You can recognise and remedy faults due to
incorrect settings as follows:
Normal condensate level Banking-up of
condensate
Penetration of live steam
if medium throughput is
excessive
Penetration of live steam
due to leaks or other
major disruptions
–
Condensate covers the
entire sight glass. No flow
is visible.
The condensate in the
sight glass is being
suppressed. There is a
clearly visible flow.
The sight glass is nearly
opaque.
Do not change the
settings.
Open the equipment until
a normal condensate
level is displayed.
Close the equipment until
a normal condensate
level is displayed.
Close the equipment until
a normal condensate
level is displayed.
Check that the part of the
system and the
equipment are not
leaking and are in perfect
condition.
Fix leaks and damages.
Setting the equipment is described on page 13.
If faults occur that are not listed above or cannot
be corrected, please contact our Technical
Service or authorized agency in your country.