extremely hot during operation.
■
■
Perform installation and maintenance work only when the conductivity electrode has been
allowed to cool.
■
■
Only remove conductivity electrodes that have cooled down.
Proceed as follows:
1.
Reduce the boiler pressure to 0 bar.
2.
Allow the conductivity electrode to cool to room temperature.
3.
Switch off the supply voltage.
4.
Detach the plug-in connection.
5.
Next, remove the conductivity electrode.