GeoSmart ECO-Y Installation Manual Download Page 18

18

ECO-Y INSTALLATION MANUAL

Blower Performance Data - X13 ECM

 Model

Motor

Spd

Motor

Tap

Blower

Size

Motor

HP

Airflow (cfm) at External Static Pressure (in . wg)

0 .00 0 .05 0 .10 0 .15 0 .20 0 .25 0 .30 0 .35 0 .40 0 .45 0 .50 0 .60 0 .70 0 .80 0 .90 1 .00

024

High

5

9 x 7

1/2

980

960

940

930

920

905

890

875

860

840

820

800

745

-

-

-

Med High

4

890

878

865

845

825

813

800

785

770

753

735

710

665

-

-

-

Med

3

830

815

800

788

775

755

735

723

710

690

670

640

600

-

-

-

Med Low

2

780

760

740

703

665

653

640

620

600

585

570

-

-

-

-

-

Low

1

625

593

560

535

510

495

480

455

430

410

390

-

-

-

-

-

030

High

5

9 x 7

1/2

1340 1310 1280 1240 1200 1170 1140 1095 1050 1015

980

900

800

-

-

-

Med High

4

1130 1115 1100 1085 1070 1057 1044 1022 1000

970

940

870

780

-

-

-

Med

3

1030 1005

980

965

950

935

920

900

880

870

860

830

750

-

-

-

Med Low

2

960

945

930

915

900

885

870

855

840

825

810

790

740

-

-

-

Low

1

790

765

740

725

710

690

670

660

650

630

610

580

500

-

-

-

036

High

5

9 x 7

1/2

1370 1345 1320 1285 1250 1220 1190 1158 1125 1085 1045

960

-

-

-

-

Med High

4

1265 1253 1240 1220 1200 1175 1150 1120 1090 1053 1015

-

-

-

-

-

Med

3

1160 1143 1125 1113 1100 1085 1070 1055 1040 1020 1000

-

-

-

-

-

Med Low

2

1110 1095 1080 1065 1050 1038 1025 1008

990

980

970

-

-

-

-

-

Low

1

825

803

780

770

760

740

720

705

690

670

650

-

-

-

-

-

042

High

5

11 x 10

1

1840 1825 1810 1790 1770 1745 1720 1700 1680 1660 1640 1600 1570 1530 1480

-

Med High

4

1730 1713 1695 1670 1645 1623 1600 1575 1550 1535 1520 1480 1440 1390 1350

-

Med

3

1630 1610 1590 1563 1535 1513 1490 1470 1450 1425 1400 1370 1330 1290

-

-

Med Low

2

1550 1520 1490 1465 1440 1415 1390 1370 1350 1330 1310 1260 1220 1180

-

-

Low

1

1380 1340 1300 1275 1250 1225 1200 1175 1150 1125 1100 1030

980

820

-

-

048

High

5

11 x 10

1

2060 2045 2030 2015 2000 1970 1940 1925 1910 1890 1870 1830 1800 1750 1740

-

Med High

4

1880 1860 1840 1825 1810 1785 1760 1740 1720 1705 1690 1640 1610 1570 1535

-

Med

3

1790 1770 1750 1730 1710 1685 1660 1640 1620 1600 1580 1550 1510 1460

-

-

Med Low

2

1670 1650 1630 1605 1580 1555 1530 1510 1490 1470 1450 1410 1370 1340

-

-

Low

1

1430 1405 1380 1353 1325 1303 1280 1255 1230 1210 1190 1130 1070

925

-

-

060

High

5

11 x 10

1

2400 2360 2330 2315 2300 2290 2285 2275 2265 2250 2230 2200 2165 2110 2080 2030

Med High

4

2180 2160 2140 2130 2120 2105 2090 2075 2060 2045 2030 2000 1960 1930 1890 1850

Med

3

2080 2050 2020 2010 2000 1985 1970 1955 1940 1925 1910 1870 1840 1800 1760 1720

Med Low

2

1930 1920 1910 1893 1875 1863 1850 1833 1815 1798 1780 1740 1700 1660 1620 1590

Low

1

1750 1735 1720 1698 1675 1658 1640 1620 1600 1583 1565 1525 1490 1450 1410 1350

070

High

5

11 x 10

1

2400 2360 2330 2315 2300 2290 2285 2275 2265 2250 2230 2200 2165 2110 2080 2030

Med High

4

2180 2160 2140 2130 2120 2105 2090 2075 2060 2045 2030 2000 1960 1930 1890 1850

Med

3

2080 2050 2020 2010 2000 1985 1970 1955 1940 1925 1910 1870 1840 1800 1760 1720

Med Low

2

1930 1920 1910 1893 1875 1863 1850 1833 1815 1798 1780 1740 1700 1660 1620 1590

Low

1

1750 1735 1720 1698 1675 1658 1640 1620 1600 1583 1565 1525 1490 1450 1410 1350

11/13/09

Factory settings are in Bold

Air flow values are with dry coil and standard filter

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). 

Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12 in. wg. and 500 fpm by 0.16 in. wg.

ISO/AHRI rating  point on the YS070 will require moving the red wire on the motor to high speed (tap 5) and disconnecting the tan wire from tap 5.

Summary of Contents for ECO-Y

Page 1: ...tion Maintenance Manual Geothermal Water Source Heat Pump R 410A Refrigerant 2 6 Ton Installation Information Water Piping Connections Hot Water Generator Connections Electrical Startup Procedures Tro...

Page 2: ......

Page 3: ...tallation 14 Antifreeze Corrections 15 Auxiliary Heat Ratings 15 Electrical Data 16 Blower Performance Data 17 18 X13 ECM Constant Torque Motors 19 Vertical Dimensional Data 20 21 Horizontal Dimension...

Page 4: ...L Left Painted R Right Painted Voltage 1 208 230 60 1 Hot Water Options 0 No Hot Water Generation No GeoStart 1 Hot Water Generation with factory installed pump No GeoStart 3 No Hot Water Generation...

Page 5: ...units for shipping damage removing the units from the packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on...

Page 6: ...figure on page 7 The unit should be pitched approximately 1 4 inch towards the drain in both directions to facilitate the removal of condensate Use only the bolts provided in the kit to attach hanger...

Page 7: ...93 156 81 73 403 kg 42 71 37 33 183 070 lb 143 137 124 34 438 kg 65 62 56 15 199 10 28 09 Corner 1 Corner 2 Corner 3 Corner 4 Horizontal Models Unit Hanger Dimensions A B C D 024 036 in 21 1 63 4 24 8...

Page 8: ...n water connections on the unit The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant to water heat exchanger All source water connections on...

Page 9: ...n 5 ppm Ammonia Hydroxide Less than 5 ppm Less than 5 ppm Less than 5 ppm Ammonia Sulfate Less than 5 ppm Less than 5 ppm Less than 5 ppm Total Dissolved Solids TDS Less than 1000 ppm 1000 1500 ppm 10...

Page 10: ...eeze solution is used in most areas to prevent freezing Flush the system adequately to remove as much air as possible then pressurize the loop to a static pressure of 40 50 PSI summer or 50 75 PSI win...

Page 11: ...er Flow Control Valve on outlet of Solenoid Valve Compressor Line Voltage Open System Groundwater Application Open Loop Ground Water Systems Discharge water from the unit is not contaminated in any ma...

Page 12: ...enerator Installation In Preheat Tank In Ball Valve 3 4 x 3 4 x 1 2 tee Cold Water In Hot Water Out P T Relief Valve P T Relief Valve DHW Water In DHW Water Out Drain Valve Drain Valve Vent NOTE This...

Page 13: ...tor pump will not operate until this wire is connected to the contactor 2 Close the drain valve to the water heater 3 Open the cold water supply to the tank 4 Open a hot water faucet in the building t...

Page 14: ...the subbase Mark the position of the subbase mounting holes and drill holes with a 3 16 inch bit Install supplied anchors and secure base to the wall Thermostat wire must be 8 conductor 18 AWG wire S...

Page 15: ...323 50 0 920 0 833 1 399 Warning Gray area represents antifreeze concentrations greater than 35 by weight and should be avoided due to the extreme performance penalty they represent Auxiliary Heat Rat...

Page 16: ...LA Ext Loop FLA Blower Motor FLA Total Unit FLA Min Circ Amp Max Fuse HACR MCC RLA LRA LRA 024 ZP20K5E PFV 208 230 60 1 187 253 21 0 13 5 58 3 21 0 0 4 5 4 1 2 20 5 23 9 35 024 ZP20K5E PFV 208 230 60...

Page 17: ...0 1 2 1705 1685 1665 1645 1625 1595 1565 1530 1500 1450 1405 1260 1140 M 1485 1475 1465 1445 1430 1410 1390 1350 1315 1260 1210 1110 1010 L 1180 1165 1150 1135 1120 1090 1060 1030 1000 965 920 855 048...

Page 18: ...11 x 10 1 2060 2045 2030 2015 2000 1970 1940 1925 1910 1890 1870 1830 1800 1750 1740 Med High 4 1880 1860 1840 1825 1810 1785 1760 1740 1720 1705 1690 1640 1610 1570 1535 Med 3 1790 1770 1750 1730 171...

Page 19: ...ed accordingly The X13 motor is powered by 208 230VAC but the motor speed is energized by 24VAC Power Connection 3 16 in quick connects Line 1 orange wire to L Ground green wire to G Line 2 for 208V 2...

Page 20: ...tical Dimensional Data Left Return Left Front Top Right Return Top Front Right 10 22 09 B A J K L D E H F G Z Y C J K L D E H F G A B C Y U V R Q P S N M R T Q P V X W X W U N M Z Service Access 2 ft...

Page 21: ...10 6 1 Swivel 1 Swivel 6 5 12 2 17 9 5 9 3 3 cm 64 5 79 8 148 3 5 8 18 5 40 4 48 0 26 9 16 5 31 0 45 5 15 0 8 4 Vertical Dimensional Data cont Condensate is 3 4 in PVC female glue socket and is switc...

Page 22: ...9 13 7 15 7 2 5 cm 64 8 195 6 53 8 5 6 18 3 40 1 47 8 2 0 Swivel Swivel 15 0 34 8 39 9 15 0 34 8 39 9 6 4 070 in 25 5 82 0 21 2 2 2 7 2 15 8 18 8 0 8 1 1 5 9 13 7 15 7 5 9 13 7 15 7 2 5 cm 64 8 208 3...

Page 23: ...24 x 20 610 x 542 28 x 20 711 x 542 28 x 25 711 x 635 28 x 25 711 x 635 32 x 25 813 x 635 36 x 25 914 x 635 Air Coil Total Face Area ft2 m2 3 3 0 310 3 3 0 310 3 9 0 362 4 9 0 451 4 9 0 451 5 6 0 516...

Page 24: ...Flow Fan Status DHW Limit HWD SW2 OFF ON FD Green Blue L2 L1 T1 T2 CB2 CB1 5 A M P 5 A M P NOTE 2 Black Black AuxiliaryE 2 2 3 L4 L2 Pink Yel Blk Grn P9 Brn Or 5 4 C 1 P10 2 3 P2 1 G C 1 2 3 4 P1 PS 1...

Page 25: ...lugs L1 L2 and L3 L4 Blue Blue Auxiliary Electric Heat Typical schematic shown Model Vertical Horizizontal 024 M ed M ed 030 M ed M ed 036 High High 042 M ed M ed 048 High High 060 M ed M ed 070 High...

Page 26: ...1 3 2 Yellow Black Red 208V Blue 230V Cap NOTE 3 NOTE 1 Black White Blue Black Y2 1 2 3 L N G X13 Fan Motor C 4 5 Green Orange Brown Red ExtPump 1 2 hp Total 208 230 60 1 Pump G 2 1 PB1 1 2 Pump Gray...

Page 27: ...ection Table PB2 Auxiliary Electric Heat Power 208 230 60 1 With optional Field Installed EA Series 2 3 HE1 TS1 HE2 TS2 HE3 TS3 HE4 TS4 P7 L4 L2 L2 NOTE 4 Pink Yel Blk Gray Pink Yel Blk Gray Gray Blk...

Page 28: ...switch to prevent loss of charge damage and a low suction temperature thermistor for freeze sensing Upon a continuous 30 second measurement of the fault immediate for high pressure compressor operatio...

Page 29: ...int well 30 F or loop 15 F for 30 continuous seconds Condensate Overflow This lockout mode occurs when the condensate overflow level has been reached for 30 continuous seconds Controls cont DIP Switch...

Page 30: ...ill energize after a time delay 4 Be sure that the compressor and water control valve or loop pump s are activated 5 Verify that the water flow rate is correct by measuring the pressure drop through t...

Page 31: ...e Lockout Air Flow Not Used Status Micoprocessor Malfunction HW Limit Not Used HW SW2 Status Off Down Position On Up Position Diagnostic Display Modes Current Fault Display Mode Inputs Display Mode Ou...

Page 32: ...water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE COAX LOAD HEATING CYCLE ANALYSIS EXPA...

Page 33: ...her two factors must be at the normal level for proper and reliable unit operation Entering Water Temp F Water Flow GPM Ton Cooling No Hot Water Generation Suction Pressure PSIG Discharge Pressure PSI...

Page 34: ...igh Normal High Normal Low Normal Low Air Flow Heating High High High High Normal Low High Low Low Air Flow Cooling Low Low Low Low Normal High High Low Low Water Flow Heating Low Normal Low Normal Lo...

Page 35: ...apacity MBTUH S T sensible to total cooling ratio HE HR Table Model GPM Heat of Extraction Heat of Rejection 30 F 50 F 70 F 90 F 30 F 50 F 70 F 90 F 110 F 024 3 0 14 7 19 4 23 6 28 2 27 8 26 2 4 5 10...

Page 36: ...ailable High Static PSC Blower Housing 53P512B01 Not Available 53P517 02 Not Available Major Components Air Coil coated 61S503C02 61S548 02 61S505C02 61S506C02 61S507C02 Coax Copper 62I572 01 62I566 0...

Page 37: ...Not Available High Static PSC Blower Housing 53P512B01 Not Available 53P517 02 Not Available Major Components Air Coil coated 61S509C02 61S510C02 61S511C02 61S512C02 61S513C02 Coax Copper 62I572 01 62...